Grid Sensor Placement (TVA)

Sponsor: TVA (Tennessee Valley Authority) · Platform: qBraid · Hardware: IonQ Forte

The problem

TVA's grid is a network of substations joined by power lines. A PMU (phasor measurement unit) is a sensor that takes time-synchronized measurements, so operators can tell what state the grid is in. In the simple model used here, a PMU at a substation sees that substation and every substation directly connected to it. (The model assumes the needed measurements and line data are available. It doesn't test communications or data quality: say what TVA would check before installing anything.)

PMUs are expensive to install. What is the smallest set of substations that lets operators see every substation?

Everyday version: put security cameras at intersections so that every intersection is visible from at least one camera. Computer scientists call this the minimum dominating set problem. It maps naturally onto qubits: one qubit per substation, where 1 means "put a sensor here".

Background from TVA

TVA shared NERC's Reliability Guideline: PMU Placement and Installation (December 2016) as background for this track. It's in background/, with TVA's original problem in TVA's words. Three ideas from it shape the problem:

  1. There are two ways to state the goal. You can find the fewest PMUs that make the whole grid observable, which is milestones 2 to 5. Or you can find the most observability you can get from a fixed number of PMUs, which is the "fixed budget" stretch goal.
  2. Losing one PMU, or its data feed, can leave part of the grid unseen. That's why utilities plan for redundancy, which is the N-1 stretch goal.
  3. Utilities don't treat every substation the same. They score each candidate location by how many monitoring applications a PMU there would serve, such as state estimation, oscillation monitoring and angle monitoring, with a weight for each application. That's the priority-weights stretch goal.

Start here

  1. Open starter.ipynb in qBraid Lab with the qBraid-SDK (v0.12.2) kernel (pick it in the Select Kernel box).
  2. Run the cells from the top.
  3. Do the TODOs (there are 3). Each one has a hint.
  4. Early on, one teammate works through qaoa_primer.ipynb (the 6-node part, about 45 minutes) while the rest start milestones 1 and 2. It shows QAOA's three pieces (cost layer, mixer, optimizer) on a textbook problem, Max-Cut.
  5. Start your deck now. One teammate reads background/ and owns the customer questions in "Customer and value proposition" below. Bring them to a TVA mentor.

The data

File What it is
data/ieee14.json IEEE 14-bus test grid: 14 substations, 20 lines. The main grid.
data/ieee14_piece6.json A 6-substation piece of it, small enough for quantum hardware
data/ieee30.json IEEE 30-bus test grid, for the stretch goal

A bus is an electrical node in a substation; in these files there's one per substation. Each file lists the buses, the lines, the zero-injection buses (see stretch goals), the power plant buses and each bus's load. See data/README.md for sources.

check.py checks any placement: is it valid, which substations are unseen, and how sturdy it is. Once you have your own answer, check_placement(grid, chosen, compare=True) also says how far it is from the fewest possible (grids of 20 buses or fewer). Run %run check.py in a notebook cell for a demo.

Milestones

Times are suggested team time, including reading and experiments. Once your TODOs are in, the notebook runs in about a minute: spend the rest understanding the results, testing your own question, and building the pitch.

# Milestone Time What you do Done when
1 Understand it about 1 h Draw the grid and place sensors by hand. Pick one PMU application from NERC's guideline (in background/) and find out who uses it you have a placement, one sentence on what a PMU sees, and the application your team is designing for
2 Classical baseline 2 to 3 h A greedy rule and an exact integer program you have the optimal count and its runtime
3 Code the quantum cost function 1 to 2 h The number of sensors plus a large penalty for every unseen substation. Check it with the checker on the 6-substation piece. its cheapest answer matches the integer program, and you can say in one sentence how the primer's Max-Cut cost relates to yours
4 Run QAOA 3 to 4 h On the simulator: first the 6-substation piece, then all 14 you have a chart of how often QAOA finds an optimal placement and how often it leaves a substation unseen
5 IonQ hardware run about 2 h, early (queues can take hours) The 6-substation piece at 100 to 200 shots, after tuning on IonQ's free simulator with its noise model on. Recommended: run the same circuit on Quantinuum's free H2 emulator too. you have the job IDs and a chart comparing hardware with the simulator, with Quantinuum's emulator alongside if you ran it.
6 Tell the story all weekend, plus 2 to 3 h at the end Your five slides: what the sensors cost, what an operator gains, what happens if one fails, and where quantum honestly stands you can walk a judge through your slides in the time the organizers give you

Why a 6-substation piece for hardware: the full 14-substation QAOA circuit needs over 300 two-qubit gates per layer, far more than today's hardware runs well. The piece needs a few dozen.

What judges look for

On Sunday morning, you present your pitch deck to this track's judges, and they ask you to walk them through your work. Understanding and clarity count most: why your cost function works, what QAOA did, and what your results mean for a grid operator. Code counts less. See the main README.

