Prometheus metrics

Heliograph exposes its state in the Prometheus text exposition format at GET /metrics. Nothing needs enabling: if the firmware was built with Prometheus support (all release images are), the endpoint is live as soon as the bridge is on the network.

curl http://heliograph-a1b2c3.local/metrics

The endpoint is also readable by anything that speaks the same format — Zabbix, Checkmk and Telegraf can all scrape it directly, and Grafana can graph it through any of them.

How to scrape it

Add the bridge as a normal static target. It is a small, cheap endpoint — a few kilobytes of text — but there is no point scraping faster than the inverter is polled: the default poll interval is 10 seconds, so anything under that just repeats a sample.

scrape_configs:
  - job_name: heliograph
    scrape_interval: 30s
    static_configs:
      - targets: ["heliograph-a1b2c3.local:80"]

Prefer the IP address if your Prometheus host cannot resolve mDNS .local names — many containers cannot.

Response codes

Code Meaning
200 Metrics, Content-Type: text/plain; version=0.0.4
503 No device configured yet — body is # no device configured

The 503 is deliberate: a freshly provisioned bridge with no driver selected has nothing to report, and reporting zeroes would be worse than reporting nothing. Prometheus marks the target down, which is exactly what it is.

Authentication

There is none on /metrics. Every mutating endpoint in the REST API is admin-gated, but this one is a read-only scrape target and is deliberately left open so a scraper needs no credentials.

That means anyone on your network can read your production figures, your firmware version and your board type. On a home LAN that is normally fine. If it is not, put the bridge on a segregated VLAN and let only the scraper reach it — the firmware has no per-endpoint access control to do it for you. See security.md.

Several inverters: the device label

Every inverter series carries a device label holding the device id — the same string /api/v1/devices serves, e.g. modbus_profile-2. So one bus of three inverters is three series per metric:

heliograph_inverter_ac_power_watts{device="modbus_profile-1"} 1240.000
heliograph_inverter_ac_power_watts{device="modbus_profile-2"} 980.500
heliograph_inverter_ac_power_watts{device="modbus_profile-3"} 1105.000

Bridge-wide series carry no device label — uptime, heap, WiFi, the RS485 and poll counters, the relay and DRM series. They are not per device: the counters live in one place for the whole bus, so labelling them would invent a distinction the firmware does not make.

Upgrading from 0.19.x or earlier

heliograph_inverter_ac_voltage_volts and heliograph_inverter_ac_current_amperes gained a phase label. The metric names did not change, but a series with a new label is a new series: an existing panel keeps its history and stops receiving points, and the new series starts empty beside it.

Selectors keep working — heliograph_inverter_ac_voltage_volts{device="x"} still matches, now returning one series per phase. What needs a look is anything that assumed a single series, such as a panel with no legend format or an alert on the bare metric. max by (device) or {phase="l1"} restores the old meaning.

Nothing else was renamed. Everything else in this release is new metrics that were simply not exported before.

If you already have a dashboard

The first device is labelled too. That is a breaking change and it was chosen deliberately: leaving device 1 unlabelled would have been back-compatible, but sum by (device) would then produce a blank label forever, and an asymmetry that has to be explained every time is worse than a one-off edit. (MQTT made the opposite call for its topics, because there the cost of changing was a user's whole Home Assistant history.)

What actually breaks, and what does not:

Query Before After
heliograph_inverter_ac_power_watts one series one series per inverter — a graph gains lines
sum(heliograph_inverter_ac_power_watts) the one inverter the whole bus — usually what you wanted
a recording rule expecting a single series fine fix it: add sum(...) or {device="…"}
heliograph_build_info one series one per inverter, and it gains device too — a group_left join on it now fans out
any bridge-wide series unchanged unchanged

With one inverter the only visible change is that a label appears, and existing panels keep working. One thing to expect at the upgrade itself, on any number of inverters: adding a label changes the series identity, so Prometheus ends the old series and starts a new one. Gauges graph straight across the gap, but rate(), increase() or resets() over the boundary — and an alert with a long for: — will see a discontinuity once.

Matching it up with Home Assistant

The device label matches /api/v1/devices, and matches the MQTT subtree for devices 2..N. It does not match what Home Assistant displays: device 1 keeps the bridge-scoped MQTT topics, so its id appears nowhere in MQTT, and HA names the devices after the model (… - Growatt MIC TL-X, … #2, … #3). Lining a Grafana panel up with an HA entity is a short lookup rather than a string match.

