layout | title |
---|---|
documentation |
ZIF5029 - ZWave |
{% include base.html %}
This describes the Z-Wave device ZIF5029, manufactured by Logic Group with the thing type UID of logic_zif5029_00_000
.
The device is in the category of Power Outlet, defining Small devices to be plugged into a power socket in a wall which stick there.
The ZIF5029 supports routing. This allows the device to communicate using other routing enabled devices as intermediate routers. This device is also able to participate in the routing of data between other devices in the mesh network.
The ZIF5029 DIN-rail module is a device with a wireless Z-Wave communication protocol. It has 6 relay driven outputs and 6 pulse inputs (S0). The unit is a multi-purpose Z-Wave I/O module, which can be used for many applications. E.g. the module provides the possibility to control other systems via the Z-Wave network, by utilizing the 6 outputs as a kind of hand-over function to another automation system.
Upon delivery, the ZIF5029 module has not been enrolled into any Z-Wave network. To communicate with other devices in the Z-Wave network, ZIF5029 must be enrolled in the network. This process is called to include the device in the Z-Wave network. Devices can also be removed from the Z-Wave network if they are to be used in another installation. This is called to exclude the device from the Z-Wave network.
Both processes are initiated by setting the central network controls in either inclusion or exclusion mode. Please refer to the network controller's manual how to set the central controls in either inclusion or exclusion mode.
The inclusion / exclusion mode on the ZIF5029 device is activated by pressing the small button through the hole in the front of the module, marked "INCLUSION", after which the status LED will start flashing.
If the device already belongs to a network, the device must be excluded before it can be included in the current network, otherwise the inclusion process will fail.
Furthermore, see section 3 above about maintaining configuration parameters during exclusion / inclusion.
See inclusion section.
The relay outputs can be controlled from the Z-Wave network, and are suitable for switching up to 6 230Vac loads. When connecting to SELV (Safety Extra Low Voltage) and 230Vac power circuits for relay outputs, relays must be considered as two groups, where the first group includes output 1 to 3 and the second group includes the outputs 4 to 6. If one of the relays in the group is connected to a SELV circuit, the remaining outputs are not allowed to be connected to 230Vac or another circuit which is not a SELV circuit. This ensurescomplete separation between the SELV and 230Vac circuits.
For example, the relay outputs can be used to control the 230Vac power supply outlet, making it possible toturn on and disconnect the electrical outlets directly through the Z-Wave network. For safety reasons,however, it is recommended not to use the ZIF5029 to plug electrical outlets that are normally used for hazardous tools and machinery.
The 6 pulse inputs can be used for counting pulses from utility meters such as water meters and electricity meters with an output that generates pulses when a specific consumption measure has been reached. E.g. a water meter can generate a pulse per liter passing through the meter or 1,000 pulses per m 3 water. ZIF5029 can translate these pulses to a Command Class Metering Report which is sent over the Z-Wave network.
All 6 inputs can be used for different utility meters. For instance, input 1 can be connected to an electricity meter, input 2 to a water meter and so on. It is possible to individually configure the utility meter type connected to each input.
In addition, the ZIF5029 also acts as a repeater, thus extending the range of the Z-Wave network.
The following table summarises the channels available for the ZIF5029 -:
Channel Name | Channel ID | Channel Type | Category | Item Type |
---|---|---|---|---|
Switch | switch_binary | switch_binary | Switch | Switch |
Electric meter (pulses) | meter_pulse | meter_pulse | Energy | Number |
Switch 1 | switch_binary1 | switch_binary | Switch | Switch |
Switch 2 | switch_binary2 | switch_binary | Switch | Switch |
Switch 3 | switch_binary3 | switch_binary | Switch | Switch |
Switch 4 | switch_binary4 | switch_binary | Switch | Switch |
Switch 5 | switch_binary5 | switch_binary | Switch | Switch |
Switch 6 | switch_binary6 | switch_binary | Switch | Switch |
Electric meter (pulses) 1 | meter_pulse7 | meter_pulse | Energy | Number |
Electric meter (pulses) 2 | meter_pulse8 | meter_pulse | Energy | Number |
Electric meter (pulses) 3 | meter_pulse9 | meter_pulse | Energy | Number |
Electric meter (pulses) 4 | meter_pulse10 | meter_pulse | Energy | Number |
Electric meter (pulses) 5 | meter_pulse11 | meter_pulse | Energy | Number |
Electric meter (pulses) 6 | meter_pulse12 | meter_pulse | Energy | Number |
Switch the power on and off.
