GridBoss Configuration

GridBoss is an advanced distribution monitoring and control system for LuxPower inverters. This guide covers setup and configuration.

Overview

GridBoss provides:

  • 🔌 House Backup - Easy whole-house backup configuration
  • Smart Load Control - Manage up to 4 configurable SmartLoads
  • 🔋 Generator Integration - Automatic start/stop control
  • ☀️ AC Coupling - Monitor up to 4 external solar systems
  • 📊 Split-Phase Monitoring - Individual L1, L2 tracking (USA standard)
  • Advanced Scheduling - Time-based automation with multiple schedules

⚠️ Important: Port Exclusivity & Configuration Sequence

Each of the 4 ports can be configured as either a SmartLoad or AC Coupling, but not both. The port mode determines which functionality is available for that specific port.

🔧 Configuration Sequence:

  1. First: Set the port mode (SmartLoadX_PortMode) to "Smart Load" or "Ac Coupled"
  2. Then: Configure the port-specific settings (switches, numbers, time schedules, etc.)

❌ Common Mistake: Trying to configure port settings before setting the port mode will result in unavailable/grayed-out entities.

Requirements

  • ✅ LuxPower inverter
  • ✅ Firmware code IAAB
  • ✅ GridBoss hardware unit
  • ✅ Integration v3.0.0+

Enabling GridBoss

New Installation

During initial setup:

  1. Check "GridBoss Connected" option
  2. Complete setup normally

Existing Installation

  1. Go to SettingsDevices & Services
  2. Find Monitor My Solar → Click Configure
  3. Select Update Settings
  4. Check "GridBoss Connected"
  5. Click Submit
  6. Integration will reload with GridBoss entities

GridBoss Entities

When enabled, GridBoss adds 190+ new entities:

Sensors (80+ entities)

GridBoss Status & Monitoring

  • sensor.dongle_XX_midboxStatus - GridBoss Status
  • sensor.dongle_XX_gridRMSVoltage - Grid RMS Voltage
  • sensor.dongle_XX_buRMSVoltage - BU (Backup) RMS Voltage
  • sensor.dongle_XX_genRMSVoltage - Generator RMS Voltage
  • sensor.dongle_XX_PhaseLockFreq - Phase Lock Frequency
  • sensor.dongle_XX_GridFreq - Grid Frequency
  • sensor.dongle_XX_GenFreq - Generator Frequency
  • sensor.dongle_XX_SmartPortMode - Smart Port Mode

Split-Phase Voltage Monitoring (L1/L2)

  • sensor.dongle_XX_gridL1RMSVoltage - Grid L1 RMS Voltage
  • sensor.dongle_XX_gridL2RMSVoltage - Grid L2 RMS Voltage
  • sensor.dongle_XX_buL1RMSVoltage - BU L1 RMS Voltage
  • sensor.dongle_XX_buL2RMSVoltage - BU L2 RMS Voltage
  • sensor.dongle_XX_genL1RMSVoltage - Generator L1 RMS Voltage
  • sensor.dongle_XX_genL2RMSVoltage - Generator L2 RMS Voltage

Split-Phase Current Monitoring (L1/L2)

  • sensor.dongle_XX_gridL1RMSCurrent - Grid L1 RMS Current
  • sensor.dongle_XX_gridL2RMSCurrent - Grid L2 RMS Current
  • sensor.dongle_XX_loadL1RMSCurrent - Load L1 RMS Current
  • sensor.dongle_XX_loadL2RMSCurrent - Load L2 RMS Current
  • sensor.dongle_XX_genL1RMSCurrent - Generator L1 RMS Current
  • sensor.dongle_XX_genL2RMSCurrent - Generator L2 RMS Current
  • sensor.dongle_XX_buL1RMSCurrent - BU L1 RMS Current
  • sensor.dongle_XX_buL2RMSCurrent - BU L2 RMS Current

SmartLoad Current Monitoring (4 SmartLoads)

  • sensor.dongle_XX_smartLoad1L1RMSCurrent - SmartLoad1 L1 RMS Current
  • sensor.dongle_XX_smartLoad1L2RMSCurrent - SmartLoad1 L2 RMS Current
  • sensor.dongle_XX_smartLoad2L1RMSCurrent - SmartLoad2 L1 RMS Current
  • sensor.dongle_XX_smartLoad2L2RMSCurrent - SmartLoad2 L2 RMS Current
  • sensor.dongle_XX_smartLoad3L1RMSCurrent - SmartLoad3 L1 RMS Current
  • sensor.dongle_XX_smartLoad3L2RMSCurrent - SmartLoad3 L2 RMS Current
  • sensor.dongle_XX_smartLoad4L1RMSCurrent - SmartLoad4 L1 RMS Current
  • sensor.dongle_XX_smartLoad4L2RMSCurrent - SmartLoad4 L2 RMS Current

Split-Phase Power Monitoring (L1/L2)

