This document describes the LED status codes specific to the OAM-NeoPixel module. All NeoPixel diagnostics are shown exclusively on the STATUS LED.

Design

Condition LED Colour Effect Identifiable?
Error STATUS Red errorCode(N) — N× blink, pause, repeat Yes — count the blinks
Warning STATUS Orange / Yellow pulsing() — smooth sine-wave breathing By colour only — check serial log for details

Errors take visual priority over warnings. If both exist, only the error is shown (the warning is still logged to serial).

LED Priority System (OpenKNX Framework)

The STATUS LED follows the OpenKNX priority chain. Higher priority always wins:

Priority Mode Used by
1 PowerSave (LED off) Flash save operations
2 errorCode(N) NeoPixel errors (this module)
3 Heartbeat Debug heartbeat (if enabled)
4 ForceOn KNX programming mode
5 pulsing() NeoPixel warnings (this module)

Severity Logic

When multiple errors or warnings occur, only the most severe is displayed:

  • Lower code number = higher severity (code 1 wins over code 3)
  • An active error (Prio 2) suppresses all warnings (Prio 5) on the same LED
  • Codes persist until device restart

Error Codes (STATUS LED, Red, countable blinks)

These indicate critical configuration or hardware failures that prevent normal operation.

Code Blinks Condition Description Resolution
NEO_ERROR_HW_MISMATCH Hardware Mismatch Firmware compiled for different hardware than ETS configuration. GPIO port mappings from ETS are ignored to prevent damage. Flash correct firmware, or update hardware selection in ETS (use "Hardware auto-detect").
NEO_ERROR_NO_HW_CONFIGURED No Hardware Configured ETS has dummy value (255) — no board selected yet. Open ETS and select correct hardware or use "Hardware auto-detect".
NEO_ERROR_GPIO_CONFLICT GPIO Pin Conflict Multiple strips or relays share the same GPIO pin. Conflicting strips are skipped. Check ETS strip and relay configuration for duplicate GPIO assignments.
NEO_ERROR_STRIP_FAILED Strip Creation Failed Physical LED strip could not be created (nullptr). Memory exhaustion or driver failure. Reduce strip/LED count. Check SPI configuration.
NEO_ERROR_VSTRIP_FAILED Virtual Strip Failed Virtual strip could not be created — no LED output possible. Ensure at least one physical strip was created. Check serial log.

Warning Codes (STATUS LED, pulsing / breathing)

These indicate non-critical issues. The device continues to operate with limitations. Warnings use a smooth breathing effect — the colour indicates the type of warning. For the exact warning, connect a serial console.

Code Colour Condition Description Resolution
NEO_WARN_ABL_ACTIVE Orange Auto Brightness Limiting Power consumption >= 95% of limit. Brightness is being reduced. Increase power limit, reduce LEDs/brightness, or upgrade power supply.
NEO_WARN_FLASH_DISCARDED Purple Flash Data Discarded Saved states don't match current config (e.g., segment count changed). Default startup behaviour used. Expected after ETS config changes. Clears after next save cycle.
NEO_WARN_UNKNOWN_EFFECT Yellow Unknown Effect Type Effect configured in ETS not recognized by firmware. Update firmware or change effect type in ETS.

Quick Identification Guide

What you see on STATUS LED Meaning
Red, 1× blink Hardware mismatch (firmware vs ETS)
Red, 2× blink No hardware selected in ETS
Red, 3× blink GPIO pin conflict
Red, 4× blink Strip creation failed
Red, 5× blink Virtual strip creation failed
Orange, breathing Power limit active
Purple, breathing Flash data discarded (config changed)
Yellow, breathing Unknown effect type
No indication Everything OK

OpenKNX Framework Fatal Errors (PROG LED, for reference)

These are defined by OGM-Common, not by OAM-NeoPixel. They use the PROG LED (Red) and halt the device completely.

Code Blinks Condition
FATAL_FLASH_PARAMETERS Flash parameter error
FATAL_I2C_BUSY I2C bus busy during startup
FATAL_LOG_WRONG_CHANNEL_COUNT knxprod channel count mismatch
FATAL_SENS_UNKNOWN Unknown or unsupported sensor
FATAL_SCHEDULE_MAX_CALLBACKS Too many scheduler callbacks
FATAL_NETWORK Network error
FATAL_INIT_FILESYSTEM 10× LittleFS initialization failed
FATAL_SYSTEM 20× System error (e.g., buffer overrun)