layout | title |
---|---|
documentation |
ZW100 - ZWave |
{% include base.html %}
This describes the Z-Wave device ZW100, manufactured by AEON Labs with the thing type UID of aeon_zw100_01_010
.
This version of the device is limited to firmware versions above 1.10
The device is in the category of Sensor, defining Device used to measure something.
The ZW100 supports routing. This allows the device to communicate using other routing enabled devices as intermediate routers. This device is also able to participate in the routing of data between other devices in the mesh network.
Battery or USB powered PIR motion sensor,
operating distance: Up to 500 feet/150 metres outdoors.
Click one time
Send non-security Node Info frame, add MultiSensor into Z-Wave network (non-securre inclusion):
- Power on MultiSensor. The MultiSensor’s LED will blink slowly when you short press the Action Button.
- Let the primary controller into inclusion mode (If you don’t know how to do this, refer to its manual).
- Press the Action Button.
- If the inclusion is success, MultiSensor’s LED will be kept turning on for 8 seconds when you short press the Action Button. If the LED is still in slow blink, in which you need to repeat the process from step 2.
Short press 2 times within 1 second
Send Security Node Info frame, add MultiSensor into z-wave network (seciure inclusion):
- Power on MultiSensor. The MultiSensor’s LED will blink slowly when you short press the Action Button.
- Let the primary controller into inclusion mode (If you don’t know how to do this, refer to its manual).
- Press the Action Button.
- If the inclusion is success, MultiSensor’s LED will be kept turning on for 8 seconds when you short press the Action Button. If the LED is still in slow blink, in which you need to repeat the process from step 2.
Remove MultiSensor from Z-wave network:
- Power on MultiSensor. The MultiSensor’s LED will be kept turning on for 8 seconds when you short press the Action Button.
- Let the primary controller into exclusion mode (If you don’t know how to do this, refer to its manual).
- Press the Action Button.
- If the exclusion is success, MultiSensor’s LED will blink slowly when you short press the Action Button. If MultiSensor’s LED still keeps on status, in which you need to repeat the process from step 2.
RESET - Press and hold for 20 seconds
Reset MultiSensor to factory default:
- Press and hold the Action Button for 20 seconds.
- If holding time more than one second, the LED will blink faster and faster. If holding time more than 20 seconds, the LED will be on for 2 seconds, which indicates reset is success, otherwise please repeat step 2.
Note: this procedure should only be used when the primary controller is inoperable:
- Reset MultiSensor to factory default settings, it will:
- let the MultiSensor to be excluded in Z-Wave network
- delete the Association settings
- restore the Configuration settings to the default.
The following table summarises the channels available for the ZW100 -:
Channel Name | Channel ID | Channel Type | Category | Item Type |
---|---|---|---|---|
Sensor (temperature) | sensor_temperature | sensor_temperature | Temperature | Number:Temperature |
Sensor (ultraviolet) | sensor_ultraviolet | sensor_ultraviolet | Number | |
Sensor (luminance) | sensor_luminance | sensor_luminance | Number | |
Sensor (relative humidity) | sensor_relhumidity | sensor_relhumidity | Humidity | Number |
Motion Alarm | alarm_motion | alarm_motion | Motion | Switch |
Tamper Alarm | alarm_tamper | alarm_tamper | Switch | |
Battery Level | battery-level | system.battery_level | Battery | Number |
Indicates the current temperature.
The sensor_temperature
channel is of type sensor_temperature
and supports the Number:Temperature
item and is in the Temperature
category.
Indicates the current ultraviolet level.
The sensor_ultraviolet
channel is of type sensor_ultraviolet
and supports the Number
item. This is a read only channel so will only be updated following state changes from the device.
Indicates the current light reading.
The sensor_luminance
channel is of type sensor_luminance
and supports the Number
item. This is a read only channel so will only be updated following state changes from the device.
Indicates the current relative humidity.
The sensor_relhumidity
channel is of type sensor_relhumidity
and supports the Number
item and is in the Humidity
category. This is a read only channel so will only be updated following state changes from the device.
Indicates if a motion alarm is triggered.
The alarm_motion
channel is of type alarm_motion
and supports the Switch
item and is in the Motion
category. This is a read only channel so will only be updated following state changes from the device.
The following state translation is provided for this channel to the Switch
item type -:
Value | Label |
---|---|
OFF | OK |
ON | Alarm |
Indicates if the tamper alarm is triggered.
The alarm_tamper
channel is of type alarm_tamper
and supports the Switch
item. This is a read only channel so will only be updated following state changes from the device.
The following state translation is provided for this channel to the Switch
item type -:
Value | Label |
---|---|
OFF | OK |
ON | Alarm |
Represents the battery level as a percentage (0-100%). Bindings for things supporting battery level in a different format (e.g. 4 levels) should convert to a percentage to provide a consistent battery level reading.
The system.battery-level
channel is of type system.battery-level
and supports the Number
item and is in the Battery
category.