The switch_binary
channel is of type switch_binary
and supports the Switch
item and is in the Switch
category.
Indicates the pulse count.
The meter_pulse
channel is of type meter_pulse
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Switch the power on and off.
The switch_binary1
channel is of type switch_binary
and supports the Switch
item and is in the Switch
category.
Switch the power on and off.
The switch_binary2
channel is of type switch_binary
and supports the Switch
item and is in the Switch
category.
Switch the power on and off.
The switch_binary3
channel is of type switch_binary
and supports the Switch
item and is in the Switch
category.
Switch the power on and off.
The switch_binary4
channel is of type switch_binary
and supports the Switch
item and is in the Switch
category.
Switch the power on and off.
The switch_binary5
channel is of type switch_binary
and supports the Switch
item and is in the Switch
category.
Switch the power on and off.
The switch_binary6
channel is of type switch_binary
and supports the Switch
item and is in the Switch
category.
Indicates the pulse count.
The meter_pulse7
channel is of type meter_pulse
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Indicates the pulse count.
The meter_pulse8
channel is of type meter_pulse
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Indicates the pulse count.
The meter_pulse9
channel is of type meter_pulse
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Indicates the pulse count.
The meter_pulse10
channel is of type meter_pulse
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Indicates the pulse count.
The meter_pulse11
channel is of type meter_pulse
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
Indicates the pulse count.
The meter_pulse12
channel is of type meter_pulse
and supports the Number
item and is in the Energy
category. This is a read only channel so will only be updated following state changes from the device.
The following table provides a summary of the 39 configuration parameters available in the ZIF5029. Detailed information on each parameter can be found in the sections below.
Param | Name | Description |
---|---|---|
1 | Status of LED | Status of LED |
2 | Brightness of status LED | Brightness of status LED |
3 | Output Function, Output 1 | Output Function, Output 1 |
4 | Output Function, Output 2 | Output Function, Output 2 |
5 | Output Function, Output 3 | Output Function, Output 3 |
6 | Output Function, Output 4 | Output Function, Output 4 |
7 | Output Function, Output 5 | Output Function, Output 5 |
8 | Output Function, Output 6 | Output Function, Output 6 |
9 | Meter Type of input 1 | Meter Type of input 1 |
10 | Scale Type of input 1 | Scale Type of input 1 |
11 | Precision of input 1 | Precision of input 1 |
12 | Pulses per Unit of input 1 | Pulses per Unit of input 1 |
13 | Rate Type of input 1 | Rate Type of input 1 |
14 | Meter Type of input 2 | Meter Type of input 2 |
15 | Scale Type of input 2 | Scale Type of input 2 |
16 | Precision of input 2. | Precision of input 2. |
17 | Pulses per Unit of input 2 | Pulses per Unit of input 2 |
18 | Rate Type of input 2 | Rate Type of input 2 |
19 | Meter Type of input 3 | Meter Type of input 3 |
20 | Scale Type of input 3 | Scale Type of input 3 |
21 | Precision of input 3 | Precision of input 3 |
22 | Pulses per Unit of input 3 | Pulses per Unit of input 3 |
23 | Rate Type of input 3. | Rate Type of input 3. |
24 | Meter Type of input 4. | Meter Type of input 4. |
25 | Scale Type of input 4 | Scale Type of input 4. |
26 | Precision of input 4 | Precision of input 4 |
27 | Pulses per Unit of input 4 | Pulses per Unit of input 4 |
28 | Rate Type of input 4 | Rate Type of input 4 |
29 | Meter Type of input 5 | Meter Type of input 5 |
30 | Scale Type of input 5 | Scale Type of input 5 |
31 | Precision of input 5 | Precision of input 5 |
32 | Pulses per Unit of input 5 | Pulses per Unit of input 5 |
33 | Rate Type of input 5. | Rate Type of input 5. |
34 | Meter Type of input 6 | Meter Type of input 6 |
35 | Scale Type of input 6 | Scale Type of input 6 |
36 | Precision of input 6 | Precision of input 6 |
37 | Pulses per Unit of input 6 | Pulses per Unit of input 6 |
38 | Rate Type of input 6 | Rate Type of input 6 |
39 | Time interval between meter reports | Time interval between meter reports |
Status of LED This parameter can be used to change the mode of the front-mounted status LED. The following option values may be configured -:
Value | Description |
---|---|
0 | The LED is Off |
1 | The LED is steadily lit-up. (Standard) |
2 | The LED flashes in 1 second interval |
3 | The LED flashes in 1⁄2 second interval |
The manufacturer defined default value is 1
(The LED is steadily lit-up. (Standard)).