  • sensor.dongle_XX_gridL1ActivePower - Grid L1 Active Power
  • sensor.dongle_XX_gridL2ActivePower - Grid L2 Active Power
  • sensor.dongle_XX_loadL1ActivePower - Load L1 Active Power
  • sensor.dongle_XX_loadL2ActivePower - Load L2 Active Power
  • sensor.dongle_XX_genL1ActivePower - Generator L1 Active Power
  • sensor.dongle_XX_genL2ActivePower - Generator L2 Active Power
  • sensor.dongle_XX_buL1ActivePower - BU L1 Active Power
  • sensor.dongle_XX_buL2ActivePower - BU L2 Active Power

SmartLoad Power Monitoring (4 SmartLoads)

  • sensor.dongle_XX_smartLoad1L1ActivePower - SmartLoad1 L1 Active Power
  • sensor.dongle_XX_smartLoad1L2ActivePower - SmartLoad1 L2 Active Power
  • sensor.dongle_XX_smartLoad2L1ActivePower - SmartLoad2 L1 Active Power
  • sensor.dongle_XX_smartLoad2L2ActivePower - SmartLoad2 L2 Active Power
  • sensor.dongle_XX_smartLoad3L1ActivePower - SmartLoad3 L1 Active Power
  • sensor.dongle_XX_smartLoad3L2ActivePower - SmartLoad3 L2 Active Power
  • sensor.dongle_XX_smartLoad4L1ActivePower - SmartLoad4 L1 Active Power
  • sensor.dongle_XX_smartLoad4L2ActivePower - SmartLoad4 L2 Active Power

Energy Tracking (Today)

  • sensor.dongle_XX_eLoad_TodayAll - E Load Today All
  • sensor.dongle_XX_EtoGrid_TodayAll - E to Grid Today All
  • sensor.dongle_XX_EtoUser_TodayAll - E to User Today All
  • sensor.dongle_XX_Egen_TodayAll - E Gen Today All
  • sensor.dongle_XX_ESmartLoad1_TodayAll - E SmartLoad1 Today All
  • sensor.dongle_XX_ESmartLoad2_TodayAll - E SmartLoad2 Today All
  • sensor.dongle_XX_ESmartLoad3_TodayAll - E SmartLoad3 Today All
  • sensor.dongle_XX_ESmartLoad4_TodayAll - E SmartLoad4 Today All
  • sensor.dongle_XX_EAcouple1_TodayAll - E ACcouple1 Today All
  • sensor.dongle_XX_EAcouple2_TodayAll - E ACcouple2 Today All
  • sensor.dongle_XX_EAcouple3_TodayAll - E ACcouple3 Today All
  • sensor.dongle_XX_EAcouple4_TodayAll - E ACcouple4 Today All

Energy Tracking (Total)

  • sensor.dongle_XX_ELoad_total - E Load Total
  • sensor.dongle_XX_EBU_Total - E BU Total
  • sensor.dongle_XX_EtoGrid_total - E to Grid Total
  • sensor.dongle_XX_EtoUser_total - E to User Total
  • sensor.dongle_XX_Egen_total - E Gen Total
  • sensor.dongle_XX_ESmartLoad1_total - E SmartLoad1 Total
  • sensor.dongle_XX_ESmartLoad2_total - E SmartLoad2 Total
  • sensor.dongle_XX_ESmartLoad3_total - E SmartLoad3 Total
  • sensor.dongle_XX_ESmartLoad4_total - E SmartLoad4 Total
  • sensor.dongle_XX_EAcouple1_total - E ACcouple1 Total
  • sensor.dongle_XX_EAcouple2_total - E ACcouple2 Total
  • sensor.dongle_XX_EAcouple3_total - E ACcouple3 Total
  • sensor.dongle_XX_EAcouple4_total - E ACcouple4 Total
  • sensor.dongle_XX_MIDBoox_ACType - MIDBox AC Type

Switches (17 entities)

Generator Control

  • switch.dongle_XX_Generator_enable - Generator Enable

SmartLoad Control (4 SmartLoads)

  • switch.dongle_XX_SmartLoad1_Enable - SmartLoad1 Enable
  • switch.dongle_XX_SmartLoad2_Enable - SmartLoad2 Enable
  • switch.dongle_XX_SmartLoad3_Enable - SmartLoad3 Enable
  • switch.dongle_XX_SmartLoad4_Enable - SmartLoad4 Enable
  • switch.dongle_XX_SmartLoad1_GridOn - SmartLoad1 Grid On
  • switch.dongle_XX_SmartLoad2_GridOn - SmartLoad2 Grid On
  • switch.dongle_XX_SmartLoad3_GridOn - SmartLoad3 Grid On
  • switch.dongle_XX_SmartLoad4_GridOn - SmartLoad4 Grid On
  • switch.dongle_XX_SmartLoad1_Shedding - SmartLoad1 Shedding
  • switch.dongle_XX_SmartLoad2_Shedding - SmartLoad2 Shedding
  • switch.dongle_XX_SmartLoad3_Shedding - SmartLoad3 Shedding
  • switch.dongle_XX_SmartLoad4_Shedding - SmartLoad4 Shedding

