Common wiring configurations found in Miami-Dade, Broward, and Palm Beach County homes, organized by system type and era.
| Wire | Terminal | Function | Present In |
|---|---|---|---|
| Red | R (Rh/Rc) | 24V power from transformer | All systems |
| White | W (W1) | Stage 1 heat | Heat pump, gas furnace |
| Yellow | Y (Y1) | Stage 1 cooling (compressor) | All AC systems |
| Green | G | Indoor fan (blower) | All systems |
| Blue | C | Common (24V return) | Smart thermostats |
| Orange | O | Reversing valve — cool | Heat pumps (Carrier, Trane) |
| Orange | B | Reversing valve — heat | Heat pumps (Rheem, Ruud) |
| Brown/Pink | W2/Y2 | Stage 2 heat/cool | Two-stage systems |
Critical: Colors are conventions, not standards. A white wire might connect to Y if the installer ran out of yellow. Always verify at both ends — the thermostat terminal AND the air handler terminal board.
Found in: ~70% of South Florida homes with central AC and electric heat strip
Thermostat Air Handler
───────── ───────────
R ←── Red ──────→ R (24V hot)
Y ←── Yellow ───→ Y (compressor contactor)
G ←── Green ────→ G (blower relay)
W ←── White ────→ W (heat strip relay)
C ←── Blue ─────→ C (24V common)
Smart thermostat compatible: Yes, if C-wire present. If no C-wire (4-wire system): R, Y, G, W only. See C-wire solutions in main README.
If your existing cable only has 4 conductors (R, Y, G, W):
Option A — Add-a-Wire Kit:
- Install add-a-wire module at air handler
- Module converts one existing wire to carry both its signal AND the C signal
- No new cable needed
Option B — Run new cable:
- Replace 18/4 cable with 18/5 (adds blue C-wire)
- Route through same path as existing cable (usually attic)
- Tape new cable to old cable and pull through
Found in: Newer South Florida homes (2010+) with heat pump systems
Thermostat Air Handler
───────── ───────────
R ←── Red ──────→ R (24V hot)
Y ←── Yellow ───→ Y (compressor)
G ←── Green ────→ G (blower)
O ←── Orange ───→ O (reversing valve)
W2 ←── White ────→ W2 (aux heat strip)
C ←── Blue ─────→ C (common)
Smart thermostat setup notes:
- Set O/B to "O" (energize on cooling) for Carrier, Trane, Lennox, Goodman
- Set O/B to "B" (energize on heating) for Rheem, Ruud
- If unsure: try "O" first — if heat and cool seem reversed, switch to "B"
- Aux heat lockout: Set to 40°F in South Florida (prevents expensive heat strip use above 40°F)
Found in: Larger South Florida homes with variable or two-stage compressors
Thermostat Air Handler
───────── ───────────
R ←── Red ──────→ R (24V hot)
Y1 ←── Yellow ───→ Y1 (stage 1 compressor)
Y2 ←── Pink ─────→ Y2 (stage 2 compressor)
G ←── Green ────→ G (blower)
W ←── White ────→ W (heat)
C ←── Blue ─────→ C (common)
Notes: Stage 1 runs at ~67% capacity (quieter, more efficient). Stage 2 engages when demand is high. Most smart thermostats support this — configure in Equipment settings.
Found in: Additions, condos, converted garages
Mini-splits don't use traditional thermostat wiring. They communicate between indoor and outdoor units via proprietary cables. Smart thermostat integration options:
- IR Blaster (Sensibo, Cielo, Flair Puck): Mimics the remote control via infrared
- Wi-Fi module (manufacturer-specific): Daikin, Mitsubishi, Fujitsu offer their own
- Dry contact adapter: Some mini-splits accept a thermostat via dry contact terminals
- Check Y wire connection at air handler — loose terminal is the #1 cause
- Verify contactor is receiving 24V (multimeter across contactor coil)
- Check float switch — clogged condensate drain opens the safety float, breaking the circuit
- Y wire may be disconnected at the air handler or condenser disconnect
- Check outdoor unit breaker
- Verify condenser contactor is pulling in (24V from Y wire)
- W wire may be shorted to R at a junction
- Check for damaged cable in attic (rodent damage common in South Florida)
- Verify thermostat is calling for cool (Y), not heat (W)
- Check for a shorted wire in the cable run
- Verify thermostat differential isn't set too small
- Check for refrigerant issues (low charge causes high-pressure cutout)
- Always turn off power at the breaker before touching any wires
- Thermostat wires carry 24V AC — low voltage but can damage equipment if shorted
- If you see 120V or 240V wires near the thermostat location, those are NOT thermostat wires — do not connect them
- When in doubt, photograph everything and consult a licensed HVAC technician