This channel provides the battery level as a percentage and also reflects the low battery warning state. If the battery state is in low battery warning state, this will read 0%.
The following table provides a summary of the 54 configuration parameters available in the ZW100. Detailed information on each parameter can be found in the sections below.
Param | Name | Description |
---|---|---|
2 | Stay Awake in Battery Mode | Stay awake for 10 minutes at power on |
3 | Motion Sensor reset timeout | Motion Sensor reset timeout |
4 | Motion sensor sensitivity | Sensitivity level of PIR sensor (1=minimum, 5=maximum) |
5 | Motion Sensor Triggered Command | |
8 | Timeout after wake up | Set the timeout of awake after the Wake Up CC is sent out... |
9 | Report the current power mode | Report the current power mode and the product state of battery power mode |
9 | Sleep State | |
9 | Power Mode | |
39 | Low Battery Report | Report Low Battery if below this value |
40 | Selective Reporting | Select to report on thresholds |
41 | Temperature Threshold | Temperature change threshold |
41 | Temperature Threshold Unit | Sets the unit of the threshold |
41 | Temperature Threshold | Threshold change in temperature to induce an automatic report. |
42 | Humidity Threshold | Humidity percent change threshold |
43 | Luminance Threshold | Luminance change threshold |
44 | Battery Threshold | Battery level threshold |
45 | Ultraviolet Threshold | Ultraviolet change threshold |
46 | Send Alarm Report if low temperature | Send an alarm report if temperature is less than -15 °C |
48 | Send a report if the measurement is out of limits | Send report when measurement is at upper/lower limit |
49 | Upper limit value of temp sensor | Upper limit value of temperature sensor |
49 | Unit for upper limit value of temp sensor | Unit selection for upper limit value of temperature sensor |
49 | Upper limit value of temp sensor | Upper limit value of temperature sensor |
50 | Lower limit value of temperature sensor | Lower limit value of temperature sensor |
50 | Unit for lower limit value of temp sensor | Unit selection for lower limit value of temperature sensor |
50 | Lower limit value of temperature sensor | Lower limit value of temperature sensor |
51 | Upper limit value of humidity sensor | Upper limit value of humidity sensor |
52 | Lower limit value of humidity sensor | Lower limit value of humidity sensor |
53 | Upper limit value of Lighting sensor | Upper limit value of Lighting sensor |
54 | Lower limit value of Lighting sensor | Lower limit value of Lighting sensor |
55 | Upper limit value of ultraviolet sensor | Upper limit value of ultraviolet sensor |
56 | Lower limit value of ultraviolet sensor | Lower limit value of ultraviolet sensor |
57 | Recover limit value of temperature sensor | Recover limit value of temperature sensor |
58 | Recover limit value of humidity sensor | Recover limit value of humidity sensor |
59 | Recover limit value of Lighting sensor. | Recover limit value of Lighting sensor. |
60 | Recover limit value of Ultraviolet sensor | Recover limit value of Ultraviolet sensor |
61 | Out-of-limit state of the Sensors | Out-of-limit state of the Sensors |
64 | Default unit of the automatic temperature report | Default unit of the automatic temperature report |
81 | LED function | Disable/Enable LED function |
100 | Set parameters 101-103 to default. | Reset 101-103 to defaults |
101 | Group 1 Periodic Reports | Periodic reports to send to Group 1 |
102 | Group 2 Periodic Reports | Periodic reports to send to Group 2 |
103 | Group 3 Periodic Reports | Periodic reports to send to Group 3 |
110 | Set parameters 111-113 to default. | Set parameters 111-113 to default. |
111 | Group 1 Report Interval | How often to update Group 1 |
112 | Group 2 Report Interval | Group 2 Report Interval |
113 | Group 3 Report Interval | Group 3 Report Interval |
201 | Temperature Calibration | Temperature calibration in 0.1 deg steps |
201 | Temperature Calibration Unit | |
201 | Temperature Calibration Value | Calibration value containing one decimal point |
202 | Humidity Sensor Calibration | Humidity Sensor Calibration |
203 | Luminance Sensor Calibration | Luminance Sensor Calibration |
204 | Ultraviolet Sensor Calibration | Ultraviolet Sensor Calibration |
252 | Disable/Enable Configuration Lock | Disable/Enable Configuration Lock (0=Disable, 1=Enable) |
255 | Reset to default factory settings | |
Wakeup Interval | Sets the interval at which the device will accept commands from the controller | |
Wakeup Node | Sets the node ID of the device to receive the wakeup notifications |
Stay awake for 10 minutes at power on Enable/Disable waking up for 10 minutes when re-power on (battery mode) the MultiSensor.
- Value = 0, disable.
- Value =others, enable. The following option values may be configured -:
Value | Description |
---|---|
0 | Disable |
1 | Enable |
The manufacturer defined default value is 0
(Disable).
This parameter has the configuration ID config_2_1
and is of type INTEGER
.