AC Coupling Control (4 AC Coupling Ports)

  • switch.dongle_XX_ACcouple1_Enable - ACcouple1 Enable
  • switch.dongle_XX_ACcouple2_Enable - ACcouple2 Enable
  • switch.dongle_XX_ACcouple3_Enable - ACcouple3 Enable
  • switch.dongle_XX_ACcouple4_Enable - ACcouple4 Enable

Number Entities (56 entities)

Generator Settings

  • number.dongle_XX_Generator_Warmup - Generator Warmup Time (0-600s)
  • number.dongle_XX_Generator_CoolDown - Generator Cool Down Time (0-600s)
  • number.dongle_XX_Generator_Exercise_Period - Generator Exercise Period (0-365d)

SmartLoad SOC Settings (4 SmartLoads)

  • number.dongle_XX_SmartLoad1_StartSOC - SmartLoad1 Start SOC (0-100%)
  • number.dongle_XX_SmartLoad1_EndSOC - SmartLoad1 End SOC (0-100%)
  • number.dongle_XX_SmartLoad2_StartSOC - SmartLoad2 Start SOC (0-100%)
  • number.dongle_XX_SmartLoad2_EndSOC - SmartLoad2 End SOC (0-100%)
  • number.dongle_XX_SmartLoad3_StartSOC - SmartLoad3 Start SOC (0-100%)
  • number.dongle_XX_SmartLoad3_EndSOC - SmartLoad3 End SOC (0-100%)
  • number.dongle_XX_SmartLoad4_StartSOC - SmartLoad4 Start SOC (0-100%)
  • number.dongle_XX_SmartLoad4_EndSOC - SmartLoad4 End SOC (0-100%)

SmartLoad Voltage Settings (4 SmartLoads)

  • number.dongle_XX_SmartLoad1_StartVolt - SmartLoad1 Start Voltage (40-60V)
  • number.dongle_XX_SmartLoad1_EndVolt - SmartLoad1 End Voltage (40-60V)
  • number.dongle_XX_SmartLoad2_StartVolt - SmartLoad2 Start Voltage (40-60V)
  • number.dongle_XX_SmartLoad2_EndVolt - SmartLoad2 End Voltage (40-60V)
  • number.dongle_XX_SmartLoad3_StartVolt - SmartLoad3 Start Voltage (40-60V)
  • number.dongle_XX_SmartLoad3_EndVolt - SmartLoad3 End Voltage (40-60V)
  • number.dongle_XX_SmartLoad4_StartVolt - SmartLoad4 Start Voltage (40-60V)
  • number.dongle_XX_SmartLoad4_EndVolt - SmartLoad4 End Voltage (40-60V)

AC Coupling SOC Settings (4 AC Coupling Ports)

  • number.dongle_XX_ACcouple1_StartSOC - ACcouple1 Start SOC (0-100%)
  • number.dongle_XX_ACcouple1_EndSOC - ACcouple1 End SOC (0-100%)
  • number.dongle_XX_ACcouple2_StartSOC - ACcouple2 Start SOC (0-100%)
  • number.dongle_XX_ACcouple2_EndSOC - ACcouple2 End SOC (0-100%)
  • number.dongle_XX_ACcouple3_StartSOC - ACcouple3 Start SOC (0-100%)
  • number.dongle_XX_ACcouple3_EndSOC - ACcouple3 End SOC (0-100%)
  • number.dongle_XX_ACcouple4_StartSOC - ACcouple4 Start SOC (0-100%)
  • number.dongle_XX_ACcouple4_EndSOC - ACcouple4 End SOC (0-100%)

AC Coupling Voltage Settings (4 AC Coupling Ports)

  • number.dongle_XX_ACcouple1_StartVolt - ACcouple1 Start Voltage (40-60V)
  • number.dongle_XX_ACcouple1_EndVolt - ACcouple1 End Voltage (40-60V)
  • number.dongle_XX_ACcouple2_StartVolt - ACcouple2 Start Voltage (40-60V)
  • number.dongle_XX_ACcouple2_EndVolt - ACcouple2 End Voltage (40-60V)
  • number.dongle_XX_ACcouple3_StartVolt - ACcouple3 Start Voltage (40-60V)
  • number.dongle_XX_ACcouple3_EndVolt - ACcouple3 End Voltage (40-60V)
  • number.dongle_XX_ACcouple4_StartVolt - ACcouple4 Start Voltage (40-60V)
  • number.dongle_XX_ACcouple4_EndVolt - ACcouple4 End Voltage (40-60V)

Shedding Settings (4 SmartLoads)

