| 1 | +--- |
| 2 | +layout: distill |
| 3 | +title: Dynamic Line Ratings |
| 4 | +description: Minimum level of system inertia necessary to ensure deployment of frequency responsive reserves. |
| 5 | +tags: inertia, frequency, ERCOT, ISO |
| 6 | +category: wiki |
| 7 | +bibliography: papers.bib |
| 8 | +--- |
| 9 | + |
| 10 | +**Dynamic Line Ratings (DLRs)** <d-cite key="miso2023ferc881"></d-cite> (p10) by MISO |
| 11 | + |
| 12 | +A transmission facility rating that: |
| 13 | +(1) applies to a time period of not greater than one hour; and |
| 14 | +(2) reflects up-to-date forecasts of inputs such as (but not limited to) ambient air temperature, wind, solar heating intensity, transmission line tension, or transmission line sag. |
| 15 | + |
| 16 | +**Ambient-Adjusted Ratings (AARs)** <d-cite key="miso2023ferc881"></d-cite> (p10) by MISO |
| 17 | + |
| 18 | +A transmission facility rating that: |
| 19 | +(1) applies to a time period of not greater than one hour; |
| 20 | +(2) reflects an up-to-date forecast of ambient air temperature across the time period to which the rating applies; |
| 21 | +(3) reflects the absence of solar heating during nighttime periods where the local sunrise/sunset times used to determine daytime and nighttime periods are updated at least monthly, if not more frequently; and |
| 22 | +(4) is calculated at least each hour, if not more frequently. |
| 23 | + |
| 24 | +**Emergency Rating** <d-cite key="miso2023ferc881"></d-cite> (p10) by MISO |
| 25 | + |
| 26 | +A transmission facility rating that reflects operation for a specified, finite period, rather than reflecting continuous operation. |
| 27 | +An emergency rating may assume acceptable loss of equipment life or other physical or safety limitations for the equipment involved |
| 28 | + |
| 29 | +**Facility** <d-cite key="miso2023ferc881"></d-cite> (p10) by MISO |
| 30 | + |
| 31 | +A set of electrical equipment ratings that collectively operates as a single bulk electric system element (e.g., transformers, relay protective devices, terminal equipment, and series and shunt compensation devices) |
| 32 | + |
| 33 | +**Facility Rating** <d-cite key="miso2023ferc881"></d-cite> (p10) by MISO |
| 34 | + |
| 35 | +The maximum or minimum voltage, current, frequency, or real or reactive power flow through a facility that does not violate the applicable equipment rating of any equipment comprising the facility |
0 commit comments