What is exported

Every series is prefixed heliograph_. Base units are in the names, counters end in _total.

Build and health

Metric Type Notes
heliograph_build_info gauge Always 1. One per inverter. Labels device, version, driver, board
heliograph_inverter_online gauge 1 when the inverter is answering, 0 when it is not
heliograph_data_stale gauge 1 when the last reading is too old to trust

Inverter readings

All gauges, all carrying device, and all omitted entirely when the value is unknown (see Missing values) — per device, so a bus where one inverter reports temperature and another does not gives one series, not two with a fabricated one. A metric no inverter reports is absent entirely, header included.

Two of these carry a second label besides device. A phase and an MPPT string are dimensions of the same quantity, not different quantities, so they are labels rather than three metric names — sum by (device) (heliograph_inverter_ac_power_watts) works, and would not if L1, L2 and L3 were ..._l1_volts and friends.

Whole inverter

Metric Unit
heliograph_inverter_ac_power_watts W
heliograph_inverter_dc_power_watts W (whole array, derived)
heliograph_inverter_grid_frequency_hertz Hz
heliograph_inverter_energy_today_kwh kWh
heliograph_inverter_energy_total_kwh kWh, lifetime
heliograph_inverter_operating_hours h, lifetime
heliograph_inverter_temperature_celsius °C

Per phase — extra label phase="l1", "l2", "l3"

Metric Unit
heliograph_inverter_ac_voltage_volts V
heliograph_inverter_ac_current_amperes A
heliograph_inverter_ac_phase_power_watts W

ac_phase_power_watts is a separate family from ac_power_watts on purpose. Parts and their sum in one family is how a sum() silently double-counts.

Per MPPT string — extra label string="1", "2"

Metric Unit
heliograph_inverter_mppt_voltage_volts V
heliograph_inverter_mppt_current_amperes A
heliograph_inverter_mppt_power_watts W

Battery — a separate prefix, because a battery is its own thing that happens to be reported through the inverter. A query for the inverter's temperature should not have to exclude the battery's.

Metric Unit
heliograph_battery_state_of_charge_percent %
heliograph_battery_power_watts W, positive charging
heliograph_battery_charge_power_watts W
heliograph_battery_discharge_power_watts W
heliograph_battery_voltage_volts V
heliograph_battery_current_amperes A
heliograph_battery_temperature_celsius °C
heliograph_battery_energy_charged_kwh kWh, lifetime
heliograph_battery_energy_discharged_kwh kWh, lifetime

Grid meter

Metric Unit
heliograph_grid_import_power_watts W
heliograph_grid_export_power_watts W
heliograph_grid_power_watts Net grid flow. Signed: positive means importing, negative exporting. Present only when a device publishes grid.power.
heliograph_load_power_watts W, what the house is drawing

Which of these appear depends on the inverter: a driver only reports what its device actually provides, so a single-phase inverter has no three-phase series and an inverter without a temperature sensor has no temperature series. That is not a fault.

Communication counters

Metric Type What it counts
heliograph_poll_success_total counter Successful polls
heliograph_poll_failure_total counter Failed polls
heliograph_rs485_checksum_errors_total counter Frames that failed their checksum
heliograph_rs485_timeouts_total counter Reads that timed out
heliograph_invalid_frames_total counter Structurally invalid frames
heliograph_mqtt_reconnects_total counter MQTT reconnections
heliograph_wifi_reconnects_total counter WiFi reconnections
heliograph_modbus_client_connections_total counter Modbus TCP connections accepted
heliograph_modbus_clients gauge Modbus TCP clients connected right now

None of these carry a device label, and on a bus with several inverters that is a real limitation, not just a naming choice. The counters live in one place for the whole bus, so when one of three inverters starts corrupting frames the checksum counter climbs and all three look equally guilty. What is per device is heliograph_inverter_online{device="…"} — so a unit that drops out entirely is identifiable; a unit with intermittent, sub-timeout faults is not. Per-device counters would mean changing the diagnostics model, which is tracked separately.

The distinction matters when something is wrong, and it is three-way rather than two:

  • Timeouts — nothing came back at all. Wiring, a swapped A/B, a wrong address, or an inverter that is simply asleep.
  • Checksum errors — bytes came back corrupted. This is the one that indicts the wire: a missing ground, no termination (or termination in three places instead of two), a long stub, a run alongside the inverter's own output cabling. See rs485-bus.md.
  • Invalid frames — an intact frame that was not what we asked for: a neighbour on a multidrop bus answering, or a device quirk. Addressing, not cabling.