This parameter has the configuration ID config_1_1
and is of type INTEGER
.
Brightness of status LED Determines the brightness of the status LED.
<td>
<strong>Description</strong>
</td>
<td>
Switch off LED
</td>
<td>
Brightness level (%). (Standard 50%)
</td>
Value |
1-99 |
The manufacturer defined default value is 50
.
This parameter has the configuration ID config_2_1
and is of type INTEGER
.
Output Function, Output 1
<td>
<strong>Description</strong>
</td>
<td>
Output is controlled via Z-Wave messages. (Standard)
</td>
<td>
(Not applicable)
</td>
Value |
1 |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_3_1
and is of type INTEGER
.
Output Function, Output 2
<td>
<strong>Description</strong>
</td>
<td>
Output is controlled via Z-Wave messages. (Standard)
</td>
<td>
(Not applicable)
</td>
Value |
1 |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_4_1
and is of type INTEGER
.
Output Function, Output 3
<td>
<strong>Description</strong>
</td>
<td>
Output is controlled via Z-Wave messages. (Standard)
</td>
<td>
(Not applicable)
</td>
Value |
1 |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_5_1
and is of type INTEGER
.
Output Function, Output 4
<td>
<strong>Description</strong>
</td>
<td>
Output is controlled via Z-Wave messages. (Standard)
</td>
<td>
(Not applicable)
</td>
Value |
1 |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_6_1
and is of type INTEGER
.
Output Function, Output 5
<td>
<strong>Description</strong>
</td>
<td>
Output is controlled via Z-Wave messages. (Standard)
</td>
<td>
(Not applicable)
</td>
Value |
1 |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_7_1
and is of type INTEGER
.
Output Function, Output 6
<td>
<strong>Description</strong>
</td>
<td>
Output is controlled via Z-Wave messages. (Standard)
</td>
<td>
(Not applicable)
</td>
Value |
1 |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_8_1
and is of type INTEGER
.
Meter Type of input 1 Specifies the type of meter connected to input 1.
This parameter is retained during exclusion / inclusion of the device. The following option values may be configured -:
Value | Description |
---|---|
0 | Input not in use |
1 | Electricity meter. (Standard) |
2 | Gas meter. |
3 | Water meter. |
4 | Heat meter |
5 | Cooling meter |
The manufacturer defined default value is 1
(Electricity meter. (Standard)).
This parameter has the configuration ID config_9_1
and is of type INTEGER
.
Scale Type of input 1 Specifies unit type for the chosen meter type connected to input 1.
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Value</strong>
</td>
<td>
<strong>Description</strong>
</td>
<td>
</td>
<td>
kWh
</td>
<td>
1
</td>
<td>
kVAh
</td>
<td>
2
</td>
<td>
W
</td>
<td>
3
</td>
<td>
Pulse counter (Standard)
</td>
<td>
4
</td>
<td>
V
</td>
<td>
5
</td>
<td>
A
</td>
<td>
6
</td>
<td>
Power Factor
</td>
<td>
</td>
<td>
Cubic meter
</td>
<td>
1
</td>
<td>
Cubic foot
</td>
<td>
2
</td>
<td>
Reserved
</td>
<td>
3
</td>
<td>
Pulse counter
</td>
<td>
</td>
<td>
Cubic meter
</td>
<td>
1
</td>
<td>
Cubic foot
</td>
<td>
2
</td>
<td>
US gallons
</td>
<td>
3
</td>
<td>
Pulse counter
</td>
<td>
</td>
<td>
kWh
</td>
<td>
</td>
<td>
kWh
</td>
Chosen Meter Type |
Electricity meter (1) |
Gas meter (2) |
Water meter (3) |
Heat meter (4) |
Cooling meter (5) |
The manufacturer defined default value is 3
.
