record(ao, "$(P)$(R)$(CRYO_MOD):CLLTotalPower-SP")
{
field(DESC, "Desired CLL total power")
field(EGU, "W")
field(PINI, "YES")
}
record(ai, "$(P)$(R)$(CRYO_MOD):CLLTotalPower-RB")
{
field(DESC, "Desired CLL total power")
field(EGU, "W")
field(INP, "$(P)$(R)$(CRYO_MOD):CLLTotalPower-SP CP")
}
record(calc, "$(P)$(R)$(CRYO_MOD):CLLTotalPower-Mon")
{
field(DESC, "Sum of RF and Heater powers")
field(EGU, "W")
field(INPA, "$(P)$(R)$(CRYO_MOD):EB$(CRYO_MOD)10_CLLHeaterPower-Mon CP")
field(INPB, "$(P)$(RF_R)$(SRF_CAV):PwrW-Mon CP")
field(CALC, "A+B")
}
record(calcout, "$(P)$(R)$(CRYO_MOD):TargetHeaterPwr")
{
field(DESC, "Heater pwr to reach desired total pwr")
field(EGU, "W")
field(SDIS, "$(P)$(R)$(CRYO_MOD):CLLAutoEn-Sel")
field(DISV, "0")
field(INPA, "$(P)$(R)$(CRYO_MOD):CLLTotalPower-SP CP")
field(INPB, "$(P)$(R)$(CRYO_MOD):CLLTotalPower-Mon CP")
field(INPC, "$(P)$(R)$(CRYO_MOD):EB$(CRYO_MOD)10_CLLInternalRefPower-Mon")
field(INPD, "$(P)$(R)$(CRYO_MOD):CLLPowerDeadband-SP")
field(CALC, "MOD(A-B)>D")
field(OCAL, "(A-B)+C")
# When the error is greater than the deadband
# write the corrected power to the heater
field(OOPT, "When Non-zero")
field(DOPT, "Use OCAL")
field(OUT, "$(P)$(R)$(CRYO_MOD):EB$(CRYO_MOD)10_CLLInternalRefPower-SP")
}
record(bo, "$(P)$(R)$(CRYO_MOD):CLLAutoEn-Sel")
{
field(DESC, "Enable CLL auto-adjust")
field(PINI, "YES")
field(ZNAM, "Disable")
field(ONAM, "Enable")
field(FLNK, "$(P)$(R)$(CRYO_MOD):TargetHeaterPwr")
}
record(bi, "$(P)$(R)$(CRYO_MOD):CLLAutoEn-Sts")
{
field(DESC, "Enable CLL auto-adjust")
field(INP, "$(P)$(R)$(CRYO_MOD):CLLAutoEn-Sel CP")
field(ZNAM, "Disable")
field(ONAM, "Enable")
}
record(ao, "$(P)$(R)$(CRYO_MOD):CLLPowerDeadband-SP")
{
field(DESC, "deadband for auto-adjust")
field(EGU , "W")
field(PINI, "YES")
field(VAL, "0.1")
field(PREC, "3")
}
record(ai, "$(P)$(R)$(CRYO_MOD):CLLPowerDeadband-RB")
{
field(DESC, "deadband for auto-adjust")
field(EGU , "W")
field(PREC, "3")
field(INP, "$(P)$(R)$(CRYO_MOD):CLLPowerDeadband-SP CP")
}