  • number.dongle_XX_SmartLoad1_SheddingStartPv_Power - SmartLoad1 Shedding Start PV Power (0-10000W)
  • number.dongle_XX_SmartLoad2_SheddingStartPv_Power - SmartLoad2 Shedding Start PV Power (0-10000W)
  • number.dongle_XX_SmartLoad3_SheddingStartPv_Power - SmartLoad3 Shedding Start PV Power (0-10000W)
  • number.dongle_XX_SmartLoad4_SheddingStartPv_Power - SmartLoad4 Shedding Start PV Power (0-10000W)
  • number.dongle_XX_SmartLoad1_SheddingStartSOC - SmartLoad1 Shedding Start SOC (0-100%)
  • number.dongle_XX_SmartLoad1_SheddingEndSOC - SmartLoad1 Shedding End SOC (0-100%)
  • number.dongle_XX_SmartLoad2_SheddingStartSOC - SmartLoad2 Shedding Start SOC (0-100%)
  • number.dongle_XX_SmartLoad2_SheddingEndSOC - SmartLoad2 Shedding End SOC (0-100%)
  • number.dongle_XX_SmartLoad3_SheddingStartSOC - SmartLoad3 Shedding Start SOC (0-100%)
  • number.dongle_XX_SmartLoad3_SheddingEndSOC - SmartLoad3 Shedding End SOC (0-100%)
  • number.dongle_XX_SmartLoad4_SheddingStartSOC - SmartLoad4 Shedding Start SOC (0-100%)
  • number.dongle_XX_SmartLoad4_SheddingEndSOC - SmartLoad4 Shedding End SOC (0-100%)
  • number.dongle_XX_SmartLoad1_SheddingStartVolt - SmartLoad1 Shedding Start Voltage (40-60V)
  • number.dongle_XX_SmartLoad1_SheddingEndVolt - SmartLoad1 Shedding End Voltage (40-60V)
  • number.dongle_XX_SmartLoad2_SheddingStartVolt - SmartLoad2 Shedding Start Voltage (40-60V)
  • number.dongle_XX_SmartLoad2_SheddingEndVolt - SmartLoad2 Shedding End Voltage (40-60V)
  • number.dongle_XX_SmartLoad3_SheddingStartVolt - SmartLoad3 Shedding Start Voltage (40-60V)
  • number.dongle_XX_SmartLoad3_SheddingEndVolt - SmartLoad3 Shedding End Voltage (40-60V)
  • number.dongle_XX_SmartLoad4_SheddingStartVolt - SmartLoad4 Shedding Start Voltage (40-60V)
  • number.dongle_XX_SmartLoad4_SheddingEndVolt - SmartLoad4 Shedding End Voltage (40-60V)
  • number.dongle_XX_Flash_5060hz - Flash 50/60Hz (0-1)
  • number.dongle_XX_NEC_120CurrLimit - NEC 120 Current Limit (0-200A)

Select Entities (8 entities)

Port Mode Configuration (4 Ports - Exclusive Configuration)

⚠️ Each port can only be configured as ONE mode at a time:

  • select.dongle_XX_SmartLoad1_PortMode - Smart Port 1 (Does Not Operate, Smart Load, Ac Coupled)
  • select.dongle_XX_SmartLoad2_PortMode - Smart Port 2 (Does Not Operate, Smart Load, Ac Coupled)
  • select.dongle_XX_SmartLoad3_PortMode - Smart Port 3 (Does Not Operate, Smart Load, Ac Coupled)
  • select.dongle_XX_SmartLoad4_PortMode - Smart Port 4 (Does Not Operate, Smart Load, Ac Coupled)

Port Mode Options:

  • "Does Not Operate" - Port is disabled
  • "Smart Load" - Port functions as a SmartLoad (load control)
  • "Ac Coupled" - Port functions as AC Coupling (external solar monitoring)

SmartLoad Mode Configuration (Only Available When Port Mode = "Smart Load")

  • select.dongle_XX_SmartLoad1_SOC_Volt - Smart Load 1 Mode (Time, SOC/Volt)
  • select.dongle_XX_SmartLoad2_SOC_Volt - Smart Load 2 Mode (Time, SOC/Volt)
  • select.dongle_XX_SmartLoad3_SOC_Volt - Smart Load 3 Mode (Time, SOC/Volt)
  • select.dongle_XX_SmartLoad4_SOC_Volt - Smart Load 4 Mode (Time, SOC/Volt)

SmartLoad Mode Options:

  • "Time" - SmartLoad operates based on time schedules
  • "SOC/Volt" - SmartLoad operates based on battery SOC/voltage thresholds

Time Entities (48 entities)

SmartLoad Time Scheduling (4 SmartLoads, 3 schedules each)

Each SmartLoad has 3 time schedules (Start0/End0, Start1/End1, Start2/End2):