A quiet night on a solar inverter produces timeouts and no checksum errors, and that is normal: the inverter powers down after dark. That asymmetry is exactly why the alert below watches checksum errors rather than timeouts.

Upgrading from a release before per-transaction counting? heliograph_rs485_timeouts_total steps up by roughly 2–3× on the same hardware, with nothing wrong. A dark inverter used to add one timeout per poll; it now adds one per read, which is one per register block on a Modbus profile. On EverSolar and SolaX it is worse: after three consecutive timeouts the recovery probe runs on every poll, so a night goes from ~1 to ~2 timeouts per poll — and a bridge that reboots after dark, which used to report a cold-start night as zero timeouts, now reports two per poll. Rescale any threshold you built on the raw counter. The checksum counter climbs too, but only on a bus that was already faulty. Nothing else in this file changed meaning.

These three count transactions, not polls. A Growatt poll reads each register block as its own Modbus transaction; the PMU drivers may re-register before they query. So one poll can add several errors, and on a healthy bus adds none.

That distinction took two fixes to get there:

  • Before the release carrying this note, a Modbus driver could not raise the checksum counter at all: the shared read transaction folded CRC failures into a generic protocol error, so on a Growatt or SunSpec install the metric was structurally always zero and the alert could never fire. The PMU drivers (EverSolar, SolaX) were unaffected.

  • And on every driver it only counted when a poll failed outright, because the counters were derived from the poll's verdict — and a poll succeeds as soon as one block decodes. Each driver now tallies what the wire did per transaction, and the poll verdict no longer gates it.

    Concretely, on a two-block profile polling every 10 s: at a 3% frame-corruption rate the old counter moved about once every three hours — never enough for rate(...[15m]) > 0 to hold for the alert's for: window, so it would never have fired. The new counter moves ~22 times an hour and the alert fires reliably. At heavier corruption the old counter did eventually work: at 30% it caught roughly 32 an hour, because both blocks failing at once stops being rare. So this fix does not make a failing bus visible sooner; it makes a degrading one visible at all, and the crossover is somewhere around 15%.

Two under-counts remain.

  • Line noise that damages a length or byte-count field can make the frame un-parseable rather than merely wrong, and that surfaces as a timeout rather than a checksum error. (Not always: a byte count damaged downwards shortens the frame, the CRC is then checked over the wrong span, and it does land in the checksum counter.)
  • A poll can fail with all three counters flat. A device that answers every range with an exception, or a SunSpec device advertising a model this driver cannot decode, is a configuration fault, not a wire fault — heliograph_poll_failure_total and last_error are what carry it.

So: treat a non-zero value as a definite problem, and a zero as "no proof either way". The trace log is the ground truth: a corrupt block says so on the line it happens.

Two things are deliberately not errors in any of the three counters, because both prove the wiring and the addressing are fine:

  • An exception reply — the device answering "I do not have that register".
  • A probe block failing in any way. A profile may declare a block that maps nothing and exists only to discover which register generation a model speaks (see device-profiles/schema.md). A device is allowed to answer an unknown range with silence rather than an exception, and counting that would put a permanent slope on the metric of a perfectly healthy installation — 360 timeouts an hour at the default poll interval.

Bridge health

Metric Type Notes
heliograph_uptime_seconds gauge Seconds since boot
heliograph_free_heap_bytes gauge Free heap
heliograph_max_alloc_heap_bytes gauge Largest single allocatable block
heliograph_psram_size_bytes gauge Total external PSRAM — absent on a board without it
heliograph_psram_free_bytes gauge Free external PSRAM — absent on a board without it
heliograph_coredump_present gauge 1 when a crash dump is waiting in flash — always emitted, 0 is a fact
heliograph_mqtt_publish_failures_total counter Publishes the MQTT client refused (link down, or outbox full)
heliograph_wifi_rssi_dbm gauge Only present while WiFi is connected
heliograph_rs485_stack_free_bytes gauge Only after the first sample
heliograph_loop_stack_free_bytes gauge Only after the first sample
heliograph_time_synced gauge 1 once the clock has been set from NTP
heliograph_ntp_last_sync_timestamp_seconds gauge Unix time of the last sync; absent until there has been one

Relays and curtailment

Only on relay boards. A board without relays exports none of these — not zeroes — so a monitoring-only bridge never grows a panel for hardware it does not have.

