Cerbo GX integration package

This directory contains the active Venus OS integration for the Scheiber Multibloc V8 network. The passive analysis tools elsewhere in the repository remain read-only.

The installer deploys two independent runit services that share the same SocketCAN interface:

Service D-Bus service Purpose
scheiber-gx com.victronenergy.genset.scheiber plus tank/battery services Existing field-tested generator and telemetry bridge
scheiber-switch com.victronenergy.switch.scheiber Native GX switchboard controls and pump-running feedback

Keeping the switch service separate avoids destabilising the generator bridge while the newly decoded control-panel path is field-validated.

Native GX switchboard

The switch service publishes ten logical controls:

  • Electronics
  • Deck Floodlight
  • Navigation Lights
  • Anchor Light
  • Steaming Light
  • Port Bilge Pump
  • Starboard Bilge Pump
  • Fresh Water Pump
  • Fridge Unit
  • General Lighting

Anchor Light and both bilges use the native three-state GX control.

For each bilge the physical modes are:

OFF     AUTO=0  MANUAL=0
AUTO    AUTO=1  MANUAL=0
MANUAL  AUTO=1  MANUAL=1

The GX row presents OFF / AUTO / ON, where ON is Scheiber MANUAL/forced pumping. The ON segment also acts as the physical pump-activity lamp:

OFF, stopped       Off
AUTO, idle         Auto
AUTO, pumping      Auto + On
MANUAL             On

Actual activity comes from 0x02141808, not from the selected mode. It is also published as a separate read-only activity card for each bilge.

Fresh Water Pump is a simple OFF / ON enable. When ON, the existing pressure switch automatically starts the motor as taps are opened. A separate activity card displays Standby or ACTIVE from 0x02141808 bit 0.

The service never assumes an output is OFF. At startup every physical state is UNKNOWN; the service listens for the six paired state frames and issues CAN RTR state requests. Writes are rejected until the relevant state is known.

The physical keys are momentary events rather than explicit ON/OFF commands. A requested state is implemented by comparing desired state with synchronized CAN feedback, transmitting one captured-style 0x04001808 press/release pair, and waiting for authoritative output-state feedback. No direct CMD_S_TOR output forcing is used, so Scheiber interlocks remain authoritative.

Stable USB-CAN discovery

The Linux name assigned to the candleLight/gs_usb adapter is not stable. The same physical adapter may be can0, can1, or can2 after a reboot. The integration therefore does not persist a boot-specific canN name by default.

resolve_can_interface.py discovers the current interface using:

  1. driver gs_usb;
  2. exact USB serial number when configured;
  3. optional USB vendor/product IDs;
  4. a fail-closed rule if more than one device matches.

The main service is the single owner of discovery and CAN configuration. After bringing the interface up, it atomically publishes the selected name to:

/run/scheiber-can-if

The switch service waits for that file and uses the same interface. It never independently guesses a device.

Observed adapter identity on this vessel:

driver:       gs_usb
USB VID:PID:  1d50:606f
USB serial:   0025003C5457530220383638

The native Cerbo CAN controller is sun4i_can and is deliberately excluded from automatic gs_usb selection.

Canonical runtime files

cerbo/bridge.py                     existing generator/telemetry bridge
cerbo/resolve_can_interface.py      stable USB-CAN identity resolver
cerbo/scheiber_switch_protocol.py   pure switch protocol and state planner
cerbo/switch_service.py             native D-Bus/SocketCAN switch service
cerbo/service/run                   telemetry runit wrapper and CAN owner
cerbo/service-switch/run            switch-service runit wrapper
cerbo/install.sh                    transactional installer/updater
cerbo/uninstall.sh                  disables both services

The telemetry bridge is version 5.10.2, with canonical SHA-256:

83b555c1ed77cf60bf38b441e3e04c088d1c6ae74089a4f99b638492782908d4

Fresh installation or update with curl

SSH to the Cerbo as root. For a pinned PR/commit build:

mkdir -p /data/scheiber-gx-installer
cd /data/scheiber-gx-installer

REF="<commit-sha>"
RAW_BASE="https://raw.githubusercontent.com/danielkope/scheiber-can-analysis-nmea2000/${REF}/cerbo"

curl -fL "${RAW_BASE}/install.sh" -o install.sh
chmod 755 install.sh

CAN_IF=auto \
CAN_USB_SERIAL=0025003C5457530220383638 \
CAN_USB_VENDOR_ID=1d50 \
CAN_USB_PRODUCT_ID=606f \
CAN_BITRATE=250000 \
SWITCH_TX_ENABLED=1 \
SWITCH_RTR_ENABLED=1 \
RAW_BASE="${RAW_BASE}" \
./install.sh

CAN_IF=auto is preferred. If exactly one gs_usb device is connected and no serial is supplied, the installer auto-enrols its USB serial. Pinning the serial is still recommended because it remains unambiguous if another USB-CAN adapter is added later.