Motion Sensor reset timeout
- The default PIR time is 4 minutes. The Multisensor will send BASIC SET CC (0x00) to the associated nodes if no motion is triggered again in 4 minutes.
- Range: 10~3600.
Note:
- The time unit is second if the value range is in 10 to 255.
- If the value range is in 256 to 3600, the time unit will be minute and its value should follow the below rules:
a) Interval time =Value/60, if the interval time can be divided by 60 and without remainder.
b) Interval time= (Value/60) +1, if the interval time can be divided by 60 and has remainder. - Other values will be ignored. Values in the range 10 to 3600 may be set.
The manufacturer defined default value is 240
.
This parameter has the configuration ID config_3_2
and is of type INTEGER
.
Sensitivity level of PIR sensor (1=minimum, 5=maximum)
The following option values may be configured -:
Value | Description |
---|---|
0 | Disable |
1 | Enable, sensitivity level 1 (minimum) |
2 | Enable, sensitivity level 2 |
3 | Enable, sensitivity level 3 |
4 | Enable, sensitivity level 4 |
5 | Enable, sensitivity level 5 (maximum) |
The manufacturer defined default value is 5
(Enable, sensitivity level 5 (maximum)).
This parameter has the configuration ID config_4_1
and is of type INTEGER
.
The following option values may be configured -:
Value | Description |
---|---|
1 | Send Basic Set CC |
2 | Send Sensor Binary Report CC |
The manufacturer defined default value is 1
(Send Basic Set CC).
This parameter has the configuration ID config_5_1
and is of type INTEGER
.
Set the timeout of awake after the Wake Up CC is sent out...
Values in the range 8 to 255 may be set.
The manufacturer defined default value is 30
.
This parameter has the configuration ID config_8_1
and is of type INTEGER
.
Report the current power mode and the product state of battery power mode
Value1 (MSB): 0x00=USB power mode, 0x01=Battery power mode
Value2 (LSB): 0x00=keep sleep state for Battery power mode, 0x01=keep awake for 10 minutes for battery power mode
NOTE: this parameter cannot be used as Get/Set usageThis is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 0 to 65535 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_9_2
and is of type INTEGER
.
This is a read only parameter.
The following option values may be configured -:
Value | Description |
---|---|
0 | Asleep |
1 | Awake |
The manufacturer defined default value is 0
(Asleep).
This parameter has the configuration ID config_9_2_00000001
and is of type INTEGER
.
This is a read only parameter.
The following option values may be configured -:
Value | Description |
---|---|
0 | USB |
1 | Battery |
The manufacturer defined default value is 0
(USB).
This parameter has the configuration ID config_9_2_00000100
and is of type INTEGER
.
This is a read only parameter.
Report Low Battery if below this value
Configure low battery value.
Value=10 to 50.(10% to 50%)
Values in the range 10 to 50 may be set.
The manufacturer defined default value is 20
.
This parameter has the configuration ID config_39_1
and is of type INTEGER
.
Select to report on thresholds Enable/disable the selective reporting only when measurements reach a certain threshold or percentage set in 41-44 below. This is used to reduce network traffic. (0 == disable, 1 == enable)
Note: If USB Power, the Sensor will check threshold every 10 seconds. If battery power, the Sensor will check the threshold when it is waken up. The following option values may be configured -:
Value | Description |
---|---|
0 | Disable |
1 | Enable |
The manufacturer defined default value is 0
(Disable).
This parameter has the configuration ID config_40_1
and is of type INTEGER
.
Temperature change threshold
Threshold change in temperature to induce an automatic report.
Note:
- The unit is Fahrenheit for US version, Celsius for EU/AU version.
- High byte is the threshold value. Low byte is the unit (0x01=Celsius, 0x02=Fahrenheit).
- The threshold value (high byte) contains one decimal point. E.g. if the value is set to 20 (0x1401), the threshold value =2.0°C (EU/AU version) or if the value is set to 20 (0x1402), the threshold value=2.0 °F (US version). When the current temperature gap is more then 2.0, which will induce a temperature report to be sent out.This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range 0 to 2678400 may be set.
The manufacturer defined default value is 20
.
This parameter has the configuration ID config_41_4_wo
and is of type INTEGER
.
This is a write only parameter.
Sets the unit of the threshold 0x0100=Celsius, 0x0200=Fahrenheit, 1= Celsius, 2= Fahrenheit The following option values may be configured -:
Value | Description |
---|---|
1 | Celsius |
2 | Fahrenheit |
The manufacturer defined default value is 1
(Celsius).
This parameter has the configuration ID config_41_4_0000FF00
and is of type INTEGER
.
Threshold change in temperature to induce an automatic report. Lower byte of the upper word is used for temperature threshold. Values in the range 0 to 100 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_41_4_00FF0000
and is of type INTEGER
.
Humidity percent change threshold
Threshold change in humidity to induce an automatic report.
Note:
- The unit is %.
