Scheiber CAN Analysis for NMEA 2000

Reverse-engineering notes, evidence, tools, and reproducible integration work for a Scheiber marine CAN installation observed through a DSD TECH SH-C30A (CANable/Candlelight-compatible) USB-CAN adapter.

Project status: engineering reverse-engineering project, not an OEM protocol specification. Passive analysis remains the default workflow. An optional, isolated Cerbo GX bridge under cerbo/ implements the two generator commands that were live-validated on this installation; AC/House source-selection control remains disabled.

What is included

  • A complete, hash-identified 228.962 s candump capture, stored as one .xz file, with 4,401 valid extended-CAN frames and 45 CAN IDs.
  • A pure-Python decoder and CSV/JSON report generator.
  • A context-aware passive generator lifecycle state machine.
  • A tested Victron Cerbo GX connected-genset bridge with runit installer, rollback path, D-Bus integration, tanks, batteries, and diagnostics.
  • A native Cerbo GX Smart Anchor Watch & Alarm Service with geodesic projection, multi-hour Cairo vector chart & wind strip plot rendering, multi-sensor marine alarms, Scheiber deck light automation, and interactive Telegram control (docs/ANCHOR_WATCH.md).
  • A live-validated Signal K -> NMEA 2000 tank path using PGN 127505, including B&G Zeus3 compatibility guidance.
  • Wiring/setup instructions for the SH-C30A on Raspberry Pi and Cerbo GX.
  • A mapping register with datatypes, endianness, scales, offsets, units, observed ranges, confidence, and proposed NMEA 2000 PGNs.
  • A validation plan for the batteries, chargers, source panels, generator, and tanks.
  • Dry-run NMEA 2000 translation examples for mappings that are not yet live-enabled.

The historical analyzer does not transmit Scheiber control frames. The optional Cerbo bridge transmits only the live-tested generator START/STOP frame (0x02460B88) and explicitly does not transmit source-selector requests.

Known installation inventory

Item Count / capacity Current identification status
House batteries 6 Six individual CAN streams identified; voltage and SoC semantics established, physical battery 1-6 assignment pending
Engine start batteries 2 Two experimental streams (0x06140580, 0x06180580); port/starboard identity and voltage scale still require crank validation
Generator start battery 1 Starter voltage published from 0x00501020 bytes 0-1 LE x0.1 V
Battery chargers 3 Device families with credible 12 V / 60 A, 12 V / 40 A, and 12 V / 25 A signatures
Water tank 600 L Confirmed level mapping
Diesel tank 1 500 L Confirmed level mapping
Diesel tank 2 500 L Confirmed level mapping
Power source panels 2 AC panel and House panel request/applied states decoded; bridge uses applied state receive-only

The capacities and inventory are centrally defined in config/system_config.json.

Victron Cerbo GX integration

The tested bridge is documented in docs/CERBO_GX_INTEGRATION.md. The confirmed-versus-candidate generator, inverter, and charger fields are summarized in docs/POWER_DEVICE_METADATA_AUDIT.md.

It publishes:

com.victronenergy.genset.scheiber
com.victronenergy.grid.scheiber_shore
com.victronenergy.acsystem.scheiber_house
com.victronenergy.inverter.scheiber_mastervolt
com.victronenergy.switch.scheiber

which Victron's normal dbus-generator service matches to a connected-genset manager (com.victronenergy.generator.startstop1). Native Victron manual starts, automatic conditions, timed runs, runtime accounting, and stop commands therefore remain manager-owned rather than being reimplemented in the bridge.

The complete canonical runtime source is checked in directly as cerbo/bridge.py. It is not generated or patched during installation.

Current bridge:

version 5.10.2
SHA-256 83b555c1ed77cf60bf38b441e3e04c088d1c6ae74089a4f99b638492782908d4

Fresh install or update

The same repository installer is used for both a new installation and an update. Re-download it before running so an old local copy cannot retain obsolete deployment logic:

mkdir -p /data/scheiber-gx-installer
cd /data/scheiber-gx-installer
wget -O install.sh \
  https://raw.githubusercontent.com/danielkope/scheiber-can-analysis-nmea2000/main/cerbo/install.sh
chmod +x install.sh
CAN_IF=can2 CAN_BITRATE=250000 ./install.sh

The installer downloads the complete bridge.py, compiles it, verifies the pinned SHA-256, backs up the previous installed script when present, and restarts the runit service. See cerbo/README.md for separate fresh-install/update explanations and the integration guide for the system-battery requirement and post-stop OFF_IDLE restart caveat.

Key findings

Tanks — confirmed

CAN ID 0x02040580 is four big-endian unsigned 16-bit words:

02040580#0054003F004F0001
            |   |   |   +-- raw state/quality/sequence candidate = 1
            |   |   +------ diesel 2 = 0x004F = 79%
            |   +---------- diesel 1 = 0x003F = 63%
            +-------------- water    = 0x0054 = 84%

The Cerbo bridge publishes these as native Victron tank services with configured vessel capacities of 600 L / 500 L / 500 L. Victron /Capacity and /Remaining use cubic metres, so those values are published as 0.600 / 0.500 / 0.500 m3 and the corresponding remaining volume in m3. /Level remains percent.

