Configuration

To use PowSyBl Open Load Flow for all power flow computations, you have to configure the load-flow module in your configuration file:

load-flow:
  default-impl-name: "OpenLoadFlow"

Generic parameters

Generic parameters are documented in PowSyBl Core.

The next section details the parameters that are specific to PowSyBl Open LoadFLow.

Specific parameters

voltageInitModeOverride
Additional voltage init modes of PowSyBl Open Load Flow that are not present in PowSyBl LoadFlow voltageInitMode Parameter:

  • NONE: no override
  • VOLTAGE_MAGNITUDE: specific initializer to initialize voltages magnitudes $v$, leaving $\theta=0$. Proven useful for unusual input data with transformers rated voltages very far away from bus nominal voltages.
  • FULL_VOLTAGE: voltages magnitudes $v$ initialized using VOLTAGE_MAGNITUDE initializer, $\theta$ initialized using a DC load flow.

The default value is NONE.

lowImpedanceBranchMode
The lowImpedanceBranchMode property is an optional property that defines how to deal with low impedance branches (when $Z$ is less than the per-unit lowImpedanceThreshold, see further below). Possible values are:

  • Use REPLACE_BY_ZERO_IMPEDANCE_LINE if you want to consider low impedance branches as zero impedance branches.
  • Use REPLACE_BY_MIN_IMPEDANCE_LINE if you want to consider low impedance branches with a value equal to the lowImpedanceThreshold.

The default value is REPLACE_BY_ZERO_IMPEDANCE_LINE.

lowImpedanceThreshold
The lowImpedanceThreshold property is an optional property that defines in per-unit the threshold used to identify low impedance branches (when $Z$ is less than the lowImpedanceThreshold per-unit threshold).
The default value is $10^{-8}$ and it must be greater than 0.

slackDistributionFailureBehavior
This option defines the behavior in case the slack distribution fails. Available options are:

  • THROW if you want an exception to be thrown in case of failure
  • FAIL if you want the OuterLoopStatus to be FAILED in case of failure
  • LEAVE_ON_SLACK_BUS if you want to leave the remaining slack on the slack bus
  • DISTRIBUTE_ON_REFERENCE_GENERATOR if you want to put the slack on the reference generator, disregarding active power limits. There must be a reference generator defined, i.e. referenceBusSelectionMode must be GENERATOR_REFERENCE_PRIORITY - otherwise this mode falls back to FAIL mode automatically.

The default value is LEAVE_ON_SLACK_BUS.

slackBusSelectionMode
The slackBusSelectionMode property is an optional property that defines how to select the slack bus. The three options are available through the configuration file:

  • FIRST if you want to choose the first bus of all the network buses.
  • NAME if you want to choose a specific bus as the slack bus. In that case, the slackBusesIds property has to be filled.
  • MOST_MESHED if you want to choose the most meshed bus among buses with the highest nominal voltage as the slack bus. This option is typically required for computation with several synchronous components.
  • LARGEST_GENERATOR if you want to choose the bus with the highest total generation capacity as the slack bus.

The default value is MOST_MESHED.

Note that if you want to choose the slack buses that are defined inside the network with a slack terminal extension, you have to set the PowSyBl LoadFlow readSlackBus Parameter to true. When readSlackBus is set to true, slackBusSelectionMode is still used and serves as a secondary selection criteria:

  • for e.g. synchronous components where no slack terminal extension is present.
  • for e.g. synchronous components where more than maxSlackBusCount slack terminal extensions are present.

mostMeshedSlackBusSelectorMaxNominalVoltagePercentile
This option is used when slackBusSelectionMode is set to MOST_MESHED. It sets the maximum nominal voltage percentile. The default value is 95 and it must be inside the interval [0, 100].

maxSlackBusCount
Number of slack buses to be selected. Setting a value above 1 can help convergence on very large networks with large initial imbalances, where it might be difficult to find a single slack with sufficient branches connected and able to absorb or evacuate the slack power.
The default value is 1.

slackBusesIds
The slackBusesIds property is a required property if you choose NAME for property slackBusSelectionMode. It defines a prioritized list of buses or voltage levels to be chosen for slack bus selection (as an array, or as a comma or semicolon separated string).

slackBusCountryFilter
The slackBusCountryFilter defines a list of countries where slack bus should be selected (as an array, or as a comma or semicolon separated string).
Countries are specified by their alpha 2 code (e.g. FR, BE, DE, ...).
The default value is an empty list (any country can be used for slack bus selection).

loadPowerFactorConstant
The loadPowerFactorConstant property is an optional boolean property. This property is used in the outer loop that distributes slack on loads if :

  • distributedSlack property is set to true in the load flow default parameters,
  • balanceType property is set to PROPORTIONAL_TO_LOAD or PROPORTIONAL_TO_CONFORM_LOAD in the load flow default parameters.