  • time.dongle_XX_SmartLoad1Start0 - SmartLoad1 Start0
  • time.dongle_XX_SmartLoad1End0 - SmartLoad1 End0
  • time.dongle_XX_SmartLoad1Start1 - SmartLoad1 Start1
  • time.dongle_XX_SmartLoad1End1 - SmartLoad1 End1
  • time.dongle_XX_SmartLoad1Start2 - SmartLoad1 Start2
  • time.dongle_XX_SmartLoad1End2 - SmartLoad1 End2
  • time.dongle_XX_SmartLoad2Start0 - SmartLoad2 Start0
  • time.dongle_XX_SmartLoad2End0 - SmartLoad2 End0
  • time.dongle_XX_SmartLoad2Start1 - SmartLoad2 Start1
  • time.dongle_XX_SmartLoad2End1 - SmartLoad2 End1
  • time.dongle_XX_SmartLoad2Start2 - SmartLoad2 Start2
  • time.dongle_XX_SmartLoad2End2 - SmartLoad2 End2
  • time.dongle_XX_SmartLoad3Start0 - SmartLoad3 Start0
  • time.dongle_XX_SmartLoad3End0 - SmartLoad3 End0
  • time.dongle_XX_SmartLoad3Start1 - SmartLoad3 Start1
  • time.dongle_XX_SmartLoad3End1 - SmartLoad3 End1
  • time.dongle_XX_SmartLoad3Start2 - SmartLoad3 Start2
  • time.dongle_XX_SmartLoad3End2 - SmartLoad3 End2
  • time.dongle_XX_SmartLoad4Start0 - SmartLoad4 Start0
  • time.dongle_XX_SmartLoad4End0 - SmartLoad4 End0
  • time.dongle_XX_SmartLoad4Start1 - SmartLoad4 Start1
  • time.dongle_XX_SmartLoad4End1 - SmartLoad4 End1
  • time.dongle_XX_SmartLoad4Start2 - SmartLoad4 Start2
  • time.dongle_XX_SmartLoad4End2 - SmartLoad4 End2

AC Coupling Time Scheduling (4 AC Coupling Ports, 3 schedules each)

Each AC Coupling port has 3 time schedules (Start0/End0, Start1/End1, Start2/End2):

  • time.dongle_XX_ACcouple1Start0 - ACcouple1 Start0
  • time.dongle_XX_ACcouple1End0 - ACcouple1 End0
  • time.dongle_XX_ACcouple1Start1 - ACcouple1 Start1
  • time.dongle_XX_ACcouple1End1 - ACcouple1 End1
  • time.dongle_XX_ACcouple1Start2 - ACcouple1 Start2
  • time.dongle_XX_ACcouple1End2 - ACcouple1 End2
  • time.dongle_XX_ACcouple2Start0 - ACcouple2 Start0
  • time.dongle_XX_ACcouple2End0 - ACcouple2 End0
  • time.dongle_XX_ACcouple2Start1 - ACcouple2 Start1
  • time.dongle_XX_ACcouple2End1 - ACcouple2 End1
  • time.dongle_XX_ACcouple2Start2 - ACcouple2 Start2
  • time.dongle_XX_ACcouple2End2 - ACcouple2 End2
  • time.dongle_XX_ACcouple3Start0 - ACcouple3 Start0
  • time.dongle_XX_ACcouple3End0 - ACcouple3 End0
  • time.dongle_XX_ACcouple3Start1 - ACcouple3 Start1
  • time.dongle_XX_ACcouple3End1 - ACcouple3 End1
  • time.dongle_XX_ACcouple3Start2 - ACcouple3 Start2
  • time.dongle_XX_ACcouple3End2 - ACcouple3 End2
  • time.dongle_XX_ACcouple4Start0 - ACcouple4 Start0
  • time.dongle_XX_ACcouple4End0 - ACcouple4 End0
  • time.dongle_XX_ACcouple4Start1 - ACcouple4 Start1
  • time.dongle_XX_ACcouple4End1 - ACcouple4 End1
  • time.dongle_XX_ACcouple4Start2 - ACcouple4 Start2
  • time.dongle_XX_ACcouple4End2 - ACcouple4 End2

Configuration Examples

Basic SmartLoad Control

Control SmartLoads based on battery SOC:

automation:
  - alias: "Disable non-essential SmartLoads on low battery"
    trigger:
      - platform: numeric_state
        entity_id: sensor.dongle_12_34_56_78_90_ab_soc
        below: 20
    action:
      - service: switch.turn_off
        entity_id:
          - switch.dongle_12_34_56_78_90_ab_SmartLoad3_Enable
          - switch.dongle_12_34_56_78_90_ab_SmartLoad4_Enable

Generator Auto-Start

Start generator on low battery:

automation:
  - alias: "Auto-start generator"
    trigger:
      - platform: numeric_state
        entity_id: sensor.dongle_12_34_56_78_90_ab_vbat
        below: 47.5
    condition:
      - condition: state
        entity_id: switch.dongle_12_34_56_78_90_ab_Generator_enable
        state: "off"
    action:
      - service: switch.turn_on
        entity_id: switch.dongle_12_34_56_78_90_ab_Generator_enable
      - service: notify.mobile_app
        data:
          message: "Generator started - Low battery voltage"