Tanks on Signal K / NMEA 2000 — live

Signal K receives the Victron tank services as:

tanks.freshWater.90
tanks.fuel.91
tanks.fuel.92

The standard signalk-to-nmea2000 plugin has been live-tested forwarding them as PGN 127505 Fluid Level using NMEA tank instances 6, 7, and 8. Signal K then received those PGNs back from the VE.Can/NMEA 2000 connection with matching level and capacity values, proving the output was present on the NMEA 2000 bus.

The live mapping and B&G Zeus3 display/setup guidance are in docs/SIGNALK_NMEA2000.md. The consolidated standard-PGN register is in docs/NMEA2000_MAPPING.md.

Source selectors — confirmed, receive-only in bridge

The source enum is:

  • 0x01 = OFF
  • 0x02 = SHORE
  • 0x04 = GENERATOR

Request and applied-state frames are distinct:

Panel Request Applied
AC 0x02420B90 0x02400B90
House 0x02420B88 0x02400B88

Transfers from shore to generator include an applied intermediate OFF state, consistent with break-before-make behavior.

The Cerbo bridge only consumes the applied IDs and associated panel-voltage telemetry. It never transmits 0x02420B90 or 0x02420B88.

Generator lifecycle and control

The generator is represented by three complementary signal families:

CAN ID Datatype Scale / enum Role
0x02460B88 uint8 enum 01=START, 02=STOP External command / transaction trigger; live-tested transmit
0x02440B88 uint8 enum 00=OFF_IDLE, 01=RUNNING_SETTLED, 02/03=STARTING, 04/05=STOPPING Generator lifecycle/status confirmation
0x005A1020 bytes 0-1 uint16 little-endian x0.1 Hz Generator-specific AC-frequency milestone

START

02460B88#01                 -> STARTING
02440B88#02 or #03          -> STARTING confirmed
005A1020 ~= 50.0 Hz         -> RUNNING after confirmation hold
02440B88#01                 -> RUNNING_SETTLED

STOP

02460B88#02                 -> STOPPING
02440B88#05 or #04          -> STOPPING confirmed
005A1020 = 0.0 Hz           -> STOPPED
02440B88#00                 -> OFF_IDLE

The baseline capture contains START, STARTING confirmation, 50 Hz, RUNNING_SETTLED, STOP, STOPPING confirmation, frequency decay, and 0 Hz. It does not contain 02440B88#00; OFF_IDLE was confirmed in later live work.

Live generator-command validation

The exact one-byte commands were successfully transmitted on the installation:

cansend can2 02460B88#01   # START
cansend can2 02460B88#02   # STOP

The production bridge sends those commands only in response to the Victron connected-genset /Start command (or observes/adopts an externally generated Scheiber command). It sends no automatic CAN retry.

A key live finding is that STOPPED and OFF_IDLE are not equivalent for immediate restart. The engine can reach 0 Hz quickly while the Scheiber controller takes roughly another minute to emit 02440B88#00. A START sent in that settling interval was ignored; a START sent after OFF_IDLE worked. Bridge v5.4.2 documents this but does not yet queue an early start.

See docs/GENERATOR_LIFECYCLE.md and docs/CERBO_GX_INTEGRATION.md.

Why generator frequency is no longer treated as shared AC

Live testing separated the generator-specific 0x005A1020 signal from the shared 0x02040898 AC telemetry. With the generator off and shore power present, 0x005A1020 stayed at 0 Hz while 0x02040898 still reported approximately 235 V / 50 Hz. The Cerbo bridge therefore uses 0x005A1020 as generator-specific frequency and treats 0x02040898 as shared/fallback AC telemetry only.

Six house batteries

The six IDs are:

0x06020580  0x06060580  0x060A0580
0x060E0580  0x06120580  0x06160580

Each six-byte payload is decoded as:

Bytes Type Interpretation
0-1 uint16 little-endian, x0.01 Voltage in volts — confirmed
2-3 offset uint16 little-endian, raw - 0x4E00 Signed current code — zero/sign strong; x0.1 A remains a working scale candidate
4-5 uint16 little-endian SoC percent for this installation — confirmed by follow-on validation

The older temperature alternative is no longer used by the bridge. Physical battery 1-6 ordering still needs direct validation.