The default value is false.

If prerequisites fulfilled and loadPowerFactorConstant property is set to true, the distributed slack outer loop adjusts the load P value and adjusts also the load Q value in order to maintain the power factor as a constant value. At the end of the load flow calculation, $P$ and $Q$ at loads terminals are both updated. Note that the power factor of a load is given by this equation :

$$ Power Factor = {\frac {P} {\sqrt {P^2+{Q^2}}}} $$

Maintaining the power factor constant from an updated active power $P^‎\prime$ means we have to isolate $Q^‎\prime$ in this equation :

$$ {\frac {P} {\sqrt {P^2+{Q^2}}}}={\frac {P^‎\prime} {\sqrt {P^‎\prime^2+{Q^‎\prime^2}}}} $$

Finally, a simple rule of three is implemented in the outer loop :

$$ Q^\prime={\frac {Q P^\prime} {P}} $$

If balanceType equals to PROPORTIONAL_TO_LOAD, the power factor remains constant scaling the global $P0$ and $Q0$ of the load. If balanceType equals to PROPORTIONAL_TO_CONFORM_LOAD, the power factor remains constant scaling only the variable parts. Thus, we fully rely on load detail extension.

In both cases, slack is not distributed to fictitious loads. A load can be fictitious by setting its boolean attribute isFictitious or by having a loadType equal to LoadType.FICTITIOUS.

The default value for loadPowerFactorConstant property is false.

slackBusPMaxMismatch
When slack distribution is enabled (distributedSlack set to true in LoadFlowParameters), this is the threshold below which slack power is considered to be distributed.
The default value is 1 MW and it must be greater or equal to 0 MW.

areaInterchangeControl
The areaInterchangeControl property is an optional property that defines if the area interchange control outer loop is enabled. If set to true, the area interchange control outer loop will be used instead of the slack distribution outer loop.
The default value is false.

areaInterchangeControlAreaType
Defines the areaType of the areas on which the area interchange control is applied. Only the areas of the input network that have this type will be considered.
The default value is ControlArea.

areaInterchangePMaxMismatch
Defines the maximum interchange mismatch tolerance for area interchange control. The default value is 2 MW and it must be greater than 0 MW.

voltageRemoteControl
The voltageRemoteControl property is an optional property that defines if the remote control for voltage controllers has to be modeled. If set to false, any existing voltage remote control is converted to a local control, rescaling the target voltage according to the nominal voltage ratio between the remote regulated bus and the equipment terminal bus.
The default value is true.

voltageRemoteControlRobustMode
When set to true, the algorithm for remote voltage control is more robust to inconsistent voltage targets that might otherwise cause unrealistic voltage exceptions and cause a loadflow failure. The control of unrealistic voltage is performed after the reactive limit outerloop. In addition, groups with unrealistic voltage when entering the reactive limit outerloop, but that do not exceed their reactive diagram are moved PQ and their reactive injection is set to targetQ. With this parameter set to true it is in general possible to set the minRealisticVoltage and maxRealisticVoltage values to 0.8pu and 1.2pu.

Note that when this option is set to true, instead of failing with an unrealistic voltage at a controller bus, the load flow may produce a solution where a voltage controlled bus does not reach the target voltage, while voltage controllers still have reactive power margin available.

The default value is true.

voltagePerReactivePowerControl
Whether simulation of static VAR compensators with voltage control enabled and a slope defined should be enabled (See voltage per reactive power control extension).
The default value is false.

generatorReactivePowerRemoteControl
Whether simulation of generators reactive power remote control should be enabled (See remote reactive power control).
The default value is false.

disableInconsistentVoltageControl
If multiple generators (or batteries, or VSC converters, or static VAR compensators) are connected to the same bus but either control different buses, either have different target voltages, then their voltage control is disabled if disableInconsistentVoltageControl is set to true. If the parameter is set to false, then only the control of the first generator is kept and applied to all the other generators. The default value is false.

secondaryVoltageControl
Whether simulation of secondary voltage control should be enabled.
Modeling of secondary voltage control has been designed to provide a fast, static, approximation of the equilibrium state of the generator reactive power alignment process that controls the voltage of a remote pilot point. This reactive power alignment process typically takes several minutes on the network. The default value is false.