Time-Based SmartLoad Management

Schedule SmartLoads for off-peak usage:

# First, configure the port as a SmartLoad with Time mode
script:
  setup_smartload_time_mode:
    sequence:
      # Step 1: Set port mode to Smart Load (REQUIRED FIRST)
      - service: select.select_option
        target:
          entity_id: select.dongle_12_34_56_78_90_ab_SmartLoad1_PortMode
        data:
          option: "Smart Load"
      # Step 2: Set SmartLoad mode to Time
      - service: select.select_option
        target:
          entity_id: select.dongle_12_34_56_78_90_ab_SmartLoad1_SOC_Volt
        data:
          option: "Time"

# Then use automations to control the SmartLoad
automation:
  - alias: "Enable water heater off-peak"
    trigger:
      - platform: time
        at: "23:00:00"
    action:
      - service: switch.turn_on
        entity_id: switch.dongle_12_34_56_78_90_ab_SmartLoad1_Enable
      
  - alias: "Disable water heater peak"
    trigger:
      - platform: time
        at: "06:00:00"
    action:
      - service: switch.turn_off
        entity_id: switch.dongle_12_34_56_78_90_ab_SmartLoad1_Enable

SmartLoad SOC-Based Control

Configure SmartLoad to operate based on battery SOC:

script:
  configure_smartload_soc:
    sequence:
      # Step 1: Set port mode to Smart Load (REQUIRED FIRST)
      - service: select.select_option
        target:
          entity_id: select.dongle_12_34_56_78_90_ab_SmartLoad1_PortMode
        data:
          option: "Smart Load"
      # Step 2: Set SmartLoad mode to SOC/Volt
      - service: select.select_option
        target:
          entity_id: select.dongle_12_34_56_78_90_ab_SmartLoad1_SOC_Volt
        data:
          option: "SOC/Volt"
      # Step 3: Configure SOC thresholds
      - service: number.set_value
        target:
          entity_id: number.dongle_12_34_56_78_90_ab_SmartLoad1_StartSOC
        data:
          value: 80  # Start when SOC > 80%
      - service: number.set_value
        target:
          entity_id: number.dongle_12_34_56_78_90_ab_SmartLoad1_EndSOC
        data:
          value: 20  # Stop when SOC < 20%

AC Coupling Configuration

Configure AC coupling for external solar:

script:
  configure_ac_coupling:
    sequence:
      # First, set port mode to AC Coupled (this disables SmartLoad functionality)
      - service: select.select_option
        target:
          entity_id: select.dongle_12_34_56_78_90_ab_SmartLoad1_PortMode
        data:
          option: "Ac Coupled"
      # Then enable AC coupling
      - service: switch.turn_on
        entity_id: switch.dongle_12_34_56_78_90_ab_ACcouple1_Enable
      # Configure AC coupling SOC thresholds
      - service: number.set_value
        target:
          entity_id: number.dongle_12_34_56_78_90_ab_ACcouple1_StartSOC
        data:
          value: 90  # Start AC coupling when SOC > 90%

Port Configuration Examples

Example 1: Mixed Port Configuration

script:
  configure_mixed_ports:
    sequence:
      # Port 1: SmartLoad
      - service: select.select_option
        target:
          entity_id: select.dongle_12_34_56_78_90_ab_SmartLoad1_PortMode
        data:
          option: "Smart Load"
      - service: select.select_option
        target:
          entity_id: select.dongle_12_34_56_78_90_ab_SmartLoad1_SOC_Volt
        data:
          option: "SOC/Volt"
      
      # Port 2: AC Coupling
      - service: select.select_option
        target:
          entity_id: select.dongle_12_34_56_78_90_ab_SmartLoad2_PortMode
        data:
          option: "Ac Coupled"
      - service: switch.turn_on
        entity_id: switch.dongle_12_34_56_78_90_ab_ACcouple2_Enable
      
      # Port 3: Disabled
      - service: select.select_option
        target:
          entity_id: select.dongle_12_34_56_78_90_ab_SmartLoad3_PortMode
        data:
          option: "Does Not Operate"
      
      # Port 4: SmartLoad with Time mode
      - service: select.select_option
        target:
          entity_id: select.dongle_12_34_56_78_90_ab_SmartLoad4_PortMode
        data:
          option: "Smart Load"
      - service: select.select_option
        target:
          entity_id: select.dongle_12_34_56_78_90_ab_SmartLoad4_SOC_Volt
        data:
          option: "Time"

Example 2: Converting Port from SmartLoad to AC Coupling

script:
  convert_port_to_ac_coupling:
    sequence:
      # Step 1: Disable SmartLoad first
      - service: switch.turn_off
        entity_id: switch.dongle_12_34_56_78_90_ab_SmartLoad1_Enable
      