Metric Type Notes
heliograph_relays_enabled gauge 1 when the relay feature is enabled in the configuration
heliograph_relay_energised gauge 1 per energised relay, label relay
heliograph_drm_mode gauge Always 1; the mode label carries the active mode

The relay label is 0-based, deliberately: it is the same index as the MQTT topic (<base>/<id>/relay/0/state) and the REST route (/api/v1/relays/0/set), so a series in a dashboard and the topic that switched it line up. The web UI numbers relays from 1 for humans; the machine interfaces all agree on 0.

heliograph_drm_mode follows the standard enum-as-label pattern: exactly one series exists at a time and its value is always 1, so heliograph_drm_mode in a graph shows which mode is active over time. It is absent entirely when no DRM roles are configured — with no roles there is no curtailment vocabulary to report, and inventing a normal would claim a model the operator never set up.

relays_enabled is the configuration flag, not permission to move: a relay also needs security.read_only_mode off before anything actuates. See drm.md.

This is what makes curtailment reviewable after the fact. Graphing heliograph_relay_energised beside heliograph_inverter_ac_power_watts shows the contact closing and the production dropping in the same picture — which is the evidence you want when deciding whether a curtailment rule is behaving.

The three heap gauges are internal SRAM only. Arduino's ESP.getFreeHeap() and friends are heap_caps_*(MALLOC_CAP_INTERNAL), so on the RS485-CAN and Relay-1CH — which carry 8 MB of external PSRAM — they describe roughly 300 KB of the RAM that exists. heliograph_psram_* covers the rest, and is omitted entirely on the Relay-6CH, which has none. Omitted rather than zero, for the same reason as the RSSI and stack gauges: a flat 0 reads as exhaustion to an alerting rule. Their absence is also the only way to tell from the network that PSRAM failed to initialise on a board that should have it.

max_alloc_heap_bytes is the fragmentation signal, and it is the more useful of the two heap numbers on a device meant to run for months: free heap can look healthy while no allocation of any size still fits. A steady free heap with a falling max-alloc is fragmentation.

The two stack gauges are low-water marks — the smallest amount of stack that task has ever had left. They only ever go down. If either approaches zero the firmware is close to a stack overflow, which is how one was caught during development.

Missing values are missing, not zero

This is the one rule worth understanding before you build a dashboard on this.

A reading that is unknown, unsupported or stale is left out of the response entirely. It is not exported as 0.

The reason is that Prometheus handles a genuine gap correctly — the series simply has no sample for that scrape, graphs show a break, and avg_over_time ignores it. A zero would be recorded as a real measurement of nothing, dragging every average down and making "the inverter is asleep" indistinguishable from "the inverter is producing nothing while awake".

The practical consequence: do not alert on the absence of a series alone. At night an inverter stops answering and its measurement series stop with it. Use heliograph_inverter_online to tell "not answering" from "answering with zero output".

The same rule is why heliograph_wifi_rssi_dbm disappears rather than reporting 0 when WiFi drops: 0 dBm would read as a perfect signal.

Cardinality

heliograph_build_info carries device, version, driver and board labels. That is the complete set — the inverter's serial number is deliberately not a label. Serial numbers are high-cardinality by definition, and putting one in a label would multiply every series by the number of devices a scraper has ever seen, which is how a small Prometheus turns into a large one. The serial is available over the REST API instead.

Example output

An abbreviated real scrape from a production bridge. Note that this one is an RS485-CAN — a monitoring-only board — which is exactly why there are no relay or DRM series in it: on a board without relays those are omitted rather than reported as zeroes.

The example below predates the per-device device="…" label described above, which every device-scoped series carries. Read it for the metric NAMES, not the exact lines.