Please note that the secondaryVoltageControl implementation has the folowing limitation:
Generators that belongs to a secondary voltage control zone should be in local voltage control only. If secondaryVoltageControl is set to true, generators that belongs to a secondary voltage control zone and that are configured for remote voltage control are switched to local voltage control with an initial local target equals to remoteTarget / remoteNominalV * localNominalV .

reactiveLimitsMaxPqPvSwitch
When useReactiveLimits is set to true, this parameter is used to limit the number of times an equipment performing voltage control is switching from PQ to PV type. After this number of PQ/PV type switch, the equipment will not change PV/PQ type anymore.
The default value is 3 and it must be greater or equal to 0.

forceTargetQInReactiveLimits
When useReactiveLimits is set to true, this parameter is used to prioritize the reactive power limits over the input target Q when target Q is outside these limits. If set to true, if any generator has a target Q which is outside its reactive power limits (for its given target P), then its target Q is overriden by the value of the exceeded limit (minQ or maxQ). The default value is false.

phaseShifterControlMode

  • CONTINUOUS_WITH_DISCRETISATION: phase shifter control is solved by the Newton-Raphson inner-loop.
  • INCREMENTAL: phase shifter control is solved in the outer-loop

The default value is CONTINUOUS_WITH_DISCRETISATION.

transformerVoltageControlMode
This parameter defines which kind of outer loops is used for transformer voltage controls. We have three kinds of outer loops:

  • WITH_GENERATOR_VOLTAGE_CONTROL means that a continuous voltage control is performed in the same time as the generator voltage control. The final transformer $\rho$ is obtained by rounding to the closest tap position. The control deadband is not taken into account.
  • AFTER_GENERATOR_VOLTAGE_CONTROL means that a continuous voltage control is performed after the generator voltage control. The final transformer $\rho$ is obtained by rounding to the closest tap position. The control deadband is taken into account.
  • INCREMENTAL_VOLTAGE_CONTROL means that an incremental voltage control is used. $\rho$ always corresponds to a tap position. Tap changes using sensitivity computations. The control deadband is taken into account.

The default value is WITH_GENERATOR_VOLTAGE_CONTROL.

transformerReactivePowerControl
This parameter enables the reactive power control of transformer through a dedicated incremental reactive power control outer loop. The default value is false.

incrementalTransformerRatioTapControlOuterLoopMaxTapShift
Maximum number of tap position change during a single iteration of the incremental voltage and or reactive power control outer loop. Applies when transformerVoltageControlMode is set to INCREMENTAL_VOLTAGE_CONTROL and or when transformerReactivePowerControl is enabled (true). The default value is 3.

shuntVoltageControlMode
This parameter defines which kind of outer loops is used for the shunt voltage control. We have two kinds of outer loops:

  • WITH_GENERATOR_VOLTAGE_CONTROL means that a continuous voltage control is performed in the same time as the generator voltage control. Susceptance is finally rounded to the closest section for shunt that are controlling voltage. The control deadband is not taken into account.
  • INCREMENTAL_VOLTAGE_CONTROL means that an incremental voltage control is used. Susceptance always corresponds to a section. Section changes using sensitivity computations. The control deadband is taken into account.

The default value is WITH_GENERATOR_VOLTAGE_CONTROL.

svcVoltageMonitoring
Whether simulation of static VAR compensators voltage monitoring should be enabled.
The default value is true.

acSolverType
AC load flow solver engine. Currently, it can be one of:

  • NEWTON_RAPHSON is the standard Newton-Raphson algorithm for load flow. Solves linear systems via Sparse LU decomposition (by SuiteSparse);
  • NEWTON_KRYLOV is also the standard Newton-Raphson algorithm for load flow. Solves linear systems via Krylov subspace methods for indefinite non-symmetric matrices (by Kinsol).

The default value is NEWTON_RAPHSON.

maxOuterLoopIterations
Maximum number of iterations for Newton-Raphson outer loop.
The default value is 20 and it must be greater or equal to 1.

newtonRaphsonStoppingCriteriaType
Stopping criteria for Newton-Raphson algorithm.

