Description
The Battery Runtime data does not match the data from the APC UPS.
This looks like some kind of variable limitation, since the upsc shows 65535, which is equal to 18 hours 12 minutes and 15 seconds.
But in fact, the APC UPS shows the remaining time as 34 hours 1 min.
How can this be fixed?
upsc output:
root@ups:~# upsc internet@localhost
Init SSL without certificate database
battery.charge: 93
battery.charge.low: 10
battery.charge.warning: 50
battery.mfr.date: 2022/10/25
battery.runtime: 65535
battery.runtime.low: 1200
battery.temperature: 16.6
battery.type: PbAc
battery.voltage: 52.4
battery.voltage.nominal: 48.0
device.mfr: American Power Conversion
device.model: Smart-UPS 2200
device.serial: AS1250244567
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 10
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.synchronous: no
driver.version: 2.7.4
driver.version.data: APC HID 0.96
driver.version.internal: 0.41
input.sensitivity: medium
input.transfer.high: 253
input.transfer.low: 200
input.voltage: 0.0
output.current: 0.50
output.frequency: 50.0
output.voltage: 220.4
output.voltage.nominal: 220.0
ups.beeper.status: disabled
ups.delay.shutdown: 20
ups.delay.start: 30
ups.firmware: 654.19.I
ups.firmware.aux: 7.4
ups.load: 5.2
ups.mfr: American Power Conversion
ups.mfr.date: 2012/12/11
ups.model: Smart-UPS 2200
ups.productid: 0002
ups.serial: AS1250244567
ups.status: OB DISCHRG
ups.test.result: No test initiated
ups.timer.reboot: -1
ups.timer.shutdown: -1
ups.timer.start: -1
ups.vendorid: 051d