- The default value is 10, which means that if the current humidity gap is
more than 10%, it will send out a humidity report. Values in the range 0 to 100 may be set.
The manufacturer defined default value is 10
.
This parameter has the configuration ID config_42_1
and is of type INTEGER
.
Luminance change threshold Threshold change in luminance to induce an automatic report. Values in the range 0 to 1000 may be set.
The manufacturer defined default value is 100
.
This parameter has the configuration ID config_43_2
and is of type INTEGER
.
Battery level threshold Threshold change in battery level to induce an automatic report.
Note:
- The unit is %.
- The default value is 10, which means that if the current battery level gap is
more than 10%, it will send out a battery report. Values in the range 0 to 100 may be set.
The manufacturer defined default value is 10
.
This parameter has the configuration ID config_44_1
and is of type INTEGER
.
Ultraviolet change threshold Threshold change in ultraviolet to induce an automatic report. Values in the range 0 to 100 may be set.
The manufacturer defined default value is 2
.
This parameter has the configuration ID config_45_1
and is of type INTEGER
.
Send an alarm report if temperature is less than -15 °C Enable/Disable to send the alarm report of low temperature (<-15°C)
Value=0, disable
Value=1, enable (The MultiSensor will send a report of Multi Level Temperature CC to controller if the current temperature is less then -15°C).
Note: The battery activity will reduced at low temperatures (-15 degrees Celsius and below), wich will lead to the product may not work normally. It is recommended to use USB power at low temperatures. The following option values may be configured -:
Value | Description |
---|---|
0 | Disable |
1 | Enable |
The manufacturer defined default value is 0
(Disable).
This parameter has the configuration ID config_46_1
and is of type INTEGER
.
Send report when measurement is at upper/lower limit
Enable/disable to send a report when the measurement is more than the upper limit value or less than the lower limit value.
Bit mask = 0, disable.
Bit mask = 1, enable.
Bit 0 = temperature.
Bit 1 = humidity.
Bit 2 = luminance.
Bit 3 = ultraviolet.
The above bit masks are used to enable/disable to send out a report when the measurement is less than the lower limit value. The below bit masks are used to enable/disable to send out a report when the measurement is more than the upper limit value
Bit 4 = temperature.
Bit 5 = humidity.
Bit 6 = luminance.
Bit 7 = ultraviolet.
Note: If USB power, the Sensor will check the limit every 10 seconds. If battery power, the Sensor will check the limit when it is waken up. Values in the range 0 to 255 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_48_1
and is of type INTEGER
.
Upper limit value of temperature sensor Set the upper limit value of temperature sensor. When the measurement is more than this upper limit, which will trigger to sent out a sensor report.
High byte is the upper limit value. Low bytes represent the unit (0x0100=Celsius, 0x0200=Fahrenheit).
When unit is Celsius:
Upper limit range: -40.0 to 100.0 ℃ (0xFE70 to 0x03E8). E.g. The default upper limit of EU/AU version is 28.0 ℃ (0x0118), when the measurement is more than 28.0℃, it will be triggered to send out a temperature sensor report.
When unit is Fahrenheit:
Upper limit range: -40.0 to 212.0 ℉ (0xFE70 to 0x0848). E.g. The default upper limit of US version is 82.4℉ (0X0338), when the measurement is more than 82.4℉, it will be triggered to send out a temperature sensor report.This is an advanced parameter and will therefore not show in the user interface without entering advanced mode.
Values in the range 0 to 0 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_49_4_wo
and is of type INTEGER
.
This is a write only parameter.
Unit selection for upper limit value of temperature sensor Low bytes represent the unit (0x0100=Celsius, 0x0200=Fahrenheit). The following option values may be configured -:
Value | Description |
---|---|
1 | Celsius |
2 | Fahrenheit |
The manufacturer defined default value is 1
(Celsius).
This parameter has the configuration ID config_49_4_0000FF00_wo
and is of type INTEGER
.
This is a write only parameter.
Upper limit value of temperature sensor Set the upper limit value of temperature sensor. When the measurement is more than this upper limit, which will trigger to sent out a sensor report. High byte is the upper limit value. Low bytes represent the unit (0x0100=Celsius, 0x0200=Fahrenheit).
When unit is Celsius:
Upper limit range: -40.0 to 100.0 ℃ (0xFE70 to 0x03E8).
E.g. The default upper limit of EU/AU version is 28.0 ℃ (0x0118), when the measurement is more than 28.0℃, it will be triggered to send out a temperature sensor report.
When unit is Fahrenheit:
Upper limit range: -40.0 to 212.0 ℉ (0xFE70 to 0x0848).
E.g. The default upper limit of US version is 82.4℉ (0X0338), when the measurement is more than 82.4℉, it will be triggered to send out a temperature sensor report.
Values in the range 0 to 65535 may be set.
The manufacturer defined default value is 280
.
This parameter has the configuration ID config_49_4_7FFF0000_wo
and is of type INTEGER
.
This is a write only parameter.