  • UNIFORM_CRITERIA: stop when quadratic norm of all mismatches vector is below quadratic norm of mismatches of value newtonRaphsonConvEpsPerEq. This criteria is defined by the following formula (for $n$ equations):

$$\sqrt {mismatch_1^2 + mismatch_2^2 + ... + mismatch_n^2} < \sqrt{n * newtonRaphsonConvEpsPerEq^2}$$

newtonRaphsonConvEpsPerEq defines the corresponding threshold for all equation types, in per-unit. The default value is $10^{-4} \text{p.u.}$ and must be greater than 0.

  • PER_EQUATION_TYPE_CRITERIA: stop when equation mismatches are below equation type specific thresholds:
    • maxActivePowerMismatch: Defines the threshold for active power equations, in MW. The default value is $10^{-2} \text{MW}$ and it must be greater than 0.
    • maxReactivePowerMismatch: Defines the threshold for reactive power equations, in MVAr. The default value is $10^{-2} \text{MVAr}$ and it must be greater than 0.
    • maxVoltageMismatch: Defines the threshold for voltage equations, in per-unit. The default value is $10^{-4} \text{p.u.}$ and it must be greater than 0.
    • maxAngleMismatch: Defines the threshold for angle equations, in radians. The default value is $10^{-5} \text{rad}$ and it must be greater than 0.
    • maxRatioMismatch: Defines the threshold for ratio equations, unitless. The default value is $10^{-5}$ and it must be greater than 0.
    • maxSusceptanceMismatch: Defines the threshold for susceptance equations, in per-unit. The default value is $10^{-4} \text{p.u.}$ and it must be greater than 0.

The default value is UNIFORM_CRITERIA.

maxNewtonRaphsonIterations
Only applies if acSolverType is NEWTON_RAPHSON. Maximum number of iterations for Newton-Raphson inner loop.
The default value is 15 and it must be greater or equal to 1.

maxNewtonKrylovIterations
Only applies if acSolverType is NEWTON_KRYLOV. Maximum number of iterations for Newton-Raphson inner loop. The default value is 100 and it must be greater or equal to 1.

stateVectorScalingMode
Only applies if acSolverType is NEWTON_RAPHSON. This parameter 'slows down' the Newton-Raphson by scaling the state vector between iterations. Can help convergence in some cases.

  • NONE: no scaling is made
  • LINE_SEARCH: applies a line search strategy
  • MAX_VOLTAGE_CHANGE: scale by limiting voltage updates to a maximum amplitude p.u. and a maximum angle.

The default value is NONE.

lineSearchStateVectorScalingMaxIteration
Only applies if acSolverType is NEWTON_RAPHSON and if stateVectorScalingMode is LINE_SEARCH.
Maximum iterations for a vector scaling when applying a line search strategy.
The default value is 10 and it must be greater or equal to 1.

lineSearchStateVectorScalingStepFold
Only applies if acSolverType is NEWTON_RAPHSON and if stateVectorScalingMode is LINE_SEARCH.
At the iteration $i$ of vector scaling with the line search strategy, with this parameter having the value $s$ , the step size will be $ \mu = \frac{1}{s^i}$ .
The default value is 4/3 = 1.333 and it must be greater than 1.

maxVoltageChangeStateVectorScalingMaxDv
Only applies if acSolverType is NEWTON_RAPHSON and if stateVectorScalingMode is MAX_VOLTAGE_CHANGE.
Maximum amplitude p.u. for a voltage change.
The default value is 0.1 p.u. and it must be greater than 0.

maxVoltageChangeStateVectorScalingMaxDphi
Only applies if acSolverType is NEWTON_RAPHSON and if stateVectorScalingMode is MAX_VOLTAGE_CHANGE.
Maximum angle for a voltage change.
The default value is 0.174533 radians (10°) and it must be greater than 0.

newtonKrylovLineSearch
Only applies if acSolverType is NEWTON_KRYLOV. Activates or deactivates line search for the Newton-Raphson Kinsol solver. The default value is false.

plausibleActivePowerLimit
The plausibleActivePowerLimit property is an optional property that defines a maximal active power limit for generators to be considered as participating elements for:

  • slack distribution (if balanceType equals to any of the PROPORTIONAL_TO_GENERATION_<any> types)
  • slack selection (if slackBusSelectionMode equals to LARGEST_GENERATOR)

The default value is $5000 MW$.

minPlausibleTargetVoltage and maxPlausibleTargetVoltage
Equipments with voltage regulation target voltage outside these per-unit thresholds are considered suspect and are discarded from regulation prior to load flow resolution.
The default values are 0.8 and 1.2 and they must be greater or equal to 0.

minRealisticVoltage and maxRealisticVoltage
These parameters are used to identify if the AC Solver has converged to an unrealistic state.

