@JayHuLBL JayHuLBL commented Feb 19, 2025

This is a draft pull request.

@ViswanathanGanesh01 Please see the comments below:

  • Missing comments for instances in the classes, in folder Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.InductionMotors.BaseClasses.
  • The base classes do not have documentation and revision note.
  • There still some mixed use of the equation and connections in the equation section. For example, in class Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.InductionMotors.SquirrelCage.
  • Run unit test with Optimica, we can still see the following warnings. It shows that some self-connectings. And also, *** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.InductionMotors.Examples.SquirrelCageDrive: Access to component v not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'.
(py3_11_3) jianjunhu@ubuntu:~/GitFolder/modelica-buildings/Buildings$ ../bin/runUnitTests.py -s Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive -t optimica
Regression tests are only run for the following package:
  Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive
Number of models   : 2658
          blocks   : 635
          functions: 222
Using 4 of 4 processors to run unit tests for optimica.
Generated 8 regression tests.

*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.InductionMotors.Examples.SquirrelCageDrive: Access to component v not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.InductionMotors.Examples.SquirrelCageDrive: Access to component i not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.InductionMotors.Examples.SquirrelCageDrive: Access to component theta not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.InductionMotors.Examples.SquirrelCageDrive: Ignored connection from connector to itself
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.InductionMotors.Examples.SquirrelCageDrive: Ignored connection from connector to itself
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.Chiller: Access to component v not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.Chiller: Access to component i not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.Chiller: Access to component theta not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.Chiller: Ignored connection from connector to itself
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.Chiller: Ignored connection from connector to itself
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.Pump: Access to component v not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.Pump: Access to component i not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.Pump: Access to component theta not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.Pump: Ignored connection from connector to itself
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.Pump: Ignored connection from connector to itself
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.Pump: Ignored connection from connector to itself
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.InductionMotors.Examples.SquirrelCageStartUp: Access to component v not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.InductionMotors.Examples.SquirrelCageStartUp: Access to component i not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.InductionMotors.Examples.SquirrelCageStartUp: Access to component theta not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.InductionMotors.Examples.SquirrelCageStartUp: Ignored connection from connector to itself
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.InductionMotors.Examples.SquirrelCageStartUp: Ignored connection from connector to itself
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.HeatPump: Access to component v not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.HeatPump: Access to component i not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.HeatPump: Access to component theta not recommended, it is not present in constraining type of declaration 'replaceable Buildings.Electrical.Interfaces.BaseTerminal terminal'
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.HeatPump: Ignored connection from connector to itself
*** Warning: Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.HeatPump: Ignored connection from connector to itself
  • Run ../bin/verifyFiles.py , we have the following errors. It means the class does not documentation.
jianjunhu@ubuntu:~/GitFolder/modelica-buildings/Buildings$ ../bin/verifyFiles.py 
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/ThermoFluid/BaseClasses/package.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/ThermoFluid/BaseClasses/Power.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/RotorCurrent_d.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/CurrentBlock.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/CurrentCalculationQ.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/TorqueBlock.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/CurrentCalculationQ_VFD.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/RotorCurrent_q.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/VoltageConversion.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/RMS_Voltage.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/FrequencyConversion.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/SimVFD.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/StatorCurrent_d.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/SpeedBlock.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/CurrentCalculationD.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/StatorCurrent_q.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/CurrentCalculationD_VFD.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/BaseClasses/package.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_10HP_400V_50Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/Generic.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_100HP_460V_60Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_20HP_460V_60Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_20HP_400V_50Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_100HP_400V_50Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_50HP_460V_60Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_200HP_460V_60Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_5HP_460V_60Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_200HP_400V_50Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_5HP_400V_50Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_10HP_460V_60Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_50HP_400V_50Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_150HP_460V_60Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/IM_150HP_400V_50Hz.mo' does not contain required string 'documentation'.
*** Error:  File 'Electrical/AC/ThreePhasesBalanced/Loads/MotorDrive/InductionMotors/Data/package.mo' does not contain required string 'documentation'.
*** Terminating due to found errors in examined files.
  • Classes (except validation and example models) should have defaultComponentName. See for example
  • For all the example and validation models, make sure the .mos script settings are consistent with the one in .mo file. For example, in class Buildings.Electrical.AC.ThreePhasesBalanced.Loads.MotorDrive.Coupled.Examples.Pump, it has annotation (experiment(Tolerance=1e-6,StopTime=600, StartTime=400),. But the corresponding .mos script has tolerance=1e-6,startTime=0, stopTime=200, .

…lanced/Loads/Examples/MotorDrive/InductionMotors/BaseClasses directory
…lanced/Loads/Examples/MotorDrive/InductionMotors/Examples directory
…lanced/Loads/MotorDrive/Coupled/Examples directory
@JayHuLBL JayHuLBL marked this pull request as ready for review October 17, 2025 20:12
Copy link
Copy Markdown
Contributor Author

@JayHuLBL JayHuLBL left a comment

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

@ViswanathanGanesh01 See the inline comments.

@JayHuLBL
Copy link
Copy Markdown
Contributor Author

@ViswanathanGanesh01 It will be ready for Michael to review after the CI tests passed.