Sensoair Air quality sensor for indoor use

This describes the Z-Wave device Sensoair, manufactured by SIEGENIA-AUBI KG with the thing type UID of siegeniaaubi_sensoair_00_000.

The device is in the category of Sensor, defining Device used to measure something.

Sensoair product image

The Sensoair supports routing. This allows the device to communicate using other routing enabled devices as intermediate routers. This device is also able to participate in the routing of data between other devices in the mesh network.

Overview

This device measures levels og carbon dioxide & VOCs.

Inclusion Information

Press the push-button on the bottom of the unit once.

Exclusion Information

Press the push-button on the bottom of the unit once.

Channels

The following table summarises the channels available for the Sensoair -:

Channel Name Channel ID Channel Type Category Item Type
Sensor (CO2) sensor_co2 sensor_co2 CarbonDioxide Number

Sensor (CO2)

Indicates the CO2 level.

The sensor_co2 channel is of type sensor_co2 and supports the Number item and is in the CarbonDioxide category. This is a read only channel so will only be updated following state changes from the device.

Device Configuration

The following table provides a summary of the 2 configuration parameters available in the Sensoair. Detailed information on each parameter can be found in the sections below.

Param Name Description
1 Device Configuration Value 1 Configuration of the device operating mode
2 Interval for unsolicited Sensor Report Mode B defines how often a Sensor report is sent

Parameter 1: Device Configuration Value 1

Configuration of the device operating mode

  • bit 0    Unsolicited Multilevel Report Mode A    0 = disabled, 1 = enabled
  • bit 1    Unsolicited Multilevel Report Mode B    0 = disabled, 1 = enabled
  • bit 2    Basic Set                                         0 = disabled, 1 = enabled
  • bit 3    Broadcast Multilevel Report                 0 = disabled, 1 = enabled
  • bit 7    SENSOAIR LEDs                               0 = disabled, 1 = enabled

Unsolicited Multilevel Report Mode A

SENSOAIR sends an usolicited multilevel report when the CO2 value
exceeds one of the following threshold values:
600 ppm, 800 ppm, 1000 ppm, 1500 ppm, 2000 ppm, 2500 ppm

**Unsolicited Multilevel Report Mode B
**

SENSOAIR sends the current CO2 value (without being requested) in an interval of
5 - 65000 seconds. The interval can be configured with parameter 2. Values in the range 0 to 143 may be set.

The manufacturer defined default value is 141.

This parameter has the configuration ID config_1_1 and is of type INTEGER.

Parameter 2: Interval for unsolicited Sensor Report Mode B

defines how often a Sensor report is sent When enabled by parameter 1, SENSOAIR sends the current CO2 value (without being requested) in an interval of 5 - 65000 seconds. The interval (default setting = 30s) is configured as follows:

Device Configuration Value 1 = MSB (default 0x00)

Device Configuration Value 2 = LSB (default 0x1e) Values in the range 5 to 65000 may be set.

The manufacturer defined default value is 30.

This parameter has the configuration ID config_2_2 and is of type INTEGER.

Association Groups

Association groups allow the device to send unsolicited reports to the controller, or other devices in the network. Using association groups can allow you to eliminate polling, providing instant feedback of a device state change without unnecessary network traffic.

The Sensoair supports 1 association group.

Group 1: Group 1

Association group 1 supports 5 nodes.

Technical Information

Endpoints

Endpoint 0

Command Class Comment
COMMAND_CLASS_NO_OPERATION_V1
COMMAND_CLASS_BASIC_V1
COMMAND_CLASS_SENSOR_MULTILEVEL_V3
COMMAND_CLASS_CONFIGURATION_V1
COMMAND_CLASS_MANUFACTURER_SPECIFIC_V1
COMMAND_CLASS_POWERLEVEL_V1
COMMAND_CLASS_ASSOCIATION_V1
COMMAND_CLASS_VERSION_V1
COMMAND_CLASS_SENSOR_CONFIGURATION_V1

Documentation Links


Did you spot an error in the above definition or want to improve the content? You can contribute to the database here.