Three charger families

The repeated device suffixes 0x1008, 0x1010, and 0x1020 each have heartbeat, telemetry, configuration, rating, and frequency messages. Their 0x005610xx payload signatures contain:

Device family Constant bytes Rating interpretation Role hypothesis
0x1008 0C 3C 12 V / 60 A House/engine charging candidate
0x1010 0C 28 12 V / 40 A House/engine charging candidate
0x1020 0C 19 12 V / 25 A Generator-start charging family

For 0x005010xx, four little-endian uint16 values plausibly decode as DC voltage x0.1 V, DC current x0.1 A, AC input voltage x0.1 V, and 0xFFFF unavailable. Example:

00501008#8700D1003809FFFF
          135  209   2360  65535  (little-endian words)
         13.5V 20.9A 236.0V   NA  (candidate engineering units)

For 0x005A10xx, the first little-endian word is an AC-frequency field: 0x01F4 = 500 -> 50.0 Hz, 0x0190 = 400 -> 40.0 Hz, and zero when off.

Analyze a capture

python3 scripts/scheiber_can_analyze.py \
  your_capture.log \
  --config config/system_config.json \
  --output analysis-output

Important outputs include:

  • decoded_fields_long.csv
  • event_candidates.csv
  • generator_state_timeline.csv
  • tank_samples.csv
  • house_battery_candidates.csv
  • charger_candidates.csv
  • capture_metadata.json
  • summary.md

The live monitor also prints context-aware lifecycle transitions:

python3 scripts/live_monitor.py --channel can1

These analysis scripts remain passive/read-only.

Engineering report

The source report is docs/ENGINEERING_REPORT.md. It documents the original hash-identified capture and analysis baseline. Live control validation and the production Cerbo integration are maintained separately in the focused integration/lifecycle documents so the evidence provenance of the original report remains clear.

Rebuild the human-friendly PDF and DOCX with:

./scripts/build_report.sh

Reproduce a passive capture

1. Wire the Scheiber six-pin connector to the SH-C30A

Scheiber six-pin Function SH-C30A terminal
5 CAN-H CAN_H
6 CAN-L CAN_L
2, or installation-specific pin 3 GND GND
1 Recovery Not connected
4 +12 V Not connected

The SH-C30A is USB-powered. Do not connect Scheiber +12 V to it.

2. SH-C30A switches

  • Programming/boot switch: normal RUN/Candlelight position, not firmware-programming mode.
  • 120-ohm termination: normally OFF for a passive tap into an already terminated bus. Enable only if the adapter is physically replacing an end terminator.
  • With all power off, CAN-H to CAN-L should normally measure about 60 ohms for two 120-ohm end terminators.

Physical switch direction depends on the exact board revision; use the label and resistance measurement rather than assuming left/right orientation.

3. Raspberry Pi and SocketCAN

sudo apt update
sudo apt install -y can-utils python3 python3-venv python3-pip git

lsusb
ip -details link show

sudo ip link set can1 down 2>/dev/null || true
sudo ip link set can1 type can bitrate 250000 restart-ms 100
sudo ip link set can1 up
ip -details -statistics link show can1

The interface may enumerate as can0 instead of can1; substitute the actual name.

4. Capture to screen and file

candump can1
candump -L can1 > scheiber_$(date +%Y%m%d_%H%M%S).log

The -L format includes absolute timestamps and is accepted by the analyzer. candump -l can1 is also useful for automatic logfile naming.

Bus checks before trusting a capture

ip -details -statistics link show can1

Look for:

  • bitrate 250000
  • state ERROR-ACTIVE
  • no increasing RX/TX error counters
  • no dropped frames or repeated bus-off events

If there are no frames, verify CAN-H/CAN-L polarity, the common ground, interface name, bitrate, termination, and the gs_usb driver. If errors rise quickly or the interface goes bus-off, disconnect and correct wiring/termination before continuing.

NMEA 2000 gateway architecture

Scheiber CAN and NMEA 2000 remain separate protocols and separate CAN interfaces.

On the current Cerbo installation the preferred gateway path is:

Scheiber bus -> SH-C30A/can2 -> Victron D-Bus -> Signal K -> VE.Can/NMEA 2000

The three tank mappings are now live on NMEA 2000 as standard PGN 127505. Other mappings remain staged according to confidence: generator starter voltage is the recommended next battery value; experimental engine-battery identity/scale and candidate house current are not ready for authoritative NMEA 2000 publication.

See docs/SIGNALK_NMEA2000.md and docs/NMEA2000_MAPPING.md.

Repository layout

cerbo/                  canonical bridge.py, installer, and runit service
config/                 capacities, inventory, mappings
data/raw/               original candump capture (single .xz file)
data/examples/          selected evidence frames
data/derived/           generated CSV/JSON results
scripts/                passive analyzer, lifecycle tracker, and helper tools
docs/                   engineering, mapping, integration, and handoff docs
tests/                  decoder, lifecycle, and bridge-source regression tests

Source references

License and disclaimer

Code and original documentation in this repository are provided under the MIT License. The CAN capture remains experimental data from one installation. This project is not affiliated with or endorsed by Scheiber, Victron Energy, DSD TECH, Signal K, B&G, or the NMEA organization.

Generator and AC source control can create hazardous conditions. Only 0x02460B88#01/#02 has been live-validated for active use in the Cerbo bridge described here. Do not infer that other observed request/control frames are safe to transmit.