      # Step 2: Change port mode to AC Coupled
      - service: select.select_option
        target:
          entity_id: select.dongle_12_34_56_78_90_ab_SmartLoad1_PortMode
        data:
          option: "Ac Coupled"
      
      # Step 3: Enable AC coupling
      - service: switch.turn_on
        entity_id: switch.dongle_12_34_56_78_90_ab_ACcouple1_Enable

Split-Phase Monitoring

Create a card showing split-phase balance (USA standard):

type: entities
title: Split-Phase Balance
entities:
  - entity: sensor.dongle_12_34_56_78_90_ab_gridL1ActivePower
    name: L1 Power
  - entity: sensor.dongle_12_34_56_78_90_ab_gridL2ActivePower
    name: L2 Power
  - type: divider
  - entity: sensor.dongle_12_34_56_78_90_ab_gridL1RMSVoltage
    name: L1 Voltage
  - entity: sensor.dongle_12_34_56_78_90_ab_gridL2RMSVoltage
    name: L2 Voltage

Advanced Features

AC Coupling

Monitor external solar systems:

  1. Enable AC coupling:
switch.dongle_12_34_56_78_90_ab_ACcouple1_Enable: on
  1. Monitor AC-coupled power:
sensor.dongle_12_34_56_78_90_ab_EAcouple1_TodayAll  # Today's energy
sensor.dongle_12_34_56_78_90_ab_EAcouple1_total     # Total energy

SmartLoad Shedding

Configure SmartLoad shedding based on PV power and SOC:

script:
  configure_smartload_shedding:
    sequence:
      - service: switch.turn_on
        entity_id: switch.dongle_12_34_56_78_90_ab_SmartLoad1_Shedding
      - service: number.set_value
        target:
          entity_id: number.dongle_12_34_56_78_90_ab_SmartLoad1_SheddingStartPv_Power
        data:
          value: 5000  # Start shedding when PV > 5kW
      - service: number.set_value
        target:
          entity_id: number.dongle_12_34_56_78_90_ab_SmartLoad1_SheddingStartSOC
        data:
          value: 30  # Start shedding when SOC < 30%

Generator Management

Configure generator with warmup and cooldown periods:

script:
  configure_generator:
    sequence:
      - service: number.set_value
        target:
          entity_id: number.dongle_12_34_56_78_90_ab_Generator_Warmup
        data:
          value: 60  # 60 second warmup
      - service: number.set_value
        target:
          entity_id: number.dongle_12_34_56_78_90_ab_Generator_CoolDown
        data:
          value: 120  # 2 minute cooldown
      - service: number.set_value
        target:
          entity_id: number.dongle_12_34_56_78_90_ab_Generator_Exercise_Period
        data:
          value: 7  # Exercise weekly

Dashboard Examples

GridBoss Overview Card

type: vertical-stack
cards:
  - type: entities
    title: GridBoss Status
    entities:
      - entity: sensor.dongle_12_34_56_78_90_ab_gridL1ActivePower
        name: Grid L1 Power
      - entity: sensor.dongle_12_34_56_78_90_ab_gridL2ActivePower
        name: Grid L2 Power
      - entity: sensor.dongle_12_34_56_78_90_ab_loadL1ActivePower
        name: Load L1 Power
      - entity: sensor.dongle_12_34_56_78_90_ab_loadL2ActivePower
        name: Load L2 Power
      - entity: sensor.dongle_12_34_56_78_90_ab_genL1ActivePower
        name: Generator L1 Power
      - entity: sensor.dongle_12_34_56_78_90_ab_genL2ActivePower
        name: Generator L2 Power
      
  - type: horizontal-stack
    cards:
      - type: gauge
        entity: sensor.dongle_12_34_56_78_90_ab_gridL1RMSVoltage
        name: L1 Voltage
        min: 200
        max: 260
      - type: gauge
        entity: sensor.dongle_12_34_56_78_90_ab_gridL2RMSVoltage
        name: L2 Voltage
        min: 200
        max: 260

SmartLoad Control Panel

type: entities
title: SmartLoad Control
entities:
  - entity: switch.dongle_12_34_56_78_90_ab_SmartLoad1_Enable
    name: Water Heater
    secondary_info: last-changed
  - entity: switch.dongle_12_34_56_78_90_ab_SmartLoad2_Enable
    name: Pool Pump
  - entity: switch.dongle_12_34_56_78_90_ab_SmartLoad3_Enable
    name: Air Conditioner
  - entity: switch.dongle_12_34_56_78_90_ab_SmartLoad4_Enable
    name: EV Charger