This parameter has the configuration ID config_10_1
and is of type INTEGER
.
Precision of input 1 Specifies the number of decimals in the measurement format for entry 1. For example, if this field is set to 1, the value will be sent with 1 decimal (e.g. 102.5).
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Description</strong>
</td>
<td>
Number of decimals. Standard is 0.
</td>
Value |
0-7 |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_11_1
and is of type INTEGER
.
Pulses per Unit of input 1 Specifies the number of pulses to count before one unit is reached at input 1. For example, if this parameter is set to 1,000 and Scale Type is set to Cubic meters, 1,000 pulses is counted to equal 1m 3 .
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Description</strong>
</td>
<td>
Number of pulses needed to equal one scale value. Standard is 1
</td>
Value |
0 – 65000 |
The manufacturer defined default value is 1
.
This parameter has the configuration ID config_12_2
and is of type INTEGER
.
Rate Type of input 1 Specifies if the meter at input 1 register consumption or production. This is only used in Metering Reports sent on the Z-Wave network.
This parameter is retained during exclusion / inclusion of the device. The following option values may be configured -:
Value | Description |
---|---|
0 | Unspecified |
1 | Import (consumption) |
2 | Export (production) |
3 | Reserved. |
The manufacturer defined default value is 1
(Import (consumption)).
This parameter has the configuration ID config_13_1
and is of type INTEGER
.
Meter Type of input 2 Specifies the type of meter connected to input 2.
This parameter is retained during exclusion / inclusion of the device. The following option values may be configured -:
Value | Description |
---|---|
0 | Input not in use. |
1 | Electricity meter. (Standard) |
2 | Gas meter |
3 | Water meter. |
4 | Heat meter. |
5 | Cooling meter. |
The manufacturer defined default value is 1
(Electricity meter. (Standard)).
This parameter has the configuration ID config_14_1
and is of type INTEGER
.
Scale Type of input 2 Specifies unit type for the chosen meter type connected to input 2.
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Value</strong>
</td>
<td>
<strong>Description</strong>
</td>
<td>
</td>
<td>
kWh
</td>
<td>
1
</td>
<td>
kVAh
</td>
<td>
2
</td>
<td>
W
</td>
<td>
3
</td>
<td>
Pulse counter (Standard)
</td>
<td>
4
</td>
<td>
V
</td>
<td>
5
</td>
<td>
A
</td>
<td>
6
</td>
<td>
Power Factor
</td>
<td>
</td>
<td>
Cubic meter
</td>
<td>
1
</td>
<td>
Cubic foot
</td>
<td>
2
</td>
<td>
Reserved
</td>
<td>
3
</td>
<td>
Pulse counter
</td>
<td>
</td>
<td>
Cubic meter
</td>
<td>
1
</td>
<td>
Cubic foot
</td>
<td>
2
</td>
<td>
US gallons
</td>
<td>
3
</td>
<td>
Pulse counter
</td>
<td>
</td>
<td>
kWh
</td>
<td>
</td>
<td>
kWh
</td>
Chosen Meter Type |
Electricity meter (1) |
Gas meter (2) |
Water meter (3) |
Heat meter (4) |
Cooling meter (5) |
The manufacturer defined default value is 3
.
This parameter has the configuration ID config_15_1
and is of type INTEGER
.
Precision of input 2. Specifies the number of decimals in the measurement format for input 2. For example, if this field is set to 1, the value will be sent with 1 decimal (e.g. 102.5).
This parameter is retained during exclusion / inclusion of the device.