An explicit interface such as CAN_IF=can0 is supported for diagnostics, but it reintroduces boot-order dependence and should not be the normal vessel configuration.

SWITCH_TX_ENABLED=1 enables active panel-key CAN commands. Set it to 0 for receive-only UI validation. SWITCH_RTR_ENABLED=1 permits startup state-query frames.

The installer stages and compiles all Python sources, validates the pinned bridge hash, replaces the runtime files, persists the selector and USB identity, and starts both runit services. A failed fetch, compile, or checksum happens before the live files are replaced.

Verify the services

cat /run/scheiber-can-if
ip -details -statistics link show "$(cat /run/scheiber-can-if)"
sv status /service/scheiber-gx /service/scheiber-switch

tail -n 100 /data/scheiber-gx/bridge.log
tail -n 100 /data/scheiber-gx/switch.log

dbus -y com.victronenergy.switch.scheiber /Connected GetValue
dbus -y com.victronenergy.switch.scheiber \
  /Scheiber/SynchronizedOutputCount GetValue
dbus -y com.victronenergy.switch.scheiber \
  /SwitchableOutput/deck_floodlight/State GetValue
dbus -y com.victronenergy.switch.scheiber \
  /GenericInput/bilge_port_running/Value GetValue

The expected synchronized output count is 12. The current switch-service snapshot is written to:

/data/scheiber-gx/switch-status.json

Existing generator and tank verification

dbus -y com.victronenergy.genset.scheiber /Connected GetValue

for s in \
  com.victronenergy.tank.scheiber_fresh \
  com.victronenergy.tank.scheiber_diesel1 \
  com.victronenergy.tank.scheiber_diesel2
do
  echo "===== $s ====="
  for p in Level Capacity Remaining FluidType CustomName; do
    printf '%-12s ' "$p:"
    dbus -y "$s" "/$p" GetValue
  done
done

Node-RED Automations & Alarms

The repository includes ready-to-use Node-RED flows installed automatically when Node-RED is present:

1. Anchor Light Sunset/Sunrise Automation (node-red-anchor-light-flow.json)

  • Listens to /SwitchableOutput/anchor_light/Auto on com.victronenergy.switch.scheiber.
  • When Auto = 0 (Manual), the flow is inactive and preserves manual switch control.
  • When Auto = 1 (Auto mode):
    • Reads GPS position from com.victronenergy.gps (/Position/Latitude, /Position/Longitude) with fallback coordinates.
    • Computes astronomical sunrise and sunset times (NOAA solar algorithm).
    • Automatically commands /SwitchableOutput/anchor_light/State to 1 (ON) at sunset (15 min buffer) and 0 (OFF) at sunrise (30 min buffer).
    • Prevents command loops by only writing to D-Bus when state changes are needed.

2. Bilge Alarms & Continuous Monitoring (node-red-bilge-alarms-flow.json)

  • Tracks authoritative running status for Port & Starboard bilges via /GenericInput/bilge_{port,starboard}_running/Value (0x02141808).
  • 2-Minute Warning: Emits Venus GUI Warning if continuous pumping exceeds 2 minutes.
  • 5-Minute Critical Alarm: Emits Venus GUI Critical Alarm (potential water ingress) if continuous pumping exceeds 5 minutes. (Never stops the pump automatically).
  • Mode OFF Anomaly: Immediate critical alarm if a bilge pump is running while its GX switch is in OFF mode.
  • Frequent Cycling Warning: Alerts if a bilge cycles 4 or more times within a 60-minute window.

3. AC Power & Inverter Routing Matrix (node-red-ac-power-flow.json)

  • Tracks the vessel's 230V AC distribution topology (House Panel vs Air Conditioning Panel).
  • Publishes the normally-enabled MasterVolt 2000W fallback separately from whether it is currently supplying the House bus. Shared 0x02140898 ramp markers update inverter enable state only outside Shore/Generator transfers.
  • Monitors applied source selectors (Shore Power, Generator, MasterVolt Inverter, OFF) and live voltages.
  • Emits real-time state object to Node-RED debug dashboard and automation logic.

4. Generator-Only House Charger (node-red-house-charger-flow.json)

  • Uses Victron's canonical /Ac/ActiveIn/Source and permits charging only when it equals 2 (Generator).
  • Starts an automatic cycle below 80% SoC and retains that automatic cycle to 92%.
  • Keeps manual override state separate from automatic hysteresis, so turning GX Relay 1 OFF immediately cancels a manual cycle.
  • Drives GX Relay 2 as the third-party charger output; an invalid SoC, a non-Generator source, or SoC at/above 92% forces it OFF.

Read ../docs/AC_POWER_AND_INVERTERS.md for the complete 230V AC distribution, Scheiber transfer contactors, and inverter architecture.

Read ../docs/SWITCH_SERVICE_HANDOVER.md for the architecture, safety rules, field evidence, rollback procedure, and Node-RED alarm/automation plan.