Due Sunday 9:00 AM: your pitch deck and your code as a ZIP (what to submit, and where). Have your notebook and any tools you built, run with their outputs and your IonQ job IDs. Be ready to explain:

  • Your solution: where the sensors go, how many, and how much of the grid they see; what happens if one fails; greedy versus integer program versus QAOA; and your hardware result next to the simulator.
  • Customer and value proposition: who uses PMU data at a utility, and who approves the money? Ask a TVA mentor, or mark your guesses as guesses. What does a PMU cost installed? A 2014 U.S. Department of Energy report, Factors Affecting PMU Installation Costs, found that the average installed cost per PMU ranged from 40,000 to 180,000 dollars, and the device itself was usually under 5% of that. What does one fewer PMU save, and what does an operator gain from full coverage? Don't count savings the classical integer program already gets as a quantum benefit.
  • What you learned: where quantum honestly stands on this problem (see below).
  • What didn't work: if something failed or you couldn't find a solution, say so clearly and explain why. That earns points.

The notebook is a starter. Add your own code, cells and notebooks, try a different approach, and expand as far as you like.

Tools worth building (they count):

  • an interactive grid map where you click substations to place sensors and see what's covered;
  • a "what if a sensor fails" explorer;
  • a dashboard that puts greedy, the integer program and QAOA side by side;
  • a visual of QAOA's answers over time, or across noise settings.

Hardware rules

  • Tune on simulators first: Aer (Qiskit's simulator, running inside your Lab instance: instant and free, but its runs don't reach your Jobs page), then IonQ's free simulator (ionq:ionq:sim:simulator) with runtime_options={"noise_model": "forte-1"}. The notebook's hardware cell is set up for this.
  • Real hardware is IonQ Forte (ionq:ionq:qpu:forte-1) through qBraid. Run only your final, tuned circuit.
  • Cap every hardware run at 200 shots.
  • Send hardware runs early. Queues can take hours, so aim for Saturday, not Sunday morning.
  • Free second opinion: Quantinuum's H2 emulator (quantinuum:quantinuum:sim:h2-emulator). It models different hardware noise, readout error included. Run your tuned circuit there too and compare (the notebook's qBraid cell has the lines; accept Quantinuum's terms under Devices first). Label it as an emulator.
  • If ionq:ionq:qpu:forte-1 shows as unavailable, the same machine is on qBraid through AWS (aws:ionq:qpu:forte-1, about 1,630 credits for 200 shots).
  • If IonQ is down or the queue isn't moving, keep your job ID and your noisy-simulator result to show judges, and ask a qBraid mentor about IQM Garnet (aws:iqm:qpu:garnet) as a backup.
  • Keep the hardware circuit to a few dozen two-qubit gates. The notebook prints the count.

Stretch goals (pick any)

  • Zero-injection buses. A zero-injection bus has no load and no generator, so the power flowing in equals the power flowing out. That lets operators work out one unseen neighbor without a sensor. IEEE 14 bus 7 is one. Use check_placement(grid, chosen, zib=True). How many sensors does the rule save?
  • N-1 (every substation seen twice). The grid stays fully visible if any one sensor fails. Use check_placement(grid, chosen, n1=True) and ilp_placement(grid, twice=True). For QAOA, penalize each missing sighting: P × (2 − sightings) for a substation seen fewer than twice, with P > 1. (A flat penalty for "seen only once" lets invalid placements tie for best.)
  • Fixed budget. With only k sensors (try k = 2 or 3 on IEEE 14), place them to see as many substations as possible. This is the second goal in NERC's guideline. How does the cost function change when you can't afford full coverage?
  • Priority weights. Some substations matter more, such as big loads, power plants and the links between regions. Build a small priority table the way NERC's guideline suggests (a weight per application, times whether a PMU at that bus serves it), then use the weights where they can matter: with a fixed budget (k sensors, maximize the weighted substations seen), or by requiring high-priority substations to be seen twice. (A bigger penalty alone won't move the best placement when every substation can be covered.) See how the placement changes.
  • 30 substations on qBraid's GPU simulator (qbraid:qbraid:sim:gpu-sv, up to 35 qubits; free up to a daily limit, then 5 credits a minute). Load data/ieee30.json. The exact table of 2^30 costs no longer fits in memory, so switch to sampled shots.
  • TVA's other grids: IEEE 57, 118 and 300 (data/ieee57.json, data/ieee118.json, data/ieee300.json). Try your methods on them: the integer program still solves them in milliseconds, but QAOA needs one qubit per substation. What would quantum need to help at this size?

Honest quantum value

Judges reward teams that say plainly where quantum stands, with their own numbers. Answer these in your story:

  • How long does your integer program take on 14 substations, and on 30? How long does QAOA take, including the hardware queue?
  • How often does QAOA find a best placement, and how often does it leave a substation unseen? How does that compare with guessing at random?
  • To tune QAOA, the notebook computes the cost of every placement first. What does that mean for your speed comparison?
  • What would have to change, in the hardware or in the problem, for quantum to be worth it here?

Reading: Jones et al. 2020 (arXiv 2001.04489) tried a D-Wave quantum annealer on this problem for grids of several sizes. What did they find, and does your result agree?

Links

The qBraid Award

The qBraid Award is open to every team. It's optional; see ../4-qbraid-award/.