For any component where a bus voltage is solved outside these per-unit thresholds, the component solution is deemed unrealistic and its solution status is flagged as failed.

If voltageRemoteControlRobustMode is set to true, the check of unrealistic voltage is done after the ReactiveLimits outerloop has been used. In addition, the ReactiveLimits outerloop uses these values as a criteria to block PQ remote controler buses that have an unrealistic voltage and a reactive injection within their reactive diagram.

The default values are 0.5 and 2.0 and they must be greater or equal to 0.

reactiveRangeCheckMode
Open Load Flow discards voltage control for generators with a too small reactive power range, because in practice a too small reactive power ranger means limited to zero voltage control capability.

For a given active power output, the reactive power range is defined as $MaxQ - MinQ$ (always a positive value).
The maximum and minimum reactive range of a generator is:

  • for generators without reactive limits: infinity
  • for generators with reactive limits defined by a pair of min/max values, both minimum and maximum reactive range are equal to $MaxQ - MinQ$
  • for generators with reactive limits defined by a reactive capability curve, the minimum (resp. maximum) reactive range is obtained by finding the curve point having the minimum (resp. maximum) $MaxQ - MinQ$.

The reactiveRangeCheckMode parameter defines how generator reactive power range is to be tested. If the test does not pass, meaning the reactive power range is too small, then the voltage control is disabled:

  • MIN_MAX mode tests if the minimum reactive range is not 0 MVAr and if the maximum reactive range is above 1 MVAr.
  • MAX mode tests if the maximum reactive range is above 1 MVAr.
  • TARGET_P tests if the reactive range at $TargetP$ is above 1 MVAr.

The default value is MAX.

reportedFeatures
This parameter allows to define a set of features which should generate additional reports (as an array, or as a comma or semicolon separated string). In current version this parameter can be used to request Newton-Raphson iterations report:

  • NEWTON_RAPHSON_LOAD_FLOW: report Newton-Raphson iteration log for load flow calculations.
  • NEWTON_RAPHSON_SECURITY_ANALYSIS: report Newton-Raphson iteration log for security analysis calculations.
  • NEWTON_RAPHSON_SENSITIVITY_ANALYSIS: report Newton-Raphson iteration log for sensitivity analysis calculations.

Newton-Raphson iterations report consist in reporting:

  • the involved synchronous component
  • the involved Newton-Raphson outer loop iteration
  • for each Newton-Raphson inner loop iteration:
    • maximum active power mismatch, the related bus Id with current solved voltage magnitude and angle.
    • maximum reactive power mismatch, the related bus Id with current solved voltage magnitude and angle.
    • maximum voltage control mismatch, the related bus Id with current solved voltage magnitude and angle.
    • the norm of the mismatch vector

The default value is an empty set of features to report.

networkCacheEnabled
This parameter is used to run fast simulations by applying incremental modifications on the network directly to the Open Load Flow internal modeling. The cache mode allows faster runs when modifications on the network are light. Not all modifications types are supported yet, currently supported modifications are:

  • target voltage modification
  • switch open/close status modification. The switches to be modified must be configured via the actionableSwitchesIds property (as an array, or as a comma or semicolon separated string).

The default value is false.

actionableSwitchesIds
This parameter list is used if networkCachedEnabled is activated. It defines a list of switches that might be modified (as an array, or as a comma or semicolon separated string). When one of the switches changes its status (open/close) and a load flow is run just after, the cache will be used to a faster resolution. Note that in the implementation, all the switches of that list will be considered as retained, leading to a size increase of the Jacobian matrix. The list should have a reasonable size, otherwise the simulation without cache use should be preferred.

alwaysUpdateNetwork
Update the iIDM network state even in case of non-convergence.
The default value is false.

debugDir
Allows to dump debug files to a specific directory.
The default value is undefined (null), disabling any debug files writing.

