InfluxDB Schema Reference

Complete schema for the Fronius Modbus MQTT InfluxDB integration.

Bucket: fronius (configurable via INFLUXDB_BUCKET) Write Mode: Batched (100 points, 10s flush interval, 2s jitter) Rate Limiting: Configurable per-device write interval (default: 5s) Publish Mode: changed (only write when values change) or all


Measurement: fronius_inverter

Data from Fronius inverters (SunSpec Models 101-103, 160).

Tags

Tag Type Description Example
device_id string Modbus unit ID 1, 2, 3, 4
device_type string Always inverter inverter
model string Device model name Fronius Symo Advanced 20.0-3-M
serial_number string Device serial number 34559971
status string SunSpec operating status name I_STATUS_MPPT, I_STATUS_FAULT

Fields - AC Output

Field Type Unit Description
ac_power float W AC power output
ac_current float A Total AC current
ac_current_a float A Phase A current
ac_current_b float A Phase B current (three-phase)
ac_current_c float A Phase C current (three-phase)
ac_voltage_an float V Phase A-N voltage
ac_voltage_bn float V Phase B-N voltage (three-phase)
ac_voltage_cn float V Phase C-N voltage (three-phase)
ac_voltage_ab float V Phase A-B voltage (three-phase)
ac_voltage_bc float V Phase B-C voltage (three-phase)
ac_voltage_ca float V Phase C-A voltage (three-phase)
ac_frequency float Hz Grid frequency
power_factor float - Power factor (-1.0 to 1.0)
apparent_power float VA Apparent power
reactive_power float var Reactive power

Fields - DC Input

Field Type Unit Description
dc_power float W Total DC power input
dc_voltage float V DC voltage
dc_current float A DC current

Fields - Energy

Field Type Unit Description
lifetime_energy float Wh Total lifetime energy produced

Fields - Temperature

Field Type Unit Description
temp_cabinet float C Cabinet temperature
temp_heatsink float C Heatsink temperature
temp_transformer float C Transformer temperature
temp_other float C Other temperature sensor

Fields - Status & Events

Field Type Description
status_code int SunSpec operating status code
status_alarm bool Alarm flag (true when fault/alarm active)
event_count int Number of active fault events
events_json string JSON array of decoded events (only present when events active)

SunSpec Status Codes:

Code Name Description
0 OFF Inverter off
1 SLEEPING Auto-shutdown
2 STARTING Starting up
3 MPPT_FORCED Tracking (forced)
4 MPPT Tracking power point (normal operation)
5 THROTTLED Power limited (grid/temp)
6 SHUTTING_DOWN Shutting down
7 FAULT Fault condition
8 STANDBY Standby

events_json format:

[
  {
    "codes": [307, 522],
    "descriptions": ["DC low", "AC freq too high"],
    "class": "Fault"
  }
]

Each array element represents one event register (EvtVnd1-4). Fields:

  • codes - List of numeric SunSpec state codes
  • descriptions - Human-readable description for each code
  • class - Event classification from FroniusEventFlags.json

Fields - MPPT Strings (Model 160)

Dynamic fields per MPPT string (N = 1, 2, ...):

Field Type Unit Description
mppt_num_modules int - Number of MPPT modules
string{N}_current float A String N DC current
string{N}_voltage float V String N DC voltage
string{N}_power float W String N DC power
string{N}_energy float Wh String N lifetime energy
string{N}_temperature float C String N module temperature

Typical configurations:

  • Primo (single-phase): 2 strings (string1_*, string2_*)
  • Symo (three-phase): 2 strings (string1_*, string2_*)

Installed Inverters

device_id Model Rated Power Serial
1 Fronius Symo Advanced 20.0-3-M 20 kW 34559971
2 Fronius Symo Advanced 20.0-3-M 20 kW 34439632
3 Fronius Symo Advanced 17.5-3-M 17.5 kW 34312229
4 Fronius Symo 17.5-3-M 17.5 kW 31459301

Measurement: fronius_controls

Inverter immediate controls data (SunSpec Model 123). Polled every 60s, written only on value change.

Tags

Tag Type Description Example
device_id string Modbus unit ID 1, 2, 3, 4
device_type string Always inverter inverter
serial_number string Device serial number 34559971

Fields - Connection

Field Type Description
connected bool Grid connection state

Fields - Power Limit

Field Type Unit Description
power_limit_pct float % Active power output limit (100 = no limit)
power_limit_enabled bool - Power limit control enabled

Fields - Power Factor

Field Type Description
power_factor float Power factor setpoint (-1.0 to 1.0)
power_factor_enabled bool Power factor control enabled

Fields - Reactive Power (VAR)

Field Type Unit Description
var_enabled bool - Reactive power control enabled
var_wmax_pct float % Reactive power as % of WMax
var_max_pct float % Reactive power as % of VArMax

Measurement: fronius_storage

Battery storage data from inverters with storage support (SunSpec Model 124).

Tags

Tag Type Description Example
device_id string Modbus unit ID (inverter) 1
device_type string Always inverter inverter
serial_number string Inverter serial number 34559971

Fields

Field Type Unit Description
charge_state_pct float % State of charge
battery_voltage float V Internal battery voltage
max_charge_power float W Maximum charge power
charge_status_code float - Charge status enum (1=OFF, 2=EMPTY, 3=DISCHARGING, 4=CHARGING, 5=FULL, 6=HOLDING, 7=TESTING)
discharge_rate_pct float % Discharge rate (% of WDisChaMax)
charge_rate_pct float % Charge rate (% of WChaMax)
min_reserve_pct float % Minimum reserve percentage
available_storage_ah float Ah Available storage capacity
charge_ramp_rate float %/s Charge ramp rate (% WChaMax/sec)
discharge_ramp_rate float %/s Discharge ramp rate (% WChaMax/sec)
grid_charging_code float - Grid charging setting (0=PV, 1=GRID)

Measurement: fronius_meter

Data from Fronius Smart Meters (SunSpec Models 201-204).