Lower limit value of temperature sensor Set the lower limit value of temperature sensor. When the measurement is less than this lower limit, which will trigger to sent out a sensor report. High byte is the lower limit value. Low bytes represent the unit (0x0100=Celsius, 0x0200=Fahrenheit).
When unit is Celsius:
Lower limit range: -40.0 to 100.0 ℃ (0xFE70 to 0x03E8). E.g. The default lower limit of EU/AU version is 0 ℃ (0x0000), when the measurement is less than 0℃, it will be triggered to send out a temperature sensor report.
When unit is Fahrenheit:
Upper limit range: -40.0 to 212.0 ℉ (0xFE70 to 0x0848). E.g. The default lower limit of US version is 32.0℉ (0x0140), when the measurement is less than 32.0℉, it will be triggered to send out a temperature sensor report. This is an advanced parameter and will therefore not show in the user interface without entering advanced mode.
Values in the range 0 to 0 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_50_4_wo
and is of type INTEGER
.
This is a write only parameter.
Unit selection for lower limit value of temperature sensor Low bytes represent the unit (0x0100=Celsius, 0x0200=Fahrenheit). The following option values may be configured -:
Value | Description |
---|---|
1 | Celsius |
2 | Fahrenheit |
The manufacturer defined default value is 1
(Celsius).
This parameter has the configuration ID config_50_4_0000FF00_wo
and is of type INTEGER
.
This is a write only parameter.
Lower limit value of temperature sensor Set the lower limit value of temperature sensor. When the measurement is less than this lower limit, which will trigger to sent out a sensor report. High byte is the lower limit value. Low bytes represent the unit (0x0100=Celsius, 0x0200=Fahrenheit).
When unit is Celsius:
Lower limit range: -40.0 to 100.0 ℃ (0xFE70 to 0x03E8).
E.g. The default lower limit of EU/AU version is 0 ℃ (0x0000), when the measurement is less than 0℃, it will be triggered to send out a temperature sensor report.
When unit is Fahrenheit:
Upper limit range: -40.0 to 212.0 ℉ (0xFE70 to 0x0848).
E.g. The default lower limit of US version is 32.0℉ (0x0140), when the measurement is less than 32.0℉, it will be triggered to send out a temperature sensor report.
Values in the range 0 to 2678400 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_50_4_7FFF0000_wo
and is of type INTEGER
.
This is a write only parameter.
Upper limit value of humidity sensor Set the upper limit value of humidity sensor. When the measurement is more than this upper limit, which will trigger to sent out a sensor report. Upper limit range: 0 to 100%. E.g. The default upper limit is 60%, when the measurement is more than 60%, it will be triggered to send out a humidity sensor report. Values in the range 0 to 100 may be set.
The manufacturer defined default value is 60
.
This parameter has the configuration ID config_51_1
and is of type INTEGER
.
Lower limit value of humidity sensor Set the lower limit value of humidity sensor. When the measurement is less than this lower limit, which will trigger to sent out a sensor report. Lower limit range: 0 to 100%.
E.g. The default lower limit is 50%, when the measurement is less than 50%, it will be triggered to send out a humidity sensor report. Values in the range 0 to 100 may be set.
The manufacturer defined default value is 50
.
This parameter has the configuration ID config_52_1
and is of type INTEGER
.
Upper limit value of Lighting sensor Set the upper limit value of Lighting sensor. When the measurement is more than this upper limit, which will trigger to sent out a sensor report. Upper limit range: 0 to 30000 Lux.
E.g. The default upper limit is 1000Lux, when the measurement is more than 1000Lux, it will be triggered to send out a Lighting sensor report. Values in the range 0 to 30000 may be set.
The manufacturer defined default value is 1000
.
This parameter has the configuration ID config_53_2
and is of type INTEGER
.
Lower limit value of Lighting sensor Set the lower limit value of Lighting sensor. When the measurement is less than this lower limit, which will trigger to sent out a sensor report. Lower limit range: 0 to 30000 Lux.
E.g. The default lower limit is 100Lux, when the measurement is less than 100Lux, it will be triggered to send out a Lighting sensor report. Values in the range 0 to 30000 may be set.
The manufacturer defined default value is 100
.
This parameter has the configuration ID config_54_2
and is of type INTEGER
.
Upper limit value of ultraviolet sensor Set the upper limit value of ultraviolet sensor. When the measurement is more than this upper limit, which will trigger to sent out a sensor report. Upper limit range: 1 to 11.
E.g. The default upper limit is 8, when the measurement is more than 8, it will be triggered to send out a ultraviolet sensor report. Values in the range 1 to 11 may be set.
The manufacturer defined default value is 8
.
This parameter has the configuration ID config_55_1
and is of type INTEGER
.
Lower limit value of ultraviolet sensor Set the lower limit value of ultraviolet sensor. When the measurement is less than this upper limit, which will trigger to sent out a sensor report. Lower limit range: 1 to 11.