asymmetrical
Allows to run asymmetrical calculations. The default value is false.

useActiveLimits
Allows to ignore active power limits during calculations. Active power limits are mainly involved in slack distribution on generators. The default value is true.

disableVoltageControlOfGeneratorsOutsideActivePowerLimits
Disables voltage control for generators with targetP outside the interval [minP, maxP]. The default value is false.

minNominalVoltageTargetVoltageCheck
This parameter defines the minimal nominal voltage to check the target of voltage control in per-unit. The default value is 20 kV, meaning that under the controlled buses of voltage levels under this value are ignored from the check. It must be greater or equal to 0 kV.

reactivePowerDispatchMode
This parameter defines how reactive power is split among generators with controls (voltage or reactive power). It tries to divide reactive power among generators in the order described below. reactivePowerDispatchMode can be one of:

  • Q_EQUAL_PROPORTION
    1. If all concerned generators have pre-defined reactive keys via the Coordinated Reactive Control extension, then it splits Q proportional to reactive keys
    2. If they don't, but they have plausible reactive limits, split proportionally to the maximum reactive power range
    3. If they don't, split Q equally
  • K_EQUAL_PROPORTION
    1. If generators have plausible reactive limits, split Q proportionally to k, where k is defined by $ k = \frac{2 qToDispatch - qmax1 - qmin1 - qmax2 - qmin2 - ...}{qmax1 - qmin1 + qmax2 - qmin2 + ...} $
    2. If they don't, split Q equally

The default value is Q_EQUAL_PROPORTION.

disableVoltageControlOfGeneratorsOutsideActivePowerLimits
This parameter allows to disable the voltage control of generators which targetP is lower than minP or greater than maxP. The default value is false.

outerLoopNames

Note: This is an advanced parameter. Unless you have specific needs, use the default outer loop order built-in PowSyBl Open Load Flow.

This parameter allows to configure both the list of outer loops that can be executed and their explicit execution order. Each outer loop name specified in the list must be unique and match the NAME attribute of the respective outer loop.

By default, this parameter is set to null, and the activated outer loops are executed in a default order (as defined in DefaultAcOuterLoopConfig for AC Load Flow and DefaultDcOuterLoopConfig for DC Load Flow).

Here an example with slack distribution and reactive limits consideration, in AC Load Flow, when outerLoopNames is not used:

  • the creation of the DistributedSlack outerloop is driven by the parameter distributedSlack parameter.
  • the creation of the ReactiveLimits outerloop is driven by the parameter useReactiveLimits parameter.
  • PowSyBl Open Load Flow default order is to run the DistributedSlack outerloop first, and then the ReactiveLimits outerloop.

Continuing this example, the outer loops creation and execution order can be modified by setting outerLoopNames to value ['ReactiveLimits', 'DistributedSlack'], in this case PowSyBl Open Load Flow will the ReactiveLimits outerloop first, and then the DistributedSlack outerloop.

For AC load flow the supported outer loop names, their default execution order, and their corresponding high-level parameter, are:

  1. DistributedSlack / AreaInterchangeControl (parameters: distributedSlack / areaInterchangeControl)
  2. SecondaryVoltageControl (parameter: secondaryVoltageControl)
  3. VoltageMonitoring (parameter: svcVoltageMonitoring)
  4. ReactiveLimits (parameter: useReactiveLimits)
  5. PhaseControl / IncrementalPhaseControl (parameters: phaseShifterRegulationOn and phaseShifterControlMode)
  6. SimpleTransformerVoltageControl / TransformerVoltageControl / IncrementalTransformerVoltageControl (parameters: transformerVoltageControlOn and transformerVoltageControlMode)
  7. IncrementalTransformerReactivePowerControl (parameter: transformerReactivePowerControl)
  8. ShuntVoltageControl / IncrementalShuntVoltageControl (parameters: shuntVoltageControl and shuntVoltageControlMode)
  9. AutomationSystem (parameter: simulateAutomationSystems)

And for DC load flow:

  1. IncrementalPhaseControl (parameter: phaseShifterRegulationOn)
  2. AreaInterchangeControl (parameter: areaInterchangeControl)

linePerUnitMode
This parameter defines how lines ending in different nominal voltages at both sides are perunit-ed. linePerUnitMode can be one of:

  • IMPEDANCE: handle difference in nominal voltage via impedance correction
  • RATIO: handle difference in nominal voltage by introducing a ratio

