Confusing indirect water heater outputs #2187

@shorowit

Description

@shorowit

A user reported that the hot water gallons outputs for an indirect water heater (base-dhw-indirect.xml) are much lower than that of a conventional water heater (base.xml). We've seen this before for HPWHs (see here), but in that case it is much more complicated due to the use of a stratified tank. In this case, we have a mixed tank, so it should be more straightforward.

@yzhou601 and I briefly started to investigate and noticed that the Water Heater Use Side Outlet Temperature for the indirect water heater is 1 deg-C higher than the standard water heater, so that's part of it. That appears to be caused by the fact that we are using the same (upper) tank setpoint in both cases, but the indirect water heater setpoint does not actually use a deadband? We quickly tried to address that, but the hot water gallons outputs were still far too low (though they did increase a bit).

So the question is... are we modeling the wrong hot water use? Or is it just a reporting issue? The hot water delivered energy is pretty similar between the two cases, so that may suggest that it's just a reporting issue.