<td>
Description
</td>
<td>
Number of decimals. Standard is 0.
</td>
Value |
0-7 |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_16_1
and is of type INTEGER
.
Pulses per Unit of input 2 Specifies the number of pulses to count before one unit is reached at input 2. For example, if this parameter is set to 1,000 and Scale Type is set to Cubic meters, 1,000 pulses is counted to equal 1m 3 .
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Description</strong>
</td>
<td>
Number of pulses needed to equal one scale value. Standard is 1
</td>
Value |
0 – 65000 |
The manufacturer defined default value is 1
.
This parameter has the configuration ID config_17_2
and is of type INTEGER
.
Rate Type of input 2 Specifies if the meter at input 2 register consumption or production. This is only used in Metering Reports sent on the Z-Wave network.
This parameter is retained during exclusion / inclusion of the device. The following option values may be configured -:
Value | Description |
---|---|
0 | Unspecified |
1 | Import (consumption) |
2 | Export (production). |
3 | Reserved. |
The manufacturer defined default value is 1
(Import (consumption)).
This parameter has the configuration ID config_18_1
and is of type INTEGER
.
Meter Type of input 3 Specifies the type of meter connected to input 3.
This parameter is retained during exclusion / inclusion of the device. The following option values may be configured -:
Value | Description |
---|---|
0 | Input not in use |
1 | Electricity meter |
2 | Gas meter |
3 | Water meter |
4 | Heat meter |
5 | Cooling meter |
The manufacturer defined default value is 5
(Cooling meter).
This parameter has the configuration ID config_19_1
and is of type INTEGER
.
Scale Type of input 3 Specifies unit type for the chosen meter type connected to input 3.
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Value</strong>
</td>
<td>
<strong>Description</strong>
</td>
<td>
</td>
<td>
kWh
</td>
<td>
1
</td>
<td>
kVAh
</td>
<td>
2
</td>
<td>
W
</td>
<td>
3
</td>
<td>
Pulse counter (Standard)
</td>
<td>
4
</td>
<td>
V
</td>
<td>
5
</td>
<td>
A
</td>
<td>
6
</td>
<td>
Power Factor
</td>
<td>
</td>
<td>
Cubic meter
</td>
<td>
1
</td>
<td>
Cubic foot
</td>
<td>
2
</td>
<td>
Reserved
</td>
<td>
3
</td>
<td>
Pulse counter
</td>
<td>
</td>
<td>
Cubic meter
</td>
<td>
1
</td>
<td>
Cubic foot
</td>
<td>
2
</td>
<td>
US gallons
</td>
<td>
3
</td>
<td>
Pulse counter
</td>
<td>
</td>
<td>
kWh
</td>
<td>
</td>
<td>
kWh
</td>
Chosen Meter Type |
Electricity meter (1) |
Gas meter (2) |
Water meter (3) |
Heat meter (4) |
Cooling meter (5) |
The manufacturer defined default value is 3
.
This parameter has the configuration ID config_20_1
and is of type INTEGER
.
Precision of input 3 Specifies the number of decimals in the measurement format for input 3. For example, if this field is set to 1, the value will be sent with 1 decimal (e.g. 102.5).
This parameter is retained during exclusion / inclusion of the device.
<td>
Description
</td>
<td>
Number of decimals. Standard is 0.
</td>
Value |
0-7 |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_21_1
and is of type INTEGER
.
Pulses per Unit of input 3 Specifies the number of pulses to count before one unit is reached at input 3. For example, if this parameter is set to 1,000 and Scale Type is set to Cubic meters, 1,000 pulses is counted to equal 1m 3 .
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Description</strong>
</td>
<td>
Number of pulses needed to equal one scale value. Standard is 1
</td>
Value |
0 – 65000 |
The manufacturer defined default value is 1
.
This parameter has the configuration ID config_22_2
and is of type INTEGER
.
Rate Type of input 3. Specifies if the meter at input 3 register consumption or production. This is only used in Metering Reports sent on the Z-Wave network.
This parameter is retained during exclusion / inclusion of the device. The following option values may be configured -:
Value | Description |
---|---|
0 | Unspecified |
1 | Import (consumption) |
2 | Export (production). |
3 | Reserved. |
The manufacturer defined default value is 1
(Import (consumption)).