E.g. The default lower limit is 4, when the measurement is less than 8, it will be triggered to send out a ultraviolet sensor report. Values in the range 1 to 11 may be set.
The manufacturer defined default value is 4
.
This parameter has the configuration ID config_56_1
and is of type INTEGER
.
Recover limit value of temperature sensor Set the recover limit value of temperature sensor.
Note:
- When the current measurement <= (Upper limit – Recover limit), the upper limit report is enabled and then it would send out a sensor report when the next measurement is more than the upper limit. After that the upper limit report would be disabled again until the measurement <= (Upper limit – Recover limit).
- When the current measurement >= (Lower limit + Recover limit), the lower limit report is enabled and then it would send out a sensor report when the next measurement is less than the lower limit. After that the lower limit report would be disabled again until the measurement >= (Lower limit + Recover limit).
- High byte is the recover limit value. Low byte is the unit (0x01=Celsius, 0x02=Fahrenheit).
- Recover limit range: 1.0 to 25.5 ℃/ ℉ (0x0101 to 0xFF01 or 0x0102 to 0xFF02).
- E.g. The default recover limit value is 2.0 ℃/℉ (0x1401/0x1402), when the measurement is less than (Upper limit – 2), the upper limit report would be enabled one time Values in the range 0 to 65535 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_57_2
and is of type INTEGER
.
Recover limit value of humidity sensor Set the recover limit value of humidity sensor.
Note:
- When the current measurement <= (Upper limit – Recover limit), the upper limit report is enabled and then it would send out a sensor report when the next measurement is more than the upper limit. After that the upper limit report would be disabled again until the measurement <= (Upper limit – Recover limit).
- When the current measurement >= (Lower limit + Recover limit), the lower limit report is enabled and then it would send out a sensor report when the next measurement is less than the lower limit. After that the lower limit report would be disabled again until the measurement >= (Lower limit + Recover limit).
- Recover limit range: 1 to 50% (0x01 to 0x32).
- E.g. The default recover limit value is 5%, when the measurement is less than (Upper limit – 5), the upper limit report would be enabled one time or when the measurement is more than (Lower limit + 5), the lower limit report would be enabled one time. Values in the range 1 to 50 may be set.
The manufacturer defined default value is 5
.
This parameter has the configuration ID config_58_1
and is of type INTEGER
.
Recover limit value of Lighting sensor. Set the recover limit value of Lighting sensor.
Note:
- When the current measurement <= (Upper limit – Recover limit), the upper limit report is enabled and then it would send out a sensor report when the next measurement is more than the upper limit. After that the upper limit report would be disabled again until the measurement <= (Upper limit – Recover limit).
- When the current measurement >= (Lower limit + Recover limit), the lower limit report is enabled and then it would send out a sensor report when the next measurement is less than the lower limit. After that the lower limit report would be disabled again until the measurement >= (Lower limit + Recover limit).
- Unit = 10×Recover limit (Lux)
- Recover limit range: 10 to 2550Lux (0x01 to 0xFF).
- E.g. The default recover limit value is 100 Lux, when the measurement is less than (Upper limit – 100), the upper limit report would be enabled one time or when the measurement is more than (Lower limit + 100), the lower limit report would be enabled one time. Values in the range 1 to 255 may be set.
The manufacturer defined default value is 10
.
This parameter has the configuration ID config_59_1
and is of type INTEGER
.
Recover limit value of Ultraviolet sensor Set the recover limit value of Ultraviolet sensor.
Note:
- When the current measurement <= (Upper limit – Recover limit), the upper limit report is enabled and then it would send out a sensor report when the next measurement is more than the upper limit. After that the upper limit report would be disabled again until the measurement <= (Upper limit – Recover limit).
- When the current measurement >= (Lower limit + Recover limit), the lower limit report is enabled and then it would send out a sensor report when the next measurement is less than the lower limit. After that the lower limit report would be disabled again until the measurement >= (Lower limit + Recover limit).
- Recover limit range: 1 to 5 (0x01 to 0x05).
- E.g. The default recover limit value is 2, when the measurement is less than (Upper limit – 2), the upper limit report would be enabled one time or when the measurement is more than (Lower limit + 2), the lower limit report would be enabled one time. Values in the range 1 to 5 may be set.
The manufacturer defined default value is 2
.
This parameter has the configuration ID config_60_1
and is of type INTEGER
.
Out-of-limit state of the Sensors Get the out-of-limit state of the Sensors.
- Bit mask = 0, within the limit.
- Bit mask = 1, out of the limit.
- Bit 0 = temperature.
- Bit 1 = humidity.
- Bit 2 = luminance.
- Bit 3 = ultraviolet.
The above bit masks are used to indicate whether the current measurements of the Sensors are out of the lower limit.. The below bit masks are used to indicate whether the current measurements of the Sensors are out of the upper limit.
- Bit 4 = temperature.
- Bit 5 = humidity.
- Bit 6 = luminance.