AC Coupling Monitoring

type: entities
title: AC Coupling Status
entities:
  - entity: switch.dongle_12_34_56_78_90_ab_ACcouple1_Enable
    name: AC Couple 1
  - entity: switch.dongle_12_34_56_78_90_ab_ACcouple2_Enable
    name: AC Couple 2
  - entity: switch.dongle_12_34_56_78_90_ab_ACcouple3_Enable
    name: AC Couple 3
  - entity: switch.dongle_12_34_56_78_90_ab_ACcouple4_Enable
    name: AC Couple 4
  - type: divider
  - entity: sensor.dongle_12_34_56_78_90_ab_EAcouple1_TodayAll
    name: AC Couple 1 Today
  - entity: sensor.dongle_12_34_56_78_90_ab_EAcouple2_TodayAll
    name: AC Couple 2 Today
  - entity: sensor.dongle_12_34_56_78_90_ab_EAcouple3_TodayAll
    name: AC Couple 3 Today
  - entity: sensor.dongle_12_34_56_78_90_ab_EAcouple4_TodayAll
    name: AC Couple 4 Today

Troubleshooting

GridBoss Entities Not Appearing

  1. Verify firmware code is IAAB:

    • Check in integration configuration status
    • Look in Home Assistant logs
  2. Ensure GridBoss is enabled:

    • Integration → Configure → Update Settings
    • Check "GridBoss Connected"
  3. Restart Home Assistant after enabling

Generator Not Starting

  1. Check generator is enabled:

    • switch.dongle_12_34_56_78_90_ab_Generator_enable
  2. Verify generator settings:

    • number.dongle_12_34_56_78_90_ab_Generator_Warmup
    • number.dongle_12_34_56_78_90_ab_Generator_CoolDown
  3. Check physical connections

SmartLoad Control Not Working

  1. First, verify port mode is set to Smart Load:

    • select.dongle_12_34_56_78_90_ab_SmartLoad1_PortMode = "Smart Load"
    • Critical: Port must be in "Smart Load" mode before any SmartLoad settings are available
  2. Verify SmartLoad is enabled:

    • switch.dongle_12_34_56_78_90_ab_SmartLoad1_Enable (etc.)
  3. Check SmartLoad mode configuration:

    • select.dongle_12_34_56_78_90_ab_SmartLoad1_SOC_Volt (Time or SOC/Volt)
  4. Verify SOC/voltage settings (only available if mode is SOC/Volt):

    • number.dongle_12_34_56_78_90_ab_SmartLoad1_StartSOC
    • number.dongle_12_34_56_78_90_ab_SmartLoad1_EndSOC
  5. Monitor SmartLoad current/power sensors:

    • sensor.dongle_12_34_56_78_90_ab_smartLoad1L1RMSCurrent
    • sensor.dongle_12_34_56_78_90_ab_smartLoad1L1ActivePower

AC Coupling Not Working

  1. First, verify port mode is set to AC Coupled:

    • select.dongle_12_34_56_78_90_ab_SmartLoad1_PortMode = "Ac Coupled"
    • Critical: Port must be in "Ac Coupled" mode before any AC Coupling settings are available
  2. Verify AC coupling is enabled:

    • switch.dongle_12_34_56_78_90_ab_ACcouple1_Enable
  3. Monitor AC coupling energy:

    • sensor.dongle_12_34_56_78_90_ab_EAcouple1_TodayAll

Port Mode Conflicts

  1. Cannot use both SmartLoad and AC Coupling on same port:

    • If port is set to "Smart Load", AC Coupling entities will be unavailable
    • If port is set to "Ac Coupled", SmartLoad entities will be unavailable
    • Change port mode first, then configure the desired functionality
  2. Configuration sequence is critical:

    • Step 1: Set port mode (SmartLoadX_PortMode) to "Smart Load" or "Ac Coupled"
    • Step 2: Configure port-specific settings (switches, numbers, time schedules)
    • ❌ Wrong: Trying to configure settings before setting port mode results in unavailable entities
  3. Entity availability based on port mode:

    • "Smart Load" mode: SmartLoad switches, SOC/Volt settings, time schedules available
    • "Ac Coupled" mode: AC Coupling switches, AC Coupling SOC/Volt settings, AC Coupling time schedules available
    • "Does Not Operate" mode: All port-specific entities unavailable

Best Practices

  1. Test Thoroughly: Test SmartLoad switching and generator control during installation
  2. Set Appropriate SOC/Voltage Limits: Configure SOC and voltage thresholds for SmartLoads
  3. Monitor Split-Phase Balance: Keep L1/L2 phases balanced for optimal performance
  4. Document Connections: Label all GridBoss connections clearly
  5. Regular Testing: Test generator auto-start monthly
  6. Configure Shedding: Set up SmartLoad shedding for grid stability
  7. Use Time Schedules: Configure multiple time schedules for flexible load management
  8. Monitor AC Coupling: Track external solar system performance
  9. Plan Port Configuration: Decide which ports will be SmartLoads vs AC Coupling before configuration
  10. Port Mode First: Always set port mode before configuring port-specific settings
  11. Understand Exclusivity: Remember that each port can only be one type at a time

Support

For GridBoss-specific issues:

  1. Include firmware code (IAAB) in reports
  2. List which GridBoss features are enabled
  3. Provide debug logs with GridBoss MQTT topics
  4. Include photos of physical connections if relevant