This parameter has the configuration ID config_23_1
and is of type INTEGER
.
Meter Type of input 4. Specifies the type of meter connected to input 4.
This parameter is retained during exclusion / inclusion of the device. The following option values may be configured -:
Value | Description |
---|---|
0 | Input not in use |
1 | Electricity meter |
2 | Gas meter. |
3 | Water meter. |
4 | Heat meter |
5 | Cooling meter. |
The manufacturer defined default value is 1
(Electricity meter).
This parameter has the configuration ID config_24_1
and is of type INTEGER
.
Scale Type of input 4. Specifies unit type for the chosen meter type connected to input 4.
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Value</strong>
</td>
<td>
<strong>Description</strong>
</td>
<td>
</td>
<td>
kWh
</td>
<td>
1
</td>
<td>
kVAh
</td>
<td>
2
</td>
<td>
W
</td>
<td>
3
</td>
<td>
Pulse counter (Standard)
</td>
<td>
4
</td>
<td>
V
</td>
<td>
5
</td>
<td>
A
</td>
<td>
6
</td>
<td>
Power Factor
</td>
<td>
</td>
<td>
Cubic meter
</td>
<td>
1
</td>
<td>
Cubic foot
</td>
<td>
2
</td>
<td>
Reserved
</td>
<td>
3
</td>
<td>
Pulse counter
</td>
<td>
</td>
<td>
Cubic meter
</td>
<td>
1
</td>
<td>
Cubic foot
</td>
<td>
2
</td>
<td>
US gallons
</td>
<td>
3
</td>
<td>
Pulse counter
</td>
<td>
</td>
<td>
kWh
</td>
<td>
</td>
<td>
kWh
</td>
Chosen Meter Type |
Electricity meter (1) |
Gas meter (2) |
Water meter (3) |
Heat meter (4) |
Cooling meter (5) |
The manufacturer defined default value is 3
.
This parameter has the configuration ID config_25_1
and is of type INTEGER
.
Precision of input 4 Specifies the number of decimals in the measurement format for input 4. For example, if this field is set to 1, the value will be sent with 1 decimal (e.g. 102.5).
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Description</strong>
</td>
<td>
Number of decimals. Standard is 0.
</td>
Value |
0-7 |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_26_1
and is of type INTEGER
.
Pulses per Unit of input 4 Specifies the number of pulses to count before one unit is reached at input 4. For example, if this parameter isset to 1,000 and Scale Type is set to Cubic meters, 1,000 pulses is counted to equal 1m 3 .
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Description</strong>
</td>
<td>
Number of pulses needed to equal one scale value. Standard is 1
</td>
Value |
0-65000 |
The manufacturer defined default value is 1
.
This parameter has the configuration ID config_27_2
and is of type INTEGER
.
Rate Type of input 4 Specifies if the meter at input 4 register consumption or production. This is only used in Metering Reports sent on the Z-Wave network.
This parameter is retained during exclusion / inclusion of the device. The following option values may be configured -:
Value | Description |
---|---|
0 | Unspecified |
1 | Import (consumption) |
2 | Export (production) |
3 | Reserved. |
The manufacturer defined default value is 1
(Import (consumption)).
This parameter has the configuration ID config_28_1
and is of type INTEGER
.
Meter Type of input 5 Specifies the type of meter connected to input 5.
This parameter is retained during exclusion / inclusion of the device. The following option values may be configured -:
Value | Description |
---|---|
0 | Input not in use |
1 | Electricity meter. (Standard) |
2 | Gas meter. |
3 | Water meter. |
4 | Heat meter. |
5 | Cooling meter. |
The manufacturer defined default value is 1
(Electricity meter. (Standard)).
This parameter has the configuration ID config_29_1
and is of type INTEGER
.
Scale Type of input 5 Specifies unit type for the chosen meter type connected to input 5.