The default value is IMPEDANCE.

useLoadModel
When set to true, this parameter enables the modeling of the ZIP or EXPONENTIAL response characteristic of a Load.

dcApproximationType
This parameter defines how resistance is neglected compared to inductance in DC approximation. dcApproximationType can be one of:

  • IGNORE_R: consider that r << x
  • IGNORE_G: consider that g << b

The default value is IGNORE_R.

simulateAutomationSystems
Allows to simulate automation systems that are modeled in the network. For the moment, the grid model only supports overload management systems. The default behaviour is false.

referenceBusSelectionMode
The reference bus is the bus where the angle is equal to zero. There are several mode of selection:

  • FIRST_SLACK: the angle reference bus is selected as the first slack bus among potentially multiple slacks (in case maxSlackBusCount > 1).
  • GENERATOR_REFERENCE_PRIORITY: the angle reference bus is selected from generator reference priorities defined via the Reference Priority extension.

The default value is FIRST_SLACK.

writeReferenceTerminals
This parameter allows to write to the IIDM network the Reference Terminals extension containing the generator terminals used as angle reference in the load flow calculation. There is one Terminal created/added in the extension for each calculated Synchronous Component. Works only when referenceBusSelectionMode is set to GENERATOR_REFERENCE_PRIORITY.

voltageTargetPriorities
When multiple equipment regulate the same bus with different voltage targets, this parameter enables configuring priority to resolve inconsistencies by aligning the voltage targets. Priority is determined by equipment type order; the voltage target of the equipment type listed first takes precedence over those listed later. By default, the order is ["GENERATOR", "TRANSFORMER", "SHUNT"].
Note that "GENERATOR" indistinctively includes generators, batteries, static var compensators, and VSC HVDC converters.

If the user specifies only a sub-list of priorities, this sub-list is completed by the order defined by default. Thus, if the user specifies only ["TRANSFORMER"], it will be completed to ["TRANSFORMER", "GENERATOR", "SHUNT"].

transformerVoltageControlUseInitialTapPosition
This parameter is only used if the transformer voltage control is enabled and of mode AFTER_GENERATOR_VOLTAGE_CONTROL. If this parameter is set to true, transformers of the same voltage control (meaning controlling the same bus) are merged and the algorithm tries to maintain the initial difference between rhos. If the voltage at controlled bus is closed to the target voltage at initial step of the outer loop, the algorithm blocks transformers at their initial tap positions. The default value of this parameter is false.

generatorVoltageControlMinNominalVoltage This parameter is only used if the transformer voltage control is enabled and of mode AFTER_GENERATOR_VOLTAGE_CONTROL. In this mode, at the first step of the outer loop, the transformers that controlled voltage are disabled, only generators are participating to voltage control. At second step, generators controlling voltage at a controlled bus above generatorVoltageControlMinNominalVoltage have their voltage control disabled. This parameter overrides an automatic detection of the minimal nominal voltage based on an analysis of nominal voltages controlled by transformers. The default value of this parameter is $-1$: with this value the parameter is ignored and the outer loop relies only on the automatic detection.

fictitiousGeneratorVoltageControlCheckMode
Specifies the active power checks exemption for fictitious generators voltage control.

PowSyBl open-loadflow performs these checks on generators:

  • if targetP equals zero, voltage control is disabled.
  • if parameter disableVoltageControlOfGeneratorsOutsideActivePowerLimits is enabled, a generator with a targetP lower than minP or greater than maxP, voltage control is disabled.

The fictitiousGeneratorVoltageControlCheckMode option controls whether the above checks must be performed for fictitious generators:

  • use mode FORCED for an exemption of the two previous checks for fictitious generators.
  • Use mode NORMAL for no exemption at all, i.e. fictitious generators are processed identically to real generators.

The default mode is FORCED.

Configuration file example

See below an extract of a config file that could help:

open-loadflow-default-parameters:
  lowImpedanceBranchMode: REPLACE_BY_ZERO_IMPEDANCE_LINE
  slackDistributionFailureBehavior: LEAVE_ON_SLACK_BUS
  voltageRemoteControl: false
  slackBusSelectionMode: NAME
  slackBusesIds: Bus3_0,Bus5_0
  loadPowerFactorConstant: true

At the moment, overriding the parameters by a JSON file is not supported by Open Load Flow.