Tags

Tag Type Description Example
device_id string Modbus unit ID 240
device_type string Always meter meter
model string Device model name Fronius Smart Meter TS 5kA-3
serial_number string Device serial number 40112233

Fields - Power

Field Type Unit Description
power_total float W Total active power (+ export, - import)
power_a float W Phase A active power
power_b float W Phase B active power
power_c float W Phase C active power
va_total float VA Total apparent power
va_a float VA Phase A apparent power
va_b float VA Phase B apparent power
va_c float VA Phase C apparent power
var_total float var Total reactive power
var_a float var Phase A reactive power
var_b float var Phase B reactive power
var_c float var Phase C reactive power

Fields - Voltage

Field Type Unit Description
voltage_ln_avg float V Line-to-neutral average voltage
voltage_an float V Phase A-N voltage
voltage_bn float V Phase B-N voltage
voltage_cn float V Phase C-N voltage
voltage_ll_avg float V Line-to-line average voltage
voltage_ab float V Phase A-B voltage
voltage_bc float V Phase B-C voltage
voltage_ca float V Phase C-A voltage

Fields - Current

Field Type Unit Description
current_total float A Total current
current_a float A Phase A current
current_b float A Phase B current
current_c float A Phase C current

Fields - Frequency & Power Factor

Field Type Unit Description
frequency float Hz Grid frequency
pf_avg float - Average power factor (-1.0 to 1.0)
pf_a float - Phase A power factor
pf_b float - Phase B power factor
pf_c float - Phase C power factor

Fields - Energy (Cumulative)

Field Type Unit Description
energy_exported float Wh Total energy exported to grid
energy_exported_a float Wh Phase A energy exported
energy_exported_b float Wh Phase B energy exported
energy_exported_c float Wh Phase C energy exported
energy_imported float Wh Total energy imported from grid
energy_imported_a float Wh Phase A energy imported
energy_imported_b float Wh Phase B energy imported
energy_imported_c float Wh Phase C energy imported

Installed Meters

device_id Model Type
240 Fronius Smart Meter TS 5kA-3 Three-phase

Example Flux Queries

Current inverter power by device

from(bucket: "fronius")
  |> range(start: -1h)
  |> filter(fn: (r) => r._measurement == "fronius_inverter")
  |> filter(fn: (r) => r._field == "ac_power")

Total solar production (all inverters)

from(bucket: "fronius")
  |> range(start: -24h)
  |> filter(fn: (r) => r._measurement == "fronius_inverter")
  |> filter(fn: (r) => r._field == "ac_power")
  |> aggregateWindow(every: 5m, fn: mean)
  |> group(columns: ["_field"])
  |> sum()

Grid import/export

from(bucket: "fronius")
  |> range(start: -24h)
  |> filter(fn: (r) => r._measurement == "fronius_meter")
  |> filter(fn: (r) => r._field == "power_total")
  |> aggregateWindow(every: 5m, fn: mean)

Active fault events

from(bucket: "fronius")
  |> range(start: -7d)
  |> filter(fn: (r) => r._measurement == "fronius_inverter")
  |> filter(fn: (r) => r._field == "events_json")

Throttling detection

from(bucket: "fronius")
  |> range(start: -7d)
  |> filter(fn: (r) => r._measurement == "fronius_inverter" and r._field == "ac_power")
  |> filter(fn: (r) => r.status == "I_STATUS_THROTTLED" or r.status == "I_STATUS_FAULT")
  |> group(columns: ["device_id", "status"])

MPPT string comparison

from(bucket: "fronius")
  |> range(start: -1d)
  |> filter(fn: (r) => r._measurement == "fronius_inverter")
  |> filter(fn: (r) => r._field == "string1_power" or r._field == "string2_power")
  |> group(columns: ["device_id", "_field"])

Inverter temperatures

from(bucket: "fronius")
  |> range(start: -1d)
  |> filter(fn: (r) => r._measurement == "fronius_inverter")
  |> filter(fn: (r) => r._field =~ /^temp_/)
  |> group(columns: ["device_id", "_field"])

Per-phase voltage balance (meter)

from(bucket: "fronius")
  |> range(start: -1h)
  |> filter(fn: (r) => r._measurement == "fronius_meter")
  |> filter(fn: (r) => r._field == "voltage_an" or r._field == "voltage_bn" or r._field == "voltage_cn")
  |> aggregateWindow(every: 1m, fn: mean)

Inverter controls status

from(bucket: "fronius")
  |> range(start: -7d)
  |> filter(fn: (r) => r._measurement == "fronius_controls")
  |> filter(fn: (r) => r._field == "power_limit_pct" or r._field == "connected")
  |> group(columns: ["device_id", "_field"])

Inverter status timeline

from(bucket: "fronius")
  |> range(start: -24h)
  |> filter(fn: (r) => r._measurement == "fronius_inverter" and r._field == "status_code")
  |> group(columns: ["device_id", "status"])

Write Configuration

Parameter Value Description
batch_size 100 Points per batch
flush_interval 10,000 ms Max time before flush
jitter_interval 2,000 ms Random delay to spread writes
retry_interval 5,000 ms Retry delay on failure
max_retries 3 Max retry attempts per batch
write_interval 5s (default) Min interval between writes per device
publish_mode changed Only write when values change (configurable)

Connection Resilience

  • Startup: 10 retry attempts with exponential backoff (2s to 60s)
  • Background reconnection thread if initial connection fails
  • Automatic reconnection every 30s until successful
  • Write errors trigger automatic reconnection detection