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Value</strong>
</td>
<td>
<strong>Description</strong>
</td>
<td>
</td>
<td>
kWh
</td>
<td>
1
</td>
<td>
kVAh
</td>
<td>
2
</td>
<td>
W
</td>
<td>
3
</td>
<td>
Pulse counter (Standard)
</td>
<td>
4
</td>
<td>
V
</td>
<td>
5
</td>
<td>
A
</td>
<td>
6
</td>
<td>
Power Factor
</td>
<td>
</td>
<td>
Cubic meter
</td>
<td>
1
</td>
<td>
Cubic foot
</td>
<td>
2
</td>
<td>
Reserved
</td>
<td>
3
</td>
<td>
Pulse counter
</td>
<td>
</td>
<td>
Cubic meter
</td>
<td>
1
</td>
<td>
Cubic foot
</td>
<td>
2
</td>
<td>
US gallons
</td>
<td>
3
</td>
<td>
Pulse counter
</td>
<td>
</td>
<td>
kWh
</td>
<td>
</td>
<td>
kWh<br /><br />
</td>
Chosen Meter Type |
Electricity meter (1) |
Gas meter (2) |
Water meter (3) |
Heat meter (4) |
Cooling meter (5) |
The manufacturer defined default value is 3
.
This parameter has the configuration ID config_30_1
and is of type INTEGER
.
Precision of input 5 Specifies the number of decimals in the measurement format for input 5. For example, if this field is set to 1, the value will be sent with 1 decimal (e.g. 102.5).
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Description</strong>
</td>
<td>
Number of decimals. Standard is 0.
</td>
Value |
0-7 |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_31_1
and is of type INTEGER
.
Pulses per Unit of input 5 Specifies the number of pulses to count before one unit is reached at input 5. For example, if this parameter is set to 1,000 and Scale Type is set to Cubic meters, 1,000 pulses is counted to equal 1m 3 .
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Description</strong>
</td>
<td>
Number of pulses needed to equal one scale value. Standard is 1
</td>
Value |
0-65000 |
The manufacturer defined default value is 1
.
This parameter has the configuration ID config_32_2
and is of type INTEGER
.
Rate Type of input 5. Specifies if the meter at input 5 register consumption or production. This is only used in Metering Reports sent on the Z-Wave network.
This parameter is retained during exclusion / inclusion of the device. The following option values may be configured -:
Value | Description |
---|---|
0 | Unspecified |
1 | Import (consumption). |
2 | Export (production). |
3 | Reserved. |
The manufacturer defined default value is 1
(Import (consumption).).
This parameter has the configuration ID config_33_1
and is of type INTEGER
.
Meter Type of input 6 Specifies the type of meter connected to input 6.
This parameter is retained during exclusion / inclusion of the device. The following option values may be configured -:
Value | Description |
---|---|
0 | Input not in use |
1 | Electricity meter |
2 | Gas meter |
3 | Water meter |
4 | Heat meter. |
5 | Cooling meter |
The manufacturer defined default value is 1
(Electricity meter).
This parameter has the configuration ID config_34_1
and is of type INTEGER
.
Scale Type of input 6 Specifies unit type for the chosen meter type connected to input 6.
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Value</strong>
</td>
<td>
<strong>Description</strong>
</td>
<td>
</td>
<td>
kWh
</td>
<td>
1
</td>
<td>
kVAh
</td>
<td>
2
</td>
<td>
W
</td>
<td>
3
</td>
<td>
Pulse counter (Standard)
</td>
<td>
4
</td>
<td>
V
</td>
<td>
5
</td>
<td>
A
</td>
<td>
6
</td>
<td>
Power Factor
</td>
<td>
</td>
<td>
Cubic meter
</td>
<td>
1
</td>
<td>
Cubic foot
</td>
<td>
2
</td>
<td>
Reserved
</td>
<td>
3
</td>
<td>
Pulse counter
</td>
<td>
</td>
<td>
Cubic meter
</td>
<td>
1
</td>
<td>
Cubic foot
</td>
<td>
2
</td>
<td>
US gallons
</td>
<td>
3
</td>
<td>
Pulse counter
</td>
<td>
</td>
<td>
kWh
</td>
<td>
</td>
<td>
kWh<br /><br />
</td>
Chosen Meter Type |
Electricity meter (1) |
Gas meter (2) |
Water meter (3) |
Heat meter (4) |
Cooling meter (5) |
The manufacturer defined default value is 3
.