# HELP heliograph_build_info Firmware build information
# TYPE heliograph_build_info gauge
heliograph_build_info{version="0.10.1 (Jul 24 2026 08:31:49)",driver="eversolar_legacy",board="Waveshare ESP32-S3-RS485-CAN"} 1
# HELP heliograph_inverter_online 1 if the inverter is responding
# TYPE heliograph_inverter_online gauge
heliograph_inverter_online 1
# HELP heliograph_data_stale 1 if the last reading is too old to trust
# TYPE heliograph_data_stale gauge
heliograph_data_stale 0
# HELP heliograph_inverter_ac_power_watts Current AC output power
# TYPE heliograph_inverter_ac_power_watts gauge
heliograph_inverter_ac_power_watts 507.000
# HELP heliograph_inverter_energy_today_kwh Energy produced today
# TYPE heliograph_inverter_energy_today_kwh gauge
heliograph_inverter_energy_today_kwh 1.510
# HELP heliograph_inverter_energy_total_kwh Lifetime energy produced
# TYPE heliograph_inverter_energy_total_kwh gauge
heliograph_inverter_energy_total_kwh 35505.800
# HELP heliograph_poll_success_total Successful inverter polls
# TYPE heliograph_poll_success_total counter
heliograph_poll_success_total 275
# HELP heliograph_rs485_timeouts_total RS485 read timeouts
# TYPE heliograph_rs485_timeouts_total counter
heliograph_rs485_timeouts_total 1
# HELP heliograph_wifi_rssi_dbm WiFi signal strength
# TYPE heliograph_wifi_rssi_dbm gauge
heliograph_wifi_rssi_dbm -52
# HELP heliograph_max_alloc_heap_bytes Largest allocatable heap block (fragmentation signal)
# TYPE heliograph_max_alloc_heap_bytes gauge
heliograph_max_alloc_heap_bytes 110580

(Several series are left out above for length — a full response carries the complete set listed earlier.)

Useful queries

Current output, and today's yield:

heliograph_inverter_ac_power_watts
heliograph_inverter_energy_today_kwh

Inverter efficiency, when the driver reports both sides:

heliograph_inverter_ac_power_watts / heliograph_inverter_dc_power_watts

Poll failure rate over the last hour — the honest health signal for the RS485 link:

rate(heliograph_poll_failure_total[1h])
  / (rate(heliograph_poll_success_total[1h]) + rate(heliograph_poll_failure_total[1h]))

Line noise rather than a dead link:

rate(heliograph_rs485_checksum_errors_total[15m]) > 0

Since the counter moves per transaction this fires while the bridge is still delivering data — which is the point, but it does mean a rising rate on a bus that looks healthy in Home Assistant is now the expected shape of an early warning, not a contradiction. Corrupt transactions per poll attempt reads more usefully than a bare rate:

rate(heliograph_rs485_checksum_errors_total[1h])
  / (rate(heliograph_poll_success_total[1h]) + rate(heliograph_poll_failure_total[1h]))

Note this is per poll, not per transaction — the number of transactions is not exported, so on a three-block profile the value ranges 0–3 rather than 0–1. Dividing by successful polls alone would be worse than imprecise: on the failing bus the query exists to describe, that denominator stops advancing and the expression goes to +Inf.

The bridge rebooted:

resets(heliograph_uptime_seconds[1h]) > 0

How much production a curtailment cost, by pairing the contact with the output it suppressed:

heliograph_inverter_ac_power_watts and on() heliograph_relay_energised{relay="0"} == 1

Which DRM mode was active over the last day — one series per mode that occurred:

heliograph_drm_mode

Alerting

Two rules worth having, and both need care about night-time.

groups:
  - name: heliograph
    rules:
      # The bridge itself is unreachable. Not the same as the inverter being asleep.
      - alert: HeliographDown
        expr: up{job="heliograph"} == 0
        for: 10m
        annotations:
          summary: "Heliograph is not answering scrapes"

      # Corrupted frames mean the wiring or the electrical environment, not darkness.
      # Timeouts are deliberately NOT alerted on: every night produces them.
      - alert: HeliographLineErrors
        expr: rate(heliograph_rs485_checksum_errors_total[15m]) > 0
        for: 15m
        annotations:
          summary: "RS485 frames are arriving corrupted — check ground, termination and cable routing"

      # Fragmentation: free heap can look fine while nothing sizeable still fits.
      - alert: HeliographHeapFragmented
        expr: heliograph_max_alloc_heap_bytes < 20000
        for: 30m
        annotations:
          summary: "Largest allocatable heap block is shrinking"

Do not alert on heliograph_inverter_online == 0 without a time-of-day condition: it is 0 every night, on every solar installation, by design.

Other integrations

Prometheus is one of several outputs and carries no state the others lack. If you want long-term energy statistics inside Home Assistant, the MQTT integration is the better route — see mqtt.md. For a machine-readable snapshot in JSON, use the REST API. For building or industrial tooling, there is Modbus TCP.