Running Alongside Home Assistant

This guide explains how to run luxtronik2-modbus-proxy alongside the Home Assistant BenPru/luxtronik integration (also known as the HA HACS integration). Both can share a single Luxtronik 2.0 controller without conflict, as long as you understand the single-connection constraint.

Background: The Single-Connection Constraint

Luxtronik 2.0 controllers (port 8889) allow exactly one TCP connection at a time. Any second connection attempt while the port is held will be refused. This is a hardware limitation that cannot be changed via configuration or firmware.

Both the proxy and the HA BenPru integration handle this correctly by using a connect-read/write-disconnect pattern: each tool connects briefly, reads or writes what it needs, then immediately disconnects. Neither tool holds the connection open between operations.

How Coexistence Works

Timeline:

[proxy]     CONNECT → READ → DISCONNECT ... (idle 30s) ... CONNECT → READ → DISCONNECT
[HA BenPru]                       CONNECT → READ → DISCONNECT ... (idle 30s) ...

Because both systems disconnect immediately after each operation, they naturally interleave without blocking each other. The connection is typically held for less than a second per cycle.

Port separation:

  • The proxy connects outbound to the Luxtronik controller on port 8889.
  • The proxy serves Modbus TCP clients inbound on port 502.
  • HA BenPru connects outbound to the Luxtronik controller on port 8889.
  • HA Modbus integration (if used) connects inbound to the proxy on port 502.

There is no port conflict: port 8889 is shared (briefly, sequentially); port 502 is served only by the proxy.

What Each System Reads and Writes

System Role Port Data Types
Proxy Outbound client to Luxtronik 8889 (outgoing) Parameters (read/write), Calculations (read-only), Visibilities (read-only)
HA BenPru Outbound client to Luxtronik 8889 (outgoing) Parameters, Calculations
evcc Inbound Modbus client to proxy 502 (incoming to proxy) Holding registers (SG-ready, modes)
HA Modbus integration Inbound Modbus client to proxy 502 (incoming to proxy) Holding + input registers

The proxy and HA BenPru both read from port 8889 on the Luxtronik controller. The proxy additionally caches the values and serves them to Modbus clients on port 502.

Recommended Configuration

Proxy poll_interval

The proxy polling interval controls how often it connects to port 8889. The default (30s) is designed to leave plenty of room for HA BenPru to interleave.

# config.yaml
poll_interval: 30   # Recommended for coexistence with HA BenPru
  • 30 seconds: Default, good for most setups. Leaves ~29 seconds idle per cycle.
  • 60 seconds: Conservative; use this if you see repeated connection errors in proxy logs.
  • 15 seconds: Minimum recommended for coexistence. Below this, collisions become likely.
  • 10 seconds: Absolute minimum (proxy enforces this floor). Not recommended with HA BenPru.

HA BenPru scan interval

The BenPru integration polls on its own schedule (typically 30–60 seconds by default). You do not need to change this. As long as both systems use the connect-disconnect pattern (which they do), the timing naturally staggers over time.

If you want to guarantee they never overlap, stagger the startup times (start the proxy a few seconds before HA) so their polling cycles are offset. This is optional.

Write Conflict Guidance

Both the proxy (via evcc) and HA BenPru can write Luxtronik parameters. Writing the same parameter from two systems simultaneously can lead to unpredictable behavior — each system's value overwrites the other.

Recommended write separation

System Should Write Should Not Write
Proxy (via evcc SG-ready) HeatingMode (param 3), HotWaterMode (param 4)
HA BenPru automations Operating modes for schedules, setpoints HeatingMode, HotWaterMode if proxy/evcc manages SG-ready

Rule of thumb: Assign each writable parameter to exactly one controller. If evcc manages SG-ready (which writes HeatingMode and HotWaterMode), do not also write those parameters from HA automations.

SG-ready specific guidance

When evcc sends an SG-ready mode command to the proxy, the proxy writes to:

  • Parameter 3 (HeatingMode)
  • Parameter 4 (HotWaterMode)

If HA simultaneously writes to either of these parameters, the last write wins and the system may be in an inconsistent state. Choose one of:

  1. evcc owns SG-ready: evcc writes mode via proxy. HA BenPru reads-only. HA automations do not write HeatingMode or HotWaterMode while evcc is active.

  2. HA owns operating modes: HA BenPru writes HeatingMode and HotWaterMode directly. evcc SG-ready is not used. The proxy is read-only from evcc's perspective.

  3. Coordinated via HA: HA receives both the Tibber/grid signal and the heat pump state. HA automation decides which mode to apply, either directly via BenPru or by writing the SG-ready register via the proxy's Modbus interface. This gives full control in one place.

Troubleshooting Connection Issues

Proxy logs show repeated connection errors

Symptom: Proxy logs contain poll_cycle_failed with connection refused errors every 30 seconds.

Cause: HA BenPru is holding the Luxtronik socket at the same time the proxy attempts to connect. This is rare but can happen if HA's polling cycle aligns with the proxy's.

Fix:

  1. Increase proxy poll_interval from 30s to 60s to reduce collision probability.
  2. Restart the proxy a few seconds after HA to stagger the cycles.
  3. Check if any HA automation holds the BenPru integration's connection open by triggering many rapid reads.

The proxy is resilient to connection errors — it logs the failure, marks its cache as stale, and retries on the next cycle. A few missed polls do not cause data loss.

HA BenPru shows entity as "unavailable"

Symptom: HA entities from the BenPru integration show "unavailable" periodically.

Cause: The proxy connected to the Luxtronik socket at the same time HA BenPru attempted its poll. BenPru's connection was refused, causing a temporary unavailability.

Fix: This is usually transient (one missed poll = ~30s unavailability). If it happens frequently, increase the proxy poll_interval to 60s to reduce overlap.

The proxy releases the socket within a fraction of a second per cycle, so long-term blocking of HA BenPru should not occur with poll_interval >= 30s.

Both systems show stale data

Symptom: Both the proxy cache and HA BenPru entities show outdated values.

Cause: The Luxtronik controller is unreachable (network issue, controller restart, or power outage).

Fix: Verify the Luxtronik controller is reachable on port 8889 from both the proxy host and the HA host. Check controller power and network cable. The proxy marks its cache as stale when reads fail — check proxy logs for connection errors.

Architecture Summary

                        ┌─────────────────┐
                        │  Luxtronik 2.0  │
                        │  Controller     │
                        │  port 8889      │
                        └────────┬────────┘
                                 │  (one connection at a time)
              ┌──────────────────┴──────────────────┐
              │                                     │
      connect-read-disconnect               connect-read-disconnect
              │                                     │
   ┌──────────▼──────────┐              ┌──────────▼──────────┐
   │  luxtronik2-        │              │  HA BenPru          │
   │  modbus-proxy       │              │  integration        │
   │  (port 502 server)  │              │  (reads only)       │
   └──────────┬──────────┘              └─────────────────────┘
              │
     Modbus TCP port 502
              │
    ┌─────────┴──────────┐
    │                    │
    ▼                    ▼
  evcc              HA Modbus
  (SG-ready         integration
  mode writes)      (read registers)