This parameter has the configuration ID config_35_1
and is of type INTEGER
.
Precision of input 6 Specifies the number of decimals in the measurement format for input 6. For example, if this field is set to 1, the value will be sent with 1 decimal (e.g. 102.5).
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Description</strong>
</td>
<td>
Number of decimals. Standard is 0
</td>
Value |
0-7 |
The manufacturer defined default value is 0
.
This parameter has the configuration ID config_36_1
and is of type INTEGER
.
Pulses per Unit of input 6 Specifies the number of pulses to count before one unit is reached at input 6. For example, if this parameter is set to 1,000 and Scale Type is set to Cubic meters, 1,000 pulses is counted to equal 1m 3 .
This parameter is retained during exclusion / inclusion of the device.
<td>
<strong>Description</strong>
</td>
<td>
Number of pulses needed to equal one scale value. Standard is 1
</td>
Value |
0-65000 |
The manufacturer defined default value is 1
.
This parameter has the configuration ID config_37_2
and is of type INTEGER
.
Rate Type of input 6 Specifies if the meter at input 6 register consumption or production. This is only used in Metering Reports sent on the Z-Wave network.
This parameter is retained during exclusion / inclusion of the device. The following option values may be configured -:
Value | Description |
---|---|
0 | Unspecified |
1 | Import (consumption). |
2 | Export (production) |
3 | Reserved. |
The manufacturer defined default value is 1
(Import (consumption).).
This parameter has the configuration ID config_38_1
and is of type INTEGER
.
Time interval between meter reports Specifies the time interval between the automatic Meter Reports for each input.
<td>
<strong>Description</strong>
</td>
<td>
0 – 864 seconds. Standard value is 90 (equal to 900 seconds) which will send a report every 15 minute.
</td>
Value |
0 – 8640 |
The manufacturer defined default value is 90
.
This parameter has the configuration ID config_39_2
and is of type INTEGER
.
Association groups allow the device to send unsolicited reports to the controller, or other devices in the network. Using association groups can allow you to eliminate polling, providing instant feedback of a device state change without unnecessary network traffic.
The ZIF5029 supports 1 association group.
The Lifeline association group reports device status to a hub and is not designed to control other devices directly. When using the Lineline group with a hub, in most cases, only the lifeline group will need to be configured and normally the hub will perform this automatically during the device initialisation. Lifeline group for the entire module.
Association group 1 supports 1 node.
Command Class | Comment |
---|---|
COMMAND_CLASS_NO_OPERATION_V1 | |
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_SWITCH_BINARY_V1 | Linked to BASIC |
COMMAND_CLASS_METER_V3 | |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_DEVICE_RESET_LOCALLY_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_MULTI_CHANNEL_V2 | |
COMMAND_CLASS_CONFIGURATION_V1 | |
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V1 | |
COMMAND_CLASS_POWERLEVEL_V1 | |
COMMAND_CLASS_FIRMWARE_UPDATE_MD_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_VERSION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 | |
COMMAND_CLASS_SECURITY_V1 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_SWITCH_BINARY_V1 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_SWITCH_BINARY_V1 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_SWITCH_BINARY_V1 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_SWITCH_BINARY_V1 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_SWITCH_BINARY_V1 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_SWITCH_BINARY_V1 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_METER_V3 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_METER_V3 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_METER_V3 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_METER_V3 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_METER_V3 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Command Class | Comment |
---|---|
COMMAND_CLASS_BASIC_V1 | |
COMMAND_CLASS_METER_V3 | Linked to BASIC |
COMMAND_CLASS_ASSOCIATION_GRP_INFO_V1 | |
COMMAND_CLASS_ZWAVEPLUS_INFO_V1 | |
COMMAND_CLASS_ASSOCIATION_V2 | |
COMMAND_CLASS_MULTI_CHANNEL_ASSOCIATION_V3 |
Did you spot an error in the above definition or want to improve the content? You can contribute to the database here.