- Bit 7 = ultraviolet Values in the range 0 to 255 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_61_1
and is of type INTEGER
.
This is a read only parameter.
Default unit of the automatic temperature report Set the default unit of the automatic temperature report in parameter 101- 103. 1 = Celsius. 2 = Fahrenheit. Values in the range 1 to 2 may be set.
The manufacturer defined default value is 1
.
This parameter has the configuration ID config_64_1
and is of type INTEGER
.
Disable/Enable LED function
Enable/disable the LED blinking.
0 = Enable LED blinking.
1 = Disable LED blinking only when the PIR is triggered.
2 = Completely disable LED for motion, wakeup, and sensor report.
The following option values may be configured, in addition to values in the range 0 to 2 -:
Value | Description |
---|---|
0 | Enable LED blinking |
1 | Disable PIR LED |
2 | Disable ALL |
The manufacturer defined default value is 0
(Enable LED blinking).
This parameter has the configuration ID config_81_1
and is of type INTEGER
.
Reset 101-103 to defaults Set 101-103 to default. Values in the range 0 to 1 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_100_1_wo
and is of type INTEGER
.
This is a write only parameter.
Periodic reports to send to Group 1 This value is a combination number made up of the sum of the values for the individual sensors and battery. The sensors have these values:
- Battery=1
- Ultraviolet=16
- Temperature=32
- Humidity=64
- Light=128
1+16+32+64+128 = 241 and is the default value Values in the range 0 to 65535 may be set.
The manufacturer defined default value is 241
.
This parameter has the configuration ID config_101_4
and is of type INTEGER
.
Periodic reports to send to Group 2 This value is a combination number made up of the sum of the values for the individual sensors and battery. The sensors have these values:
- Battery=1
- Ultraviolet=16
- Temperature=32
- Humidity=64
- Light=128 Values in the range 0 to 65535 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_102_4
and is of type INTEGER
.
Periodic reports to send to Group 3 This value is a combination number made up of the sum of the values for the individual sensors and battery. The sensors have these values:
- Battery=1
- Ultraviolet=16
- Temperature=32
- Humidity=64
- Light=128 Values in the range 0 to 65535 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_103_4
and is of type INTEGER
.
Set parameters 111-113 to default. Set parameters 111-113 to default. Values in the range 0 to 1 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_110_1_wo
and is of type INTEGER
.
This is a write only parameter.
How often to update Group 1 The interval time of sending reports in Report group 1 (Valid values 0x05-0x28DE80).
- The unit of interval time is second if USB power.
- If battery power, the minimum interval time is 60 minutes by default, for example, if the value is set to be more than 5 and less than 3600, the interval time is 60 minutes, if the value is set to be more than 3600 and less than 7200, the interval time is 120 minutes. You can also change the minimum interval time to 4 minutes via setting the interval value(3 bytes) to 240 in Wake Up Interval Set CC. Values in the range 5 to 2678400 may be set.
The manufacturer defined default value is 3600
.
This parameter has the configuration ID config_111_4
and is of type INTEGER
.
Group 2 Report Interval
The interval time of sending reports in Report group 2 (Valid values 0x05-
0x28DE80).
Note:
- The unit of interval time is second if USB power.
- If battery power, the minimum interval time is 60 minutes by default, for
example, if the value is set to be more than 5 and less than 3600, the interval
time is 60 minutes, if the value is set to be more than 3600 and less than 7200,
the interval time is 120 minutes. You can also change the minimum interval time
to 4 minutes via setting the interval value(3 bytes) to 240 in Wake Up Interval Set
CC. Values in the range 5 to 2678400 may be set.
The manufacturer defined default value is 3600
.
This parameter has the configuration ID config_112_4
and is of type INTEGER
.
Group 3 Report Interval The interval time of sending reports in Report group 3
- The unit of interval time is second if USB power.
- If battery power, the minimum interval time is 60 minutes by default, for example, if the value is set to be more than 5 and less than 3600, the interval time is 60 minutes, if the value is set to be more than 3600 and less than 7200, the interval time is 120 minutes. You can also change the minimum interval time to 4 minutes via setting the interval value(3 bytes) to 240 in Wake Up Interval Set CC. Values in the range 5 to 2678400 may be set.
The manufacturer defined default value is 3600
.
This parameter has the configuration ID config_113_4
and is of type INTEGER
.
Temperature calibration in 0.1 deg steps
Temperature calibration (the available value range is [-128,127] or [-12.8°C ,12.7 °C ] ).
Note:
- High byte is the calibration value. Low byte is the unit (0x01=Celsius, 0x02=Fahrenheit).
