Niagara 4 BQL/NEQL — Asset Discovery & Security Reference

Platform: Tridium Niagara 4 / JENEsys ProBuilder Interface: Workbench → CTRL+L (Open ORD / Query Dialog) Scope: Asset discovery, device inventory, network topology, real-time status, security posture — NO alarm data, NO trend history


How to Use

  1. Open Workbench
  2. Press CTRL+L to open the ORD query bar
  3. Paste any query from this repo
  4. Replace [stationName] with your actual station name where indicated
  5. Press Enter — results open in a Collection Table

For remote stations prefix every query with:

local:|fox:|station:|

Repository Structure

File Purpose
queries/01_device_inventory.md Enumerate all devices across every protocol
queries/02_point_inventory.md Enumerate all control points, I/O, virtual
queries/03_network_topology.md Driver/network map, routing, inter-station
queries/04_security_access.md Users, roles, permissions, audit trail
queries/05_realtime_status.md Device health: fault, down, stale, comms fail
queries/06_protocol_specific.md BACnet, Modbus, LonWorks, SNMP, KNX, OPC per-protocol queries
queries/07_neql_tagging.md NEQL tag/relation queries for tagged assets
queries/08_http_api.md HTTP ORD endpoints for external tooling/scripts
docs/BQL_Syntax.md Full BQL language reference
docs/NEQL_Reference.md Full NEQL tag/relation reference
docs/Type_Hierarchy.md Niagara type hierarchy for FROM clauses
docs/Encoding.md ORD encoding rules (colons, spaces, special chars)

Quick Reference — Most Useful Discovery Queries

-- ALL devices, all protocols
station:|slot:/Drivers|bql:select * from driver:Device

-- ALL control points, station-wide
station:|slot:/|bql:select slotPath, displayName, out, status from control:ControlPoint

-- ALL BACnet devices with address
station:|slot:/Drivers|bql:select name, address, deviceId, status from bacnet:BacnetDevice

-- ALL Modbus devices (TCP + RTU/Async)
station:|slot:/Drivers|bql:select * from modbusCore:ModbusClientDevice

-- Devices currently DOWN or FAULTED
station:|slot:/Drivers|bql:select slotPath, displayName, status from driver:Device where status.fault = true or status.down = true

-- Count all devices per driver network
station:|slot:/Drivers|bql:select parent.displayName as 'Network', count(name) as 'DeviceCount' from driver:Device

-- All users configured on station
station:|slot:/Services/UserService|bql:select * from user:User

-- NEQL: all tagged n:point assets
station:|slot:|neql:n:point|bql:select displayName, slotPath, ord

JENEsys ProBuilder Notes

  • JENEsys controllers run Niagara N4 — all BQL/NEQL syntax is identical
  • Default station name is typically the controller hostname
  • Access via Workbench → CTRL+L or File > Open > Open Query
  • ProBuilder often uses lonworks: driver — see 06_protocol_specific.md
  • HTTP ORD queries require Basic Hx Profile enabled on the JACE