- The calibration value (high byte) contains one decimal point. E.g. if the value is set to 20 (0x1401), the calibration value is 2.0°C (EU/AU version) or if the value is set to 20 (0x1402), the calibration value is 2.0 °F (US version)
- The calibration value = standard value - measure value. °C and the standard value = 23.2 °C , so the calibration value= 23.2 °C - 25.3 °C = -2.1 °C (0xEB). If the measure value =30.1 °C and the standard value = 33.2 °C , so the calibration value= 33.2 °C - 30.1 °C =3.1 °C (0x1F).This is an advanced parameter and will therefore not show in the user interface without entering advanced mode. Values in the range -128 to 127 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_201_2
and is of type INTEGER
.
The following option values may be configured -:
Value | Description |
---|---|
1 | Celsius |
2 | Fahrenheit |
The manufacturer defined default value is 1
(Celsius).
This parameter has the configuration ID config_201_2_000000FF
and is of type INTEGER
.
Calibration value containing one decimal point
Values in the range -127 to 127 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_201_2_0000FF00
and is of type INTEGER
.
Humidity Sensor Calibration
Humidity sensor calibration (the available value range is [-50, 50]).
The calibration value = standard value - measure value.
E.g. If measure value =80RH and the standard value = 75RH, so the calibration
value= 75RH – 80RH= -5RH (0xFB).
If the measure value =85RH and the standard value = 90RH, so the calibration
value= 90RH – 85RH=5RH (0x05).
Values in the range -50 to 50 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_202_1
and is of type INTEGER
.
Luminance Sensor Calibration
Luminance sensor calibration (the available value range is [-1000, 1000]).
The calibration value = standard value - measure value.
E.g. If measure value =800Lux and the standard value = 750Lux, so the
calibration value= 750 – 800= -50 (0xFFCE).
If the measure value =850Lux and the standard value = 900Lux, so the calibration
value= 900 – 850=50 (0x0032).
Values in the range -1000 to 1000 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_203_2
and is of type INTEGER
.
Ultraviolet Sensor Calibration
Ultraviolet sensor calibration (the available value range is [-10, 10]).
The calibration value = standard value - measure value.
E.g. If measure value =9 and the standard value = 8, so the calibration value= 8 –
9= -1 (0xFE).
If the measure value =7 and the standard value = 9, so the calibration value= 9 –
7=2 (0x02).
Values in the range -10 to 10 may be set.
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_204_1
and is of type INTEGER
.
Disable/Enable Configuration Lock (0=Disable, 1=Enable) Enable/disable Configuration Locked (0 =disable, 1 = enable). The following option values may be configured, in addition to values in the range 0 to 1 -:
Value | Description |
---|---|
0 | Disable |
1 | Enable |
The manufacturer defined default value is 0
(Disable).
This parameter has the configuration ID config_252_1
and is of type INTEGER
.
The following option values may be configured -:
Value | Description |
---|---|
1 | Resets all configuration parameters to defaults |
1431655765 | Reset to default factory settings and be excluded |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_255_4_wo
and is of type INTEGER
.
This is a write only parameter.
The wakeup interval sets the period at which the device will listen for messages from the controller. This is required for battery devices that sleep most of the time in order to conserve battery life. The device will wake up at this interval and send a message to the controller to tell it that it can accept messages - after a few seconds, it will go back to sleep if there is no further communications.
This setting is defined in seconds. It is advisable not to set this interval too short or it could impact battery life. A period of 1 hour (3600 seconds) is suitable in most instances.
Note that this setting does not affect the devices ability to send sensor data, or notification events.
This parameter has the configuration ID wakeup_interval
and is of type INTEGER
.
When sleeping devices wake up, they send a notification to a listening device. Normally, this device is the network controller, and normally the controller will set this automatically to its own address. In the event that the network contains multiple controllers, it may be necessary to configure this to a node that is not the main controller. This is an advanced setting and should not be changed without a full understanding of the impact.
This parameter has the configuration ID wakeup_node
and is of type INTEGER
.
Association groups allow the device to send unsolicited reports to the controller, or other devices in the network. Using association groups can allow you to eliminate polling, providing instant feedback of a device state change without unnecessary network traffic.
The ZW100 supports 1 association group.
The Lifeline association group reports device status to a hub and is not designed to control other devices directly. When using the Lineline group with a hub, in most cases, only the lifeline group will need to be configured and normally the hub will perform this automatically during the device initialisation.
Association group 1 supports 5 nodes.
Command Class | Comment |
---|---|
COMMAND_CLASS_NO_OPERATION_V1 | |
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_SENSOR_BINARY_V1 | Linked to BASIC |
COMMAND_CLASS_SENSOR_MULTILEVEL_V5 | |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_DEVICE_RESET_LOCALLY_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V2 | |
COMMAND_CLASS_CONFIGURATION_V1 | |
COMMAND_CLASS_ALARM_V3 | |
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V1 | |
COMMAND_CLASS_POWERLEVEL_V1 | |
COMMAND_CLASS_FIRMWARE_UPDATE_MD_V1 | |
COMMAND_CLASS_BATTERY_V1 | |
COMMAND_CLASS_WAKE_UP_V2 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_VERSION_V2 |
Did you spot an error in the above definition or want to